Regulation 47, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Inter-locks and protection for use of electricity at voltage exceeding 650 V
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 47
Text of regulation 47
Inter-locks and protection for use of electricity at voltage exceeding 650 V
47. Inter-locks and protection for use of electricity at voltage exceeding 650 V. – (1) The owner shall ensure
the following, namely: –
(i) isolators and the controlling circuit breakers shall be inter-locked so that the isolators cannot be
operated unless the corresponding breaker is in open position;
(ii) isolators and the corresponding earthing switches shall be inter-locked so that no earthing switch can
be closed unless and until the corresponding isolator is in open position;
(iii) where two or more supplies are not intended to be operated in parallel, the respective circuit breakers
or linked switches controlling the supplies shall be inter-locked to prevent possibility of any inadvertent
paralleling or backfeed;
(iv) when two or more transformers are operated in parallel, the system shall be so arranged as to trip the
secondary breaker of the transformer in case the primary breaker of that transformer trips;
(v) all gates or doors which provide access to live parts of an installation shall be inter-locked in such a
way that these cannot be opened unless the live parts are made dead and proper discharging and earthing of
these parts shall be ensured before any person comes in close proximity of such parts; and
(vi) where two or more generators operate in parallel and neutral switching is adopted, inter-lock shall be
provided to ensure that the generator breaker cannot be closed unless one of the neutrals is connected to the
earthing system.
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 119
(2) The following protection shall be provided in all systems and circuits to automatically disconnect the
supply under abnormal conditions, namely: –
(i) over current protection to disconnect the supply automatically if the rated current of the equipment,
cable or supply line is exceeded for a time which the equipment, cable or supply line is not designed to
withstand;
(ii) earth fault or earth leakage protection to disconnect the supply automatically, if the earth fault current
exceeds the limit of current for keeping the contact potential within the reasonable values;
(iii) buchholz relay, pressure relief device and winding and oil temperature protection with alarm and trip
contacts shall be provided on all transformers of ratings 1000 kVA and above;
(iv) transformers of capacity 10 MVA and above shall be protected against incipient faults by differential
protection;
(v) all generators with rating of 100 kVA and above shall be protected against earth fault or leakage;
(vi) all generators of rating 1000 kVA and above shall be protected against faults within the generator
winding using restricted earth fault protection or differential protection or by both;
(vii) high speed bus bar differential protection along with local breaker back up protection shall be
commissioned and shall always be available at all 132 kV and above voltage substations and switching
stations and generating stations connected with the grid:
Provided that in respect of existing 132 kV substations and switching stations having more than one
incoming feeders, the high speed bus bar differential protection along with local breaker back up protection,
shall be commissioned and shall always be available; and
(viii) in addition to above, all electrical protection system for generating stations, substations and
transmission lines shall be as per the regulations notified by the Authority under clause (e) of sub-section
(2) of section 177 of the Act.