Regulation 48, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Testing, Operation and Maintenance
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 48
Text of regulation 48
Testing, Operation and Maintenance
48. Testing, Operation and Maintenance. – (1) Before the approval is accorded by the Electrical Inspector under
regulation 45, the manufacturer‟s test certificates shall, if required, be produced for all the type, acceptance and
routine tests as required under the relevant standards.
(2) No new apparatus, cable or supply line of voltage exceeding 650 V shall be commissioned unless such
apparatus, cable or supply line are subjected to site tests as per relevant standards.
(3) No apparatus, cable or supply line of voltage exceeding 650 V which has been kept disconnected for a period
of six months or more from the system for alterations or repair, shall be connected to the system until such
apparatus, cable or supply line are subjected to the site tests as per relevant standards.
(4) Notwithstanding the provisions of this regulation, the Electrical Inspector may require certain tests to be
carried out before or after charging the installations.
(5) All apparatus, cables and supply lines shall be maintained in healthy conditions and tests shall be carried out
periodically as per the relevant standards.
(6) Records of all tests, trippings, maintenance works and repairs of all apparatus, cables and supply lines shall
be duly kept in such a way that these records can be compared with the past records.
(7) It shall be the responsibility of the owner of all installations of voltage exceeding 650 V to maintain and
operate the installations in a condition free from danger and as recommended by the manufacturer or by the
relevant standards.
(8) Failures of any 220 kV and above voltage level transformer, reactor and transmission line towers shall be
reported by the owner of electrical installation, within forty eight hours of the occurrence of the failure, to the
Authority and the reasons for failure and measures to be taken to avoid recurrence of failure shall be sent to the
Authority within one month of the occurrence in the forms provided in Schedule VII:
Provided that in case of mines and oil-fields, the failure of 10 MVA or above transformers shall be
reported to Electrical Inspector of mines.