Regulation 46, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Use of electricity at voltage exceeding 650 V
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 46
Text of regulation 46
Use of electricity at voltage exceeding 650 V
46. Use of electricity at voltage exceeding 650 V. – (1) The Electrical Inspector where the supply voltage exceeds
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 117
the notified voltage shall not authorise the supplier to commence supply or recommence the supply, where the
supply has been discontinued for a period of six months or more, or the supplier, where the supply voltage is
equal to or below the notified voltage but exceeds 650 V, shall not commence supply or recommence the supply
where supply has been discontinued for a period of six months or more, to any consumer unless, –
(a) all conductors and apparatus situated on the premises of the consumer are so placed as to be
inaccessible except to the designated person;
(b) the consumer has provided and agreed to maintain a separate building or a locked weather proof and
fire proof enclosure of agreed design and location, to which the supplier at all times shall have access for
the purpose of housing his apparatus and metering equipment, or where the provision for a separate
building or enclosure is impracticable, the consumer has segregated the aforesaid apparatus of the
supplier from any other part of his own apparatus:
Provided that the segregation shall be made by the fire walls, if the Electrical Inspector
considers it to be necessary:
Provided further that in the case of an outdoor installation the consumer shall suitably
segregate the aforesaid apparatus belonging to the supplier from his own;
(c) all pole type substations are constructed and maintained in accordance with regulation 52.
(2) Where electricity at voltage exceeding 650 V is supplied, converted, transformed or used, the owner shall, –
(i) maintain safety clearances for electrical apparatus as per relevant standards specification so that
sufficient space is available for easy operation and maintenance without any hazard to the operating and
maintenance personnel working near the equipment and for ensuring adequate ventilation:
Provided that in case of mines, the safety clearances for electrical apparatus to be as per relevant
mining regulations;
(ii) not allow any encroachment below such installation:
Provided that where the Electrical Inspector comes across any such encroachment, he shall direct
the owner to remove such encroachments;
(iii) maintain minimum safety working clearances specified in Schedule V for the bare conductors or
live parts of any apparatus in outdoor substations excluding overhead lines of installations of voltage
exceeding 650 V;
(iv) ensure that the live parts of all apparatus within the reach from any position in which a person may
require to be, are suitably protected to prevent danger;
(v) ensure that where the transformer is used, suitable provision shall be made, either by connecting
with earth, a point of the circuit at the lower voltage or otherwise, to guard against danger by reason of the
said circuit becoming accidentally charged above its normal voltage by leakage from or contact with the
circuit at the higher voltage;
(vi) not install a substation or a switching station with apparatus having more than 2000 litre of oil in the
basement where proper oil draining arrangement cannot be provided;
(vii) undertake the following measures, where a substation or a switching station with oil-filled
apparatus, such as transformer, static condenser, switchgear or oil circuit breaker having more than 2000
litre of oil is installed, whether indoor or outdoors,-
(a) the separation wall or fire barrier walls of thickness and dimensions as specified in the relevant
standards shall be provided between the apparatuses and between the apparatus and adjacent
building if building wall adjacent to the apparatuses is not rated for four hours fire withstand rating;
(b) provisions shall be made for suitable oil soakpit and where use of more than 9000 litre of oil in
any one oil tank, receptacle or chamber is involved, provision shall be made for the draining away or
removal of any oil which may leak or escape from the tank, receptacle or chamber containing the
same, and special precautions shall be taken to prevent the spread of any fire resulting from the
ignition of the oil from any cause and adequate provision shall be made for extinguishing any fire
which may occur;
(c) spare oil shall not be stored in the vicinity of any oil filled equipment in any such substation or
switching station; and
(d) all the transformers and switchgears shall be maintained in accordance with the maintenance
schedules prepared in accordance with the relevant standards;
118 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
(viii) without prejudice to the above measures, undertake adequate fire detection and protection
arrangement for quenching the fire of the apparatus;
(ix) ensure that every transformer of 10 MVA or reactor of 10 MVAR and above rating shall be
provided with automatic fire fighting system as per relevant standards;
(x) undertake the following measures, where it is necessary to locate the substation, or switching station
in the basement, namely: –
(a) the transformer room be in the first basement at the periphery;
(b) the direct access to the transformer room be provided from outside and the surrounding walls
of four hours fire withstand rating be provided as per relevant standards;
(c) the entrances to the transformer room be provided with fire resistant doors of two hour fire
rating and the door shall always be kept closed and a notice of this effect be affixed on outer side of
the door;
(d) a curb of a suitable height be provided at the entrance in order to prevent the flow of oil from a
ruptured transformer into other parts of the basement;
(e) the cables to primary side and secondary side have sealing at all floors and wall opening of
atleast two hours fire withstand rating; and
(f) Fire Retardant Low Smoke Low Halogen cable as per relevant standards be used;
(xi) ensure that oil filled transformers installed indoors in other than residential or commercial buildings
are placed on the ground floor or not below the first basement;
(xii) ensure that only dry type transformer shall be used inside the residential and commercial buildings;
(xiii) ensure that cable trenches inside the substations and switching stations containing cables are filled
with sand, pebbles or similar non-inflammable materials or completely covered with non-inflammable
slabs; and
(xiv) ensure that unless the conditions are such that all the conductors and apparatus may be made dead at
the same time for the purpose of cleaning or for other work, the said conductors and apparatus shall be so
arranged that these may be made dead in sections, and that work on any such section may be carried on by
the person designated or appointed or engaged or permited under these regulations without danger.
(3) The minimum clearances specified in Schedule VI shall be maintained for bare conductors or live parts of
any high voltage direct current apparatus in outdoor substations, excluding high voltage direct current
overhead lines.
(4) There shall not be tapping of another transmission line from the main line for 66 kV and above class of
lines:
Provided that during natural calamities, tapping may be allowed to ensure emergency power supply
to affected areas till normalcy is restored.