Form III, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: FORM III
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Form III
Text of form III
FORM III
FORM III
(See Regulation 32 and 45)
(Installations of voltage exceeding 650 V)
Report / Application No. __________
Date of inspection by Electrical Inspector or self-certification by supplier/owner/consumer
______________________________
Date of last inspection or self-certification ___________________
1. Consumer No. ______________________
2. Voltage and system of supply:
(iii) Volts _____________(ii) No. of Phases _____________ (iii) AC/DC _______________
3. Name of the consumer or owner _____________________________
4. Address of the consumer or owner _____________________________
5. Location of the premises _____________________________
6. Particulars of the installations:
(a) Transformers: (complete detail to be enclosed)
Make S. No. kVA/MVA rating Voltage rating Type
(i) ________________________________________________________________
(ii) ________________________________________________________________
(b) Generators: (complete detail to be enclosed)
Make S. No. kVA/MVA rating Voltage rating Type
(v) ________________________________________________________________
(vi) ________________________________________________________________
(c) List of Motors with rating, protection, overload setting, size of earth conductor used to be furnished
Make S. No. kW/MW rating Voltage rating Type
(iii) ________________________________________________________________
(iv) ________________________________________________________________
(d) List of equipment with complete details of HT /LT switchgears/ apparatus with their rating to be furnished):
(iii) ________________________________________________________________
(iv) ________________________________________________________________
(e) Total connected load kW / kVA _________________________________________
Complete list of connected loads to be furnished.
7. General condition of the installation:
Sl.
No.
Regulation No. Requirements Report
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 157
1. Regulation 3 Is the record of the designated persons properly made and kept
up to date and duly attested?
Yes/No
2. Regulation 5 Whether Electrical Safety Officer as required under the
Regulation is designated?
Yes/No
Regulation 14 (i) Is/Are there any visible sign(s) of overloading in respect
of any apparatus?
Yes/No
(ii) Whether any unauthorised temporary installation exist? Yes/No
(iii) Whether the motors and controlling equipment are
being overhauled periodically and record kept of the
same in a register?
Yes/No
(iv) Whether the transformer oil samples are being tested
periodically and results recorded in a register? State
value of dielectric strength of oil.
Yes/No
---- kV/mm
(v) Whether suitable lightning arresters have been provided
near the transformers for protection against lightning?
Yes/No
(vi) Whether earth resistance is being measured periodically
once a year and results recorded in a register? Copy of
record to be enclosed.
Yes/No
(vii) Any other defect or condition which may be a source of
danger. If yes, please explain?
Yes/No
(viii) Whether operation and maintenance data has been
clarified, categorised and computerised for prompt and
easy retrieval?
Yes/No
(ix) Whether residual life assessment and life extension
programmes are being undertaken for installations or
equipment of voltage exceeding 650 V (applicable for
installations or equipment more than 15 years old)?
Yes/No
(x) Whether all required type and routine tests at factory
done for equipment? Deficiencies and discrepancies in
above test report and results, if any, shall be reported.
Yes/No
(xi) Are there deficiencies in construction with reference to
Indian Standard requirements? Please specify.
Yes/No
4. Regulation 15 Give report on condition of service lines, cables, wires,
apparatus and such other fittings placed by the supplier or
owner of the premises. If not satisfactory, give details.
Satisfactory/
Not Satisfactory
5. Regulation 16 Whether suitable cut-outs/CBs provided by the supplier at the
consumer‟s premises are within enclosed fire proof
receptacle?
Yes/No
6. Regulation 17 (i) Whether switches are provided on live conductors? Yes/No
(ii) Whether indication of a permanent nature is provided as
per Regulation so as to distinguish earthed or earthed
neutral conductor from the live conductor?
Yes/No
(iii) Whether a direct line is provided on the neutral in the case
of single-phase double pole iron clad switches/CBs
instead of fuse?
Yes/No
7. Regulation 18 (i) Whether earthed terminal is provided by the supplier? Yes/No
(ii) General visible condition of the earthing arrangement. Satisfactory/
Not Satisfactory
158 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
8. Regulation 19 (i) Are live parts in building inaccessible? Yes/No
(ii) Whether readily accessible switches have been provided
for rendering them dead?
Yes/No
9. Regulation 20 13. Whether “Danger Notice” in Hindi and the local language of
the district and of a design as per the relevant standards is
affixed permanently in conspicuous position?
Yes/No
10. Regulation 21 (i) Whether the practice of working on live lines and
apparatus is adopted? If so, have the safety measure been
adopted as per Schedule I?
Yes/No
(ii) Whether insulating floor or mats conforming to the
relevant standards have been provided?
Yes/No
(iii) Whether identification of panel has been provided on the
front and the rear of the panel?
Yes/No
11. Regulation 23 Whether flexible cables used for portable or transportable
equipment covered under the Regulation, are heavily insulated
and adequately protected from mechanical injury?
Yes/No
12. Regulation 24 State the condition of metallic coverings provided for various
conductors.
Satisfactory/
Not Satisfactory
13. Regulation 26 Whether the circuits or apparatus intended for operating at
different voltage(s) are distinguishable by means of
indication(s) of permanent nature?
Yes/No
14. Regulation 28 Whether all circuits and apparatus are so arranged that there is
no danger of any part(s) becoming accidentally charged to any
voltage beyond the limits of voltage for which it/they is/are
intended?
Yes/No
15. Regulation 29 (i) In the case of generating stations and enclosed sub
stations, whether fire-buckets filled with clean dry sand
have been conspicuously marked and kept in convenient
location in addition to fire-extinguishers suitable for
dealing with electric fires?
Yes/No
(ii) Whether First Aid Boxes or cupboards conspicuously
marked and properly equipped are provided and
maintained?
Yes/No
(iii) Is adequate staff trained in First Aid Treatment and
firefighting?
Yes/No
16. Regulation 30 (i) Whether instructions in English or Hindi and the local
language of the district and where Hindi is the local
language, in English and Hindi, for the resuscitation of
persons suffering from electric shock have been affixed in
a “conspicuous place”?
Yes/No
(ii) Are the persons mentioned in this regulation able to
apply instructions for resuscitation of persons suffering
from electric shock?
Yes/No
17. Regulation 36 State insulation resistance between conductors and earth in
Mega Ohms.
----- Mega Ohms
18. Regulation 37 (i) Whether a suitable linked switch, or a circuit breaker, or
an emergency tripping device is placed near the point of
commencement of supply so as to be readily accessible
and capable of being easily operated to completely isolate
the supply?
Yes/No
(ii) Whether suitable linked switch or a circuit breaker to
carry and break the full load current is provided on the
Yes/No
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 159
secondary side of a transformer?
(iii) Whether every distinct circuit is protected against excess
electricity by means of a suitable circuit breaker or cut-
out?
Yes/No
(iv) Whether linked switch or circuit breaker or emergency
tripping device is provided near the motor or other
apparatus at voltage exceeding 650 V but not exceeding
33kV for controlling supply to the motor or apparatus?
Yes/No
(v) Whether adequate precautions are taken to ensure that no
live parts are so exposed as to cause danger?
Yes/No
19. Regulation 39 (i) Whether clear space of 100 cm is provided in front of the
main switchboard?
Yes/No
(ii) Whether the space behind the switchboard exceeds 75
cm in width or is less than 20 cm?
Yes/No
(iii) In case the clear space behind the switchboard exceeds
75 cm, state whether a passage way from either end of the
switchboard to a height of 1.80 metre is provided.
Yes/No
20. Regulation 46 (i) Whether all conductors and apparatus including live
parts thereof are inaccessible
Yes/No
(ii) Whether all windings of motors or other apparatus are
suitably protected?
Yes/No
(iii) Whether the separation wall or fire wall between
apparatuses or consumer premises, in a substation or a
switching station with apparatus having more than 2000
litres of oil are installed, have been provided as required
under the regulation?
Yes/No
(iv) Where 9000 litre or more of oil is used in any one oil
tank, has provision been made for draining away or
removal of oil which may leak or escape from such
tank(s)?
Yes/No
(v) Whether suitable firefighting system as per the regulation
has been provided?
Yes/No
(vi) Whether trenches inside substation containing cables are
filled with non-inflammable material or completely
covered with non-inflammable slabs?
Yes/No
(vii) Are conductors and apparatus so arranged that they may
be made dead in sections for carrying out work thereon?
Yes/No
21. Regulation 47 Whether protections and interlocks have been provided? Give
the details of the protection schemes and their settings.
Yes/No
22. Regulation 50 (i) Have all non-current carrying metal parts associated with
the installation been effectively earthed with the earthing
system or mat by two separate and distinct connections?
Yes/No
(ii) Is the earth wire free from any mechanical damage? Yes/No
(iii) Has the neutral point at the transformer and generator
been earthed by two separate and distinct connections
with earth?
Yes/No
(iv) Have the metal casings or metallic coverings containing
or protecting any electric supply line or apparatus been
properly earthed and so joined and connected across all
junction boxes as to make good mechanical and
Yes/No
160 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
electrical connections throughout their whole length?
(v) Whether earthing has been properly executed and has
been tested. If yes, give value of earth resistance.
Yes/No
___Ohm
23. Regulation 51 (i) Is the outdoor (except pole type) substation efficiently
protected by fencing not less than 1.8 metre in height?
Yes/No
(ii) Whether the mounting of a transformer on a single pole or
H pole is done as per relevant standard.
Yes/No
24 Regulation 52 (i) Where platform type construction is used for pole type
substation, has sufficient space for a man to stand on the
platform been provided?
Yes/No
(ii) Has hand-rail been provided and connected with earth (if
metallic and if substation has not been erected on wooden
supports and wooden platform)?
Yes/No
25. Regulation 53 Has suitable provision been made for immediate and
automatic or manual discharge of every static condenser on
disconnection of supply?
Yes/No
26 Overhead Lines (i) What is the minimum size of the conductors of overhead
lines used? State the type of conductors. (Regulation 57)
Minimum size of
Conductor ---
(ii) Whether clearances above ground of the lowest conductor
of overhead lines are as per regulation 60? State
clearance.
Yes/No
--- metre
(iii) On the basis of maximum sag, whether vertical clearances
where the line of voltage exceeding 650 V passes above
or adjacent to any building or part of a building as per
regulation 63? State clearance.
Yes/No
--- metre
(iv) On the basis of maximum deflection due to wind pressure,
whether horizontal clearances between the nearest
conductor and any part of such building are as per
regulation 63? State clearance.
Yes/No
--- metre
(v) Where conductors forming parts of system at different
voltages are erected on the same supports, whether
adequate provision has been made as per regulation 64 to
guard against danger to linemen and others from the lower
voltage system being charged above its normal working
voltage by leakage from or contact with the higher voltage
system?
Yes/No
(vi) Where overhead lines cross or are in proximity to each
other whether they have been suitably protected to guard
against possibility of their coming in contact with each
other as per regulation 71?
Yes/No
(vii) Has every guard wire been properly earthed as per
regulation 72 at each point at which its electrical
continuity is broken?
Yes/No
(viii) (a) Whether metal supports of overhead lines and
metallic fittings attached thereto are permanently earthed
as per regulation 74?
(b) Has each stay-wire (except in case where an insulator
has been placed in it at a height not less than 3 metre
from the ground) been earthed as per regulation 74?
Yes/No
Yes/No
(ix) (a) Whether overhead line is suitably protected with a
device for rendering the line electrically harmless in case
Yes/No
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 161
it breaks as per regulation 76?
(b) Whether anti-climbing devices have been provided at
each support as per regulation 75?
Yes/No
(x) (a) Has the owner of overhead lines adopted efficient
means for diverting to earth any electrical surges due to
lightning in every overhead line which is so exposed as
to be liable to injury from lightning as per regulation 77?
(b) Whether earth lead from the lightning arresters is
connected to a separate earth electrode as per regulation
77?
Yes/No
Yes/No
(xi) Whether unused overhead lines are maintained in a safe
mechanical condition as per regulation 78?
Yes/No
(xii) Whether statutory clearances from Authorities i.e. Forest
Department/Railways/PTCC/Defence (AHQ) /Civil
Aviation have been taken as per the relevant standards. If
yes, enclose copies of the same.
Yes/No
(xiii) Any other remarks. Yes/No
In addition to above, following electrical equipment wise test details to be given, if applicable:
Sl.
No.
Equipment Test Conducted Test Results Remarks
1. Linked Switch with
fuses (s)
(i) Mechanical operation Smooth/Trouble some
(ii) Rating of Fuse -------Amps
(iii) Contact of blades Full/Partial
2. Isolator
(Sl. No.---
Make:
Capacity:
(i) Mechanical operation Ok/Not Ok
(ii) Remote Operation OK/Not OK
(iii) Local Operation OK/Not OK
(iv) Measurement of contact resistance
(v) Interlocking with earth switch OK/Not OK
(vi) Interlocking with Circuit Breaker OK/Not OK
(vii) IR Values
Open condition
Closed condition
Phase to Phase and Phase to
Earth
--- M Ohm --- M Ohm
--- M Ohm --- M Ohm
3. Circuit Breaker
(Circuit breaker
location and no.)
Circuit breaker
control circuits
(i) Rating of Circuit Breaker
Type
Voltage
Normal Current
Rupturing Current
-------------
------------- kV
------------- Amps
-------------- kA
(ii) IR Values
Open condition
Closed Condition
Phase to Phase and Phase to
Earth
--- M Ohm --- M Ohm
--- M Ohm --- M Ohm
(iii) Contact Resistance including
Dynamic Contact Resistance
Measurement
-------------micro ohm
(iv) Mechanical Operation Instant smooth /time
gap (Sec.)
(v) Remote operation OK/Not OK
162 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
(vi) Local Operation OK/Not OK
(vii) Interlocking with Isolator OK/Not OK
(viii) Interlocking with earth switch OK/Not OK
(ix) Alarm and Trip for
OTI/WTI/Buchholz/PRV/etc.,
OK/Not OK
(x) Earth Fault Relay OK/Not OK
(xi) Over Current Relay OK/Not OK
(xii) Under Voltage Relay OK/Not OK
(xiii) other safety Alarms OK/Not OK
(xiv) Whether all the provisions of
Regulation 37 are satisfactory?
OK/Not OK
4. Transformer
Transformer No.,
Location,
(Transformer Sl. No.
Make, Capacity,
Voltage Ratio)
(i) Insulation Resistance Values
HT to LT
HT to Earth
LT to Earth
--------------M ohm
--------------M ohm
--------------M ohm
(ii) Break down Voltage test
Oil sample I (Top)
Oil Sample II (Bottom)
-------------- kV
-------------- kV
(iii) Vector Group Test OK/Not OK
(iv) Polarity Tests OK/Not OK
(v) Magnetic Balance OK/Not OK
(vi) Tan Delta Test OK/Not OK
(vii) Oil level in conservator tank OK/Not OK
(viii) Oil level in breather cup OK/Not OK
(ix) OTI/WTI settings A/T---
0
C/---
0
C A/T---
0
C/---
0
C
(x) OTI/WTI alarm and trip operation OK/Not OK
(xi) Operation of Buchholz relay OK/Not OK
(xii) Operation of PRV OK/Not OK
(xiii) Oil leakage OK/Not OK
(xiv) Interlock of door switch of dry
transformer
OK/Not OK
(xv) Clearances
Side Clearance:
Between two Transformers:
---------cm
----------Metre
(xvi) Body Earth Resistance ---------- Ohm
(xvii) Neutral Earth Resistance N1---Ohm, N2---Ohm
(xviii) Earth Flat Size Material used
Body:
Neutral:
-----------
-----------
(xix) Operation of ON LOAD & OFF
LOAD Tap Changers
OK/Not OK
(xx) Sweep Frequency Resonance
Analysis Test (SFRA)
OK/Not OK
(xxi) Dielectric Frequency Resonance
Analysis (DFRA) Test
OK/Not OK
(xxii) Partial Discharge Tests OK/Not OK
5 DG Generators:
Generator No.,
(i) Type of Generator
(ii) Interlocking with other supply OK/Not OK
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 163
Location,
(Alternator and
Engine Sl. No.
Make, Capacity)
sources
(iii) Body earth resistance ---------- Ohm
(iv) Neutral earth resistance N1---Ohm N2---Ohm
(v) Earth Flat Size, Material used
(Cu/Al)
Body:
Neutral:
------------------
------------------
(vi) Generator Protection details ------------------
6. Cable
(Details to be given:
size, length, type)
(i) Insulation Resistance Values:
Ph - Ph:
Ph – Earth:
Ph – Earth + other Ph:
--------- M Ohm
--------- M Ohm
--------- M Ohm
(ii) Cable trays Provided/ Not provided
(iii) Cable tray earthing OK/Not OK
(iv) Cables bending radius OK/Not OK -----------metre
7. Panels (i) No. of panels ___ Nos
(ii) Location of panel To be enclosed
(iii) Rating of the panel ____Amp
(iv) Size and current rating of the main
Bus bars and the distribution Bus
bars of the panel
____ mm, _____Amp
(v) Whether the Bus bar size of the
panel suitable to rating of the panel
Yes/No
(vi) IP Protection of panel ________
(vii) Type of cable entry Top Entry/Bottom Entry
(viii) No. of Incomers and Bus couplers
in a Panel
___ Nos
(ix) Ratings of the Circuit Breakers ____Amp
(x) No. of MCCBs of each rating in
the panel
___ Nos
(xi) No. of spare MCCBs of each rating ___ Nos
(xii) Panel Clearance from the wall ____mm
(xiii) Clearance between two panels i.e.
adjacent panels
____mm
(xiv) Whether all the provisions of
Regulation 39 followed
Yes / No
(xv) Size of the Earth strip used for
earthing of the panel
___sqmm
8. Earthing (i) Metal and size of Earth Strips Cu/Al/GI --- Sqmm
(ii) Type of earthing Plate/Pipe/Counterpoise
(iii) Location and No. of earth electrode ____Nos
(iv) Values of Earth resistance of each
earth electrode and Grid
_____Ω
(v) Earth mat resistance _____Ω
9. Potential
Transformer
(i) Ratio test OK/not OK
(ii) Polarity test OK/not OK
(iii) BDV of oil ---------- kV
(iv) IR test (R) P-E-------M Ohm
164 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
(Y) P-E-------M Ohm
(B) P-E-------M Ohm
(v) Tan Delta and Capacitance
measurement
_______
10. Current Transformer (i) Ratio test OK/not OK
(ii) Polarity test OK/not OK
(iii) BDV of oil ---------- kV
(iv) IR test (R) P-E-------M Ohm
(Y) P-E-------M Ohm
(B) P-E-------M Ohm
(v) Tan Delta and Capacitance
measurement
_______
11. Overhead lines and
DP structure
(i) Size of the poles of DP structure _______
(ii) Clearance between phases to phase
and phase to earth.
_______
(iii) Ground clearance of the
conductors.
_______
(iv) Check of electrical clearance along
the route of overhead line,
Ok/ Not Ok
(v) Check of guarding and clearance at
road crossings.
Ok/ Not Ok
(vi) Check the footings of the poles. Ok/ Not Ok
(vii) Earthing arrangements Ok/ Not Ok
(viii) What is the minimum size of the
conductors of overhead lines used?
State the type of conductors.
_______
(ix) Whether all the provisions of
regulation 60, 62, 63, 64, 71, 72
and 74 are satisfied.
Yes / No
General Observations:
1. Check of phase to phase, phase to ground and sectional clearance
2. Check of Manufacture test reports of individual equipment
(Copies to be enclosed)
3. General observation and views (Specific deviation from the requirements of
the Regulations shall be clearly brought out)
Date:
Signature of the supplier/ Owner / Consumer
Name ______________________
Designation _________________
File No. ____________________
To: Office of Electrical Inspector for ………………...
(For Self-certification by supplier /owner /consumer)
CERTIFICATE
[Under Regulation (32) and (45) of CEA (Measures relating to Safety & Electricity Supply) Regulation, 2023]
This is to certify that the electrical installation is complete in all respects and the work has been carried out
conforming to the CEA (Measures relating to Safety & Electric Supply) Regulation, 2023 and relevant standards. The
site tests done are found to be in order and it is electrically safe to operate the apparatus free from any danger.
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 165
Encl: Test reports
(Signature) (Signature)
Self-certifying supplier / owner / consumer Chartered Electrical Safety Engineer
Name ______________________ Name ______________________
File No. ____________________
To: Office of Electrical Inspector for ………………...
Forms of Inspection Report
[See sub-regulation (3) of regulation (32)]