LawGrids logoLAWGRIDS.ORG

Regulation 6, Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010.: Distribution System

Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010. - Regulation 6

Text of regulation 6

Distribution System

6. Distribution System:- For Power Transformers of HV class in the Distribution System, differential protection shall be provided for 10 MVA and above along with backup time lag over current and earth fault protection with directional feature for parallel operation. Transformers of 1 MVA and above but less than 10 MVA shall be protected by time lag over current and earth fault. . In addition, all power transformers shall be provided with gas operated relays, winding and oil temperature alarm and protection.

Previous and next

All provisions of Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010.

Questions people ask

Is regulation 6 of Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010. still in force?

No repeal of Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010. is recorded.