Regulation 6, Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010.: Distribution System
Joint Electricity Regulatory Commission” (Distribution Code) Regulations, 2010. - Regulation 6
Text of regulation 6
Distribution System
6. Distribution System:- For Power Transformers of HV class in the Distribution
System, differential protection shall be provided for 10 MVA and above along with
backup time lag over current and earth fault protection with directional feature for
parallel operation. Transformers of 1 MVA and above but less than 10 MVA shall
be protected by time lag over current and earth fault. . In addition, all power
transformers shall be provided with gas operated relays, winding and oil
temperature alarm and protection.