Rule 64A, THE INDIAN ELECTRICITY RULES, 1956: Additional provisions for use of energy at high and extra-high voltage- The following additional provisions shall be observed where energy at high or extra- high voltage is supplied, converted, transferred or used, namely
THE INDIAN ELECTRICITY RULES, 1956 - Rule 64A
Text of rule 64A
Additional provisions for use of energy at high and extra-high voltage- The following additional provisions shall be observed where energy at high or extra- high voltage is supplied, converted, transferred or used, namely
1[64A. Additional provisions for use of energy at high and extra-high voltage- The
following additional provisions shall be observed where energy at high or extra-
high voltage is supplied, converted, transferred or used, namely: -
(1) Inter-locks- Suitable inter-locks shall be provided in the following cases: -
(a) Isolators and the controlling circuit breakers shall be interlocked so that the
isolators cannot be operated unless the corresponding breaker is in open position;
(b) Isolators and the corresponding earthing switches shall be interlocked so
that no earthing switch can be closed unless and until the corresponding isolator is
in open position;
(c) Where two or more supplies are not intended to be operated in parallel, the
respective circuit breakers or linked switches controlling the supplies shall be inter-
locked to prevent possibility of any inadvertent paralleling or feedback;
(d) When two or more transformers are operated in parallel, the system shall
be so arranged as to trip the secondary breaker of a transformer in case the
primary breaker of that transformer trips;
(e) All gates or doors which give access to live parts of an installation shall be
inter-locked in such a way that these cannot be opened unless the live parts are
made dead. Proper discharging and earthing of these parts should be ensured
before any person comes in close proximity of such parts;
(f) Where two or more generators operate in parallel and neutral switching is
adopted, inter-lock shall be provided to ensure that generator breaker cannot be
closed unless one of the neutrals is connected to the earthing system.
(2) Protection- All systems and circuits shall be so protected as to automatically
disconnect the supply under abnormal conditions. The following protection shall
be provided, namely: -
(a) Over current protection to disconnect the supply automatically if the rated
current of the equipment, cable or supply line is exceeded for a time which the
equipment, cable or supply line is not designed to withstand;
(b) Earth-fault/earth leakage protection to disconnect the supply automatically if
the earth fault current exceeds the limit of current for keeping the contact potential
within the reasonable values;
(c) Gas pressure type protection to given alarm and tripping shall be provided
on all transformers of ratings 1000 KVA and above;
(d) Transformers of capacity 10 MVA and above shall be protected against
incipient faults by differential protection; and
(e) All generators with rating of 100 KVA and above shall be protected against
earth fault/leakage. All generators of rating 1000KVA and above shall be
protected against faults within the generator winding using restricted earth fault
protection or differential protection or by both.]
1. Ins. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987.
65. Testing, Operation and Maintenance-
(1) Before approval is accorded by the Inspector under rule 63, the
manufacturer’s test certificates shall, if required, be produced for all the routine
tests as required under the relevant Indian Standard.
(2) No new HV or EHV apparatus, cable or supply line shall be commissioned
unless such apparatus, cable or supply line are subjected to site tests as per
relevant code of practice of the 1[Bureau of Indian Standards].
(3) No HV of EHV apparatus, cable or supply line which has been kept
disconnected, for a period of 6 months or more, from the system for alterations or
repair shall be corrected to the system until such apparatus, cable or supply line
are subjected to the relevant tests as per code of practice of 1[Bureau of Indian
Standards.]
(4) Notwithstanding the provisions of sub-rules (1) to (3) (both inclusive) the
Inspector may require certain additional tests to be carried out before charging the
installations or subsequently.
(5) All apparatus, cables and supply lines shall be maintained in healthy
conditions and tests shall be carried out periodically as per the relevant codes of
practice of the 1[Bureau of Indian Standards].
(6) Records of all tests, trappings, maintenance works and repairs of all
equipments, cables and supply lines shall be duly kept in such a way that these
records can be compared with earlier ones.
(7) It shall be the responsibility of the owner of all HV and EHV installations to
maintain and operate the installations in a condition free from danger and as
recommended by the manufacturer and/or by the relevant codes of practice of the
1[Bureau of Indian Standards] and/or by the Inspector.]
1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
66. Metal sheathed electric supply lines. Precautions against excess leakage-
(1) The following provisions shall apply to electric supply lines (other than
overhead lines 1[***] for use at high or extra-high voltage: -
(a) The conductors shall be enclosed in metal sheathing which shall be
electrically continuous and connected with earth, and the conductivity of the metal
sheathing shall be maintained and reasonable precautions taken where necessary
to avoid corrosion of the sheathing;
Provided that in the case of thermoplastic insulated and sheathed cables with
metallic armour the metallic wire or tape armour shall be considered as metal
sheathing for the purpose of this rule;
Provided further that this rule shall not apply to cable with thermoplastic insulation
without any metallic screen or armour.
2[(b) The resistance of the earth connection with metallic sheath shall be kept
low enough to permit the controlling circuit breaker or cut-out to operate in the
event of any failure of insulation between the metallic sheath and the conductor.]
(c) Where an electric supply-line as aforesaid has concentric cables and the
external conductor is insulated from an outer metal sheathing and connected with
earth, the external conductor may be regarded as the metal sheathing for the
purposes of this rule provided that the foregoing provisions as to conductivity are
complied with.
(2) Nothing in the provisions of sub-rule (1) shall preclude the employment in
generating stations, sub-stations and switch-stations (including outdoor
substations and outdoor switch-stations) of conductors for use at high or extra-
high voltages which are not enclosed in metal sheathing or preclude the use of
electric supply lines laid before the prescribed date to which the provisions of
these rules apply
1. The words “of a supplier” omitted by GSR 358, dt. 30.4.1987, w.e.f.
9.5.1987.
2. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
67. Connection with earth-
1[(1) All non-current carrying metal parts associated with HV/EHV installation
shall be effectively earthed to a grounding system or mat which will: -
(a) Limit the touch and step potential to tolerable values;
(b) Limit the ground potential rise to tolerable values so as to prevent danger
due to transfer of potential through ground, earth wires, cables sheath fences, pipe
lines, etc.;
(c) Maintain the resistance of the earth connection to such a value as to make
operation of the protective device effective.
(lA) In the case of star-connected system with earthed neutrals or delta
connected system with earthed artificial neutral point: -
(a) The neutral point of every generator and transformer shall be earthed by
connecting it to the earthing system as defined in rule 61(4) and hereinabove by
not less than two separate and distinct connections;
Provided that the neutral point of a generator may be connected to the earthing
system through an impedance to limit the fault current to the earth;
Provided further that in the case of multi-machine system neutral switching may be
resorted to, for limiting the injurious effect of harmonic current circulation in the
system;
(b) In the event of an appreciable harmonic current flowing in the neutral
connection so as to cause interference, with communication circuits, the generator
or transformer neutral, shall be earthed through a suitable impedance;
(c) In case of the delta connected system the neutral point shall be obtained by
the insertion of a grounding transformer and current limiting resistance or
impedance wherever considered necessary at the commencement of such a
system.]
(2) Single-phase high or extra-high voltage systems shall be earthed in a
manner approved by the Inspector.
(3) In the case of a system comprising electric supply lines having concentric
cables, the external conductor shall be the one to be connected with earth.
(4) Where a supplier proposes to connected with earth an existing system for
use at high or extra-high voltage which has not hitherto been so connected with
earth he shall give not less than fourteen days’ notice in writing together with
particulars to the telegraph-authority of the proposed connection with earth.
(5) (a) Where the earthing lead and earth connection are used only in
connection with earthing guards erected under high or extra-high voltage overhead
lines where they cross a telecommunication line or a railway line, and where such
lines are equipped with earth leakage relays of a type and setting approved by the
Inspector, the resistance shall not exceed 25 ohms.
(b) Every earthing system belonging to either the supplier or the consumer
shall be tested for its resistance to earth on a dry day during dry season not less
than once a year. Records of such tests shall be maintained and shall be
produced, if required before the Inspector or any officer appointed to assist him
and authorised under sub-rule (2) of rule 4A.
(6) In so far as the provisions of rule 61 are consistent with the provisions of
this rule, all connections with earth shall also comply with the provisions of that
rule.
1. Subs. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987.
68. General conditions as to transformation and control of energy-
(1) Where energy at high or extra-high voltage is transformed, converted,
regulated or otherwise controlled in sub-stations or switch-stations (including
outdoor substations and out-door switch-stations) or in street boxes constructed
underground, the following provisions shall have effect: -
1[(a) Sub-stations and switch-stations shall preferably be erected above ground,
but where necessarily constructed underground due provisions for ventilation and
drainage shall be made and any space housing switchgear shall not be used for
storage of any materials especially inflammable and combustible materials or
refuse.]
(b) Outdoor sub-station is except pole type sub-stations and. outdoor switch-
stations shall (unless the apparatus is completely enclosed in a metal covering
connected with earth, the said apparatus also being connected with the system by
armoured cables) be efficiently protected by fencing not less than 1.8 metres in
height or other means so as to prevent access to the electric-supply lines and
apparatus therein by an unauthorised person.
(c) Underground street boxes (other than sub-stations) which contain
transformers shall not contain switches or other apparatus, and switches, cut-outs
or other apparatus required for controlling or other purposes shall be fixed in
separate receptacles above ground wherever practicable.
(2) Where energy is transformed, suitable provisions shall be made either by
connecting with earth a point of the system at the lower voltage or otherwise to
guard against danger by reason of the said system becoming accidentally charged
above its normal voltage by leakage from a contact with the system at the higher
voltage.
1. Subs. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987.
69. Pole type sub-stations- Where platform type construction is used for a pole
type sub-station and sufficient space for a person to stand on the platform is
provided a substantial hand rail shall be built around the said platform and if the
hand rail is of metal, it shall be connected with earth;
Provided that in the case of pole type sub-station on wooden supports and
wooden platform the metal hand-rail shall not be connected with earth.
70. Condensers- Suitable provision shall be made for immediate and automatic
discharge of every static condenser on disconnection of supply.
71. Additional provisions for supply to high voltage luminous tube sign
installation-
(1) Any person who proposes to use or who is using energy for the purpose of
operating a luminous tube sign installation, or who proposes to transform or who is
transforming energy to a high voltage for any such purpose shall comply with the
following conditions: -
(a) All live parts of the installation (including all apparatus and live conductors
in the secondary circuit, but excluding tubes except in the neighbourhood of their
terminals) shall be inaccessible to unauthorised persons and such parts shall be
effectively screened.
(b) Irrespective of the method of obtaining the voltage of the circuit which feeds
the luminous discharge tube sign, no part of any conductor of such circuit shall be
in metallic connection (except in respect of its connection with earth) with any
conductor of the supply system or with the primary winding of the transformer.
(c) All live parts of an exterior installation shall be so disposed as to protect
them against the effects of the weather and such installation shall be so arranged
and separated from the surroundings as to limit, as far as possible, the spreading
of fire.
(d) The secondary circuit shall be permanently earthed at the transformer and
the core of every transformer shall be earthed.
(e) Where the conductors of the primary circuit are not in metallic connection
with the supply conductors, (e.g., where a motor-generator or a double-wound
convertor is used), one phase of such primary circuit shall be permanently earthed
at the motor generator or convertor, or at the transformer.
1[(ee) An earth leakage circuit breaker of sufficient rating shall be provided on the
low voltage side to detect the leakage in such luminous tube sign installations.]
(f) A final sub-circuit which forms the primary circuit of a fixed luminous
discharge tube sign installation shall be reserved solely for such purpose.
(g) A separate primary final sub-circuit shall be provided for each transformer
or each group of transformers having an aggregate input not exceeding 1,000 volt
amperes, of a fixed luminous-discharge tube sign installation.
(h) An interior installation shall be provided with suitable adjacent means for
disconnecting all phases of the supply except the “neutral” in a three-phase four
wire circuit.
(i) For installations on the exterior of a building a suitable emergency fire-proof
linked switch to operate on all phases except the neutral in a three phase four wire
circuit shall be provided and fixed in a conspicuous position at not more than 2.75
metres above the ground.
(j) A special “caution” notice shall be affixed in a conspicuous place on the
door of every high voltage enclosure to the effect that the low voltage supply must
be cut off before the enclosure is opened.
(k) Where static condensers are used, they shall be installed on the load side
of the fuses and the primary (low voltage) side of the transformers.
(1) Where static condensers are used on primary side, means shall be
provided for automatically discharging the condensers when the supply is cut off;
Provided that static condensers or any circuit interrupting devices on the high or
extra-high voltage side shall not be used without the approval in writing of the
Inspector.
(2) The owner or user of any luminous tube sign or similar high voltage
installation shall not bring the same into use without giving to the Inspector not
less than 14 days notice in writing of his intention so to do.
1. Ins. by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985.
72. Additional provisions for supply to high voltage electrode boilers-
(1) Where a system having a point connected with earth is used for supply of
energy at high or extra-high voltage to an electrode boiler which is also connected
with earth, the following conditions shall apply: -
(a) The metal work of the electrode boiler shall be efficiently connected to the
metal sheathing and metallic armouring (if any) of the high voltage electric supply
line whereby energy is supplied to the electrode boiler.
(b) The supply of energy at high or extra-high voltage to the electrode boiler
shall be controlled by a suitable circuit-breaker so set as to operate in the event of
the phase currents becoming unbalanced to the extent of 10 per cent of the rated
current consumption of the electrode boiler under normal conditions of operation;
Provided that if in any case a higher setting is essential to ensure stability of
operation of the electrode boiler, the setting may be increased so as not to exceed
15 per cent of the rated current consumption of the electrode boiler under normal
conditions of operation.
(c) An inverse time element device may be used in conjunction with the
aforesaid circuit breaker to prevent the operation thereof unnecessarily on the
occurrence of unbalanced phase currents of momentary or short duration.
(d) The supplier shall serve a notice in writing on the telegraph-authority at
least seven days prior to the date on which such supply of energy is to be afforded
specifying the location of every point (including the earth connection of the
electrode boiler) at which the system is connected with earth.
(2) The owner or user of any high or extra-high voltage electrode boiler shall
not bring the same into use without giving the Inspector not less than 14 days’
notice in writing of his intention so to do.
73. Supply to X-ray and high frequency installation-
(1) Any person who proposes to employ or who is employing energy for the
purpose of operating an X-ray or similar high-frequency installation, shall comply
with the following conditions:-
(a) Mechanical barriers shall be provided to prevent too close an approach to
any high-voltage parts of the X-ray apparatus, except the X-ray tube and its leads,
unless such high-voltage parts have been rendered shock-proof by being shielded
by earthed metal or adequate insulating material.
(b) Where extra-high voltage generators operating at 300 peak KV or more are
used, such generators shall be installed in rooms separate from those containing
the other equipment and any step-up transformer employed shall be so installed
and protected as to prevent danger.
(c) A suitable switch shall be provided to control the circuit supplying a
generator, and shall be so arranged as to be open except while the door of the
room housing the generator is locked from the outside.
(d) X-ray tubes used in therapy shall be mounted in an earthed metal
enclosure.
(e) Every X-ray machine shall be provided with a millimeter or other suitable
measuring instrument, readily visible from the control position and connected, if
practicable, in the earthed lead, but guarded if connected in the high-voltage lead.
1[(ee) Notwithstanding the provisions of clause (e), earth. leakage circuit breaker
of sufficient rating shall be provided on the low voltage side to detect the leakage
in such X-ray installations.]
(f) This sub-rule shall not apply to shock-proof portable units or shockproof self
contained and stationary units.
Note: - The expression “shock-proof”, as applied to X-ray and high-frequency
equipment, shall mean that such equipment is guarded with earthed metal so that
no person may come into contact with any live part.
(2) (a) In the case of non-shock-proof equipment, overhead high-voltage
conductors, unless suitably guarded against personal contact, shall be adequately
spaced and high-voltage leads on tilting tables and fluroscopes shall be
adequately insulated or so surrounded by barriers as to prevent inadvertent
contact.
(b) The low voltage circuit of the step up transformer shall contain a manually
operated control device having overload protection, in addition to the over-current
device for circuit protection, and these devices shall have no exposed live parts
and for diagnostic work there shall be an additional switch in the said circuit, which
shall be of one of the following types:
(i) A switch with a spring or other mechanism that will open automatically
except while held close by the operator, or
(ii) A time switch which will open automatically after a definite period of time for
which it has been set.
(c) If more than one piece of apparatus be operated from the same high or
extra-high voltage source each shall be provided with a high or extra-high voltage
switch to give independent control.
(d) Low frequency current-carrying parts of a machine of the quenched gap or
open gap type shall be so insulated or guarded that they cannot be touched during
operation, the high frequency circuit proper which delivers high-frequency current
normally for the therapeutic purposes, being exempted.
(e) All X-ray generators having capacitors shall have suitable means for
discharging the capacitors manually.
(f) Except in the case of self-contained units, all 200 peak KV or higher, X-ray
generators shall have a sphere gap installed in the high-voltage system adjusted
so that it will break down on over-voltage surges.
(3) (a) All non-current carrying metal parts of tube stands, fluroscopes and
other apparatus shall be properly earthed and insulating floors, mats or platforms
shall be provided for operator in proximity to high or extra-high voltage parts
unless such parts have been rendered shock proof.
(b) Where short wave therapy machines are used, the treatment tables and
examining chairs shall be wholly non-metallic.
(4) The owner of any X-ray installations or similar high frequency apparatus
shall not bring the same into use without giving to the Inspector not less than 14
days’ notice in writing of his intention to do so.
Provided that the aforesaid notice shall not be necessary in the case of shockproof
portable X-ray and high-frequency equipment which have been inspected before
the commencement of their use and periodically, thereafter.
1. Ins. by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985.
CHAPTER VIII
1[OVERHEAD LINES, UNDER GROUND
CABLES AND GENERATING STATIONS]
1. Subs. by GSR 466, dt. 18.7.1991, w.e.f 17.8.1991.
74. Material and strength-
(1) All conductors of overhead lines other than those specified in sub-rule (1) of
rule 86 shall have a breaking strength of not less than 350 kg.
(2) Where the voltage is low and the span is of less than 15 metres and is on
the owner’s or consumer’s premises, a conductor having an actual breaking
strength of not less than 150 kg may be used.
75. Joints-Joints between conductors of overhead lines shall be mechanically
and electrically secure under the conditions of operation. The ultimate strength of
the joint shall not be less than 95 per cent of that of the conductor, and the
electrical conductivity not less than that of the conductor.
1[Provided that no conductor of an overhead line shall have more than two joints in
a span.]
1. Ins. by GSR 730, dt. 7.9.1989, w.e.f. 30.9.1989.
76. Maximum stresses: Factors of safety-
(1) (a) The owner of every overhead line shall ensure that it has the
following minimum factors of safety:-
(i) For metal supports 1.5
(ii) For mechanically processed concrete supports 2.0
(iii) For hand-moulded concrete supports 2.5
(iv) For wood supports 3.0.
The minimum factors of safety shall be based on such load as would cause failure
of the support to perform its function (assuming that the foundation and other
components of the structure are intact).
The aforesaid load shall be-
(i) Equivalent to the yield point stress or the modulus of rupture, as the case
may be, for supports subject to bending and vertical loads,
(ii) The crippling load for supports used struts.
The said owner shall also ensure that the strength of the supports in the direction
of the line is not less than one-fourth of the strength required in the direction
transverse to the line.
Provided that in the case of latticed steel or other compound structures, factors of
safety shall not be less than 1.5 under such broken wire conditions as may be
specified by the State Government in this behalf.
(b) The minimum factor of safety for stay-wires, guard-wires or bearer wires
shall be 2.5 based on the ultimate tensile strength of the wire.
(c) The minimum factor of safety for conductors shall be 2, based on their
ultimate tensile strength. In addition, the conductors tension at 320C, without
external load, shall not exceed the following percentages of the ultimate tensile
strength of the conductor: -
Initial unloaded tension 35 per cent
Final unloaded tension 25 per cent.
Provided that in the case of conductors having a cross section of a generally
triangular shape, such as conductors composed of 3-wires, the final unloaded
tension at 32’C shall not exceed 30 per cent of the ultimate tensile strength of such
conductor.
(2) For the purpose of calculating the factors of safety prescribed in sub-rule (l)-
(a) The maximum wind pressure shall be such as the State Government may
specify in each case;
(b) For cylindrical bodies the effective area shall be taken as two-thirds of the
projected area exposed to wind pressure;
(c) For latticed steel or other compound structures the wind pressure on the lee
side members shall be taken as one-half of the wind pressure on the windward
side members and the factors of safety shall be calculated on the crippling load of
struts and upon the elastic limit of tension members;
(d) The maximum and minimum temperatures shall be such as the State
Government may specify in each case.
(3) Notwithstanding anything contained in sub-rules (1) and (2), in localities
where overhead lines are liable to accumulations of ice or snow the State
Government may, by order in writing, specify the loading conditions for the
purpose of calculating the factor of safety.
77. Clearance above ground of the lowest conductor-
(1) No conductor of an overhead line, including service lines, erected across a
street shall at any part thereof be at a height of less than-
(a) For low and medium voltage lines 5.8 metres
(b) For high voltage lines 6.1 metres
(2) No conductor of an overhead line, including service lines, erected along
any street shall at any part thereof be at a height less than-
(a) For low and medium voltage lines 5.5 metres
(b) For high voltage lines 5.8 metres
(3) No conductor of in overhead line including service lines, erected
elsewhere than along or across any street shall be at a height less than-
(a) For low, medium and high voltages lines
upto and including 11,000 volts, if bare 4.6
metres
(b) For low, medium and high voltage
lines upto and including 11,000 volts, if insulated
4.0 metres
(c) For high voltage lines above 11,000 volts
5.2 metres
(4) For extra-high voltage lines the clearance above ground shall not be less
than 5.2 metres plus 0.3 metre for every 33,000 volts or part thereof by which the
voltage of the line exceeds 33,000 volts.
Provided that the minimum clearance along or across any street shall not be less
than 6.1 metres.
78. Clearance between conductors and trolley wires-
1[(l)] No conductor of an overhead line crossing a tramway or trolley bus route
using trolley wires shall have less than the following clearances above and trolley
wire-
(a) Low and medium voltage lines 1.2 metres.
Provided that where an insulated conductor suspended from a bearer
wire crosses over a trolley wire the minimum clearance for such insulated
conductor shall be 0.6 metre.
(b) High voltage lines up to and including 11,000 volts
1.8 metres
(c) High voltage lines above 11,000 volts
2.5 metres
(d) Extra-high voltage lines 3.0
metres
2[(2) In any case of a crossing referred to in sub-rule (1), whoever lays his line
later in time, shall provide the clearance between his own line and the line which
will be crossed in accordance with the provisions of said sub-rule.
Provided that if the later entrant is the owner of the lower line and is not able to
provide adequate clearance, he should bear the cost of modification of the upper
line so as to comply with this rule.]
1. Rule 78 renumbered as sub-rule (1) by GSR 528, dt. 11.7.1986, w.e.f.
19.7.1986.
2. Sub-rule (2) ins. by GSR 528, dt. 11.7.1986, w.e.f. 19.7.1986.
79. Clearances from buildings of low and medium voltage lines and service
lines-
(1) Where a low or medium voltage, overhead line passes above or adjacent
to or terminates on any building, the following minimum clearances from any
accessible point, on the basis of maximum sag, shall be observed: -
(a) For any flat roof, open balcony, verandah roof and lean-to-roof-
(i) When the line passes above the building a vertical clearance of 2.5
metres from the highest point, and
(ii) When the line passes adjacent to the building a horizontal clearance of 1.2
metres from the nearest point, and
(b) For pitched roof-
(i) When the line passes above the building a vertical clearance of 2.5
metres immediately under the lines, and
(ii) When the line passes adjacent to the building a horizontal clearance of 1.2
metres.
(2) Any conductor so situated as to have a clearance less than that specified
in sub-rule (1) shall be adequately insulated and shall be attached at suitable
intervals to a bare earthed bearer wire having a breaking strength of not less
than 350 kg.
(3) The horizontal clearance shall be measured when the line is at a
maximum deflection from the vertical due to wind pressure.
1[Explanation- For the purpose of this rule, expression “building” shall be deemed
to include any structure, whether permanent or temporary]
1. Added by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985.
80. Clearances from buildings of high and extra-high voltage lines-
(1) Where a high or extra-high voltage overhead line passes above or
adjacent to any building or part of a building it shall have on the basis of
maximum sag a vertical clearance above the highest part of the building
immediately under such line, of not less than-
(a) For high voltage lines upto and
including 33,000 volts
3.7 metres
(b) For extra-high voltage lines
3.7 metres plus 0.30 metre
for every additional 33,000
volts or part thereof.
(2) The horizontal clearance between the nearest conductor and any part of
such building shall, on the basis of maximum deflection due to wind pressure, be
not less than-
(a) For high voltage lines upto and
including 11,000 volts
1.2 metres
(b) For high voltage lines above
11,000 volts and up to and
including 33,000 volts
2.0 metres
(c) For extra-high voltage lines
2.0 metres plus 0.3
metre
for every additional
33,000 volts for part
thereof.
1[Explanation- For the purpose of this rule expression “building” shall be deemed
to include any structure, whether permanent or temporary]
1. Added by GSR 844, di. 31.7.1985. w.e.f- 7.9.1985.
81. Conductors at different voltages on same supports- Where conductors
forming parts of systems at different voltages are erected on the same supports,
the owner shall make adequate provision to guard against danger to linesman
and others from the lower voltage system being charged above its normal
working voltage by leakage from or contact with the higher voltage system and
the methods of construction and the clearances between the conductors of the
two systems shall be subject to the prior approval of the Inspector.
82. Erection of or alternation to buildings, structures, flood banks and
elevation of roads-
(1) If at any time subsequent to the erection of an overhead line (whether
covered with insulating material or bare), any person proposes to erect a new
building or structure or flood bank or to raise any road level or to carry out any
other type of work whether permanent or temporary or to make in or upon any
building or structure of flood bank or road, any permanent or temporary addition
or alternation, he and the contractor whom he employs to carry out the erection,
addition or alteration, shall if such work, building, structure, flood bank, road or
additions and alterations thereto, would, during or after the construction result in
contravention of any of the provisions of rule 77, 79 or 80, give notice in writing of
his intention to the supplier and to the Inspector and shall furnish therewith a
scale drawing showing the proposed building, structure, flood bank road, any
addition or alteration and scaffolding required during the construction.
(2) (a) On receipt of the notice referred to in sub-rule (1) or otherwise, the
supplier shall examine whether the line under reference was lawfully laid and
whether the person was liable to pay the cost of alteration and if so, send a
notice without undue delay, to such person together with an estimate of the cost
of the expenditure likely to be incurred to so after the overhead line and require
him to deposit, within 30 days of the receipt of the notice with the supplier, the
amount of the estimated cost.
(b) If the person referred to in sub-rule (1) disputes the suppliers estimated
cost of alteration of the overhead line or even the responsibility to pay such cost
the dispute may be referred to the Inspector by either of the parties whereupon
the same shall be decided by the Inspector.
(3) No work upon such building, structure, flood bank, road and addition or
alternation thereto shall be commenced or continued until the Inspector has
certified that the provisions of rule 77, 79 or 80 are not likely to be contravened
either during or after the aforesaid construction.
Provided that the Inspector may, if he is satisfied that the overhead line has been
so guarded as to secure the protection of persons or property from injury, or risk
of injury, permit the work to be executed prior to the alteration of the
overhead line or in the case of temporary addition or alteration, without
alteration of the overhead line.
(4) On receipt of the deposit, the supplier shall after the overhead line within
one month of the date of deposit or within such longer period as the Inspector
may allow and ensure that it shall not contravene the provisions of rule 77, 79 or
80 either during or after such construction.
(5) In the absence of an agreement to the contrary between the parties
concerned, the cost of such alteration of the overhead line laid down shall be
estimated on the following basis, namely: -
(a) The cost of additional material used on the alteration giving due credit for
the depreciated cost of the material which would be available from the existing
line;
(b) The wages of Labour employed in affecting the alteration;
(c) Supervision charges to the extent of 15 per cent of the wages mentioned
in clause (b); and
(d) Any charges incurred by the supplier in complying with the provisions of
section 16 of the Act in respect of such alterations.
(6) Where the estimated cost of the alteration of the overhead line is not
deposited the supplier shall be considered as an aggrieved party for the purpose
of this rule.
1[82A. Transporting and Storing of material near overhead lines-
(1) No rods, pipes or similar materials shall be taken below or in the vicinity of
any bare overhead conductors or lines if they are likely to infringe the provisions
for clearances under rules 79 and 80, unless such materials are transported
under the direct supervision of a competent person authorised in this behalf by
the owner of such overhead conductors or lines.
(2) Under no circumstances rods, pipes or other similar materials shall be
brought within the flash over distance of bare live conductors or lines; and
(3) No material or earth work or agricultural produce shall be dumped or
stored or trees grown below or in the vicinity of bare overhead conductors lines
so as to reduce the requisite safety clearances specified under rules 79 and 80.]
83. Clearances: General- For the purpose of computing the vertical clearance
of an overhead line, the maximum sag of any conductor shall be calculated on
the basis of the maximum sag in still air and the maximum temperature as
specified by the State Government under rule 76(2)(d). Similarly, for the purpose
of computing any horizontal clearance of an overhead line the maximum
deflection of any conductor shall be calculated on the basis of the wind pressure
specified by the State Government under rule 76(2)(a) or may be taken as 350,
whichever is greater.
1. Ins. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987.
84. Routes: Proximity to aerodromes- Overhead lines shall not be erected in
the vicinity of aerodromes until the aerodrome authorities have approved in
writing the route of the proposed lines.
85. Maximum interval between supports- All conductors shall be attached to
supports at intervals not exceeding the safe limits based on the ultimate tensile
strength of the conductor and the factor of safety prescribed in rule 76.
Provided that in the case of overhead lines carrying low or medium voltage
conductors, when erected in, over, along or across any street, the interval shall
not, without the consent in writing of the Inspector, exceed 65 metres.
86. Conditions to apply where telecommunication lines and power lines are
carried on same supports-
(1) Every overhead telecommunication line erected on supports carrying a
power line shall consist of conductors each having a breaking strength of not less
than 270 kg.
(2) Every telephone used on a telecommunication line erected on supports
carrying a power line shall be suitably guarded against lightning and shall be
protected by cutouts.
(3) Where a telecommunication line is erected on supports carrying a high or
extra-high voltage power line arrangement shall be made to safeguard any
person using the telephone against injury resulting from contact, leakage or
induction between such power and telecommunication lines.
87. Lines crossing or approaching each other-
(1) Where an overhead line crosses or is in proximity to any
telecommunication line, either the owner of the overhead line or the
telecommunication line, whoever lays his line later, shall arrange to provide for
protective devices or guarding arrangements, in a manner laid down in the Code
of Practice or the guidelines prepared by the Power and Telecommunication
Coordination Committee and subject to the provisions of the following sub-rules:-
(2) When it is intended to erect a telecommunication line or an overhead line
which will cross or be in proximity to an overhead line or a telecommunication
line, as the case may be, the person proposing to erect such line shall give one
month’s notice of his intention so to do along with the relevant details of
protection and drawings to the owner of the existing line.
1[(3) Where an overhead line crosses or is in proximity to another overhead
line, guarding arrangements shall be provided so as to guard against the
possibility of their coming into contact with each other.
Where an overhead line crosses another overhead line, clearances shall be as
under: -
2[Minimum clearances in metres between lines crossing each other.
Sl.
No.
Nominal System
Voltage
11-66 KV 110-132
KV
220 KV 400 KV 800 KV
1.
2.
3.
4.
5.
6.
Low & Medium
11-66 KV
110-132 KV
220 KV
400 KV
800 KV
2.44
2.44
3.05
4.58
5.49
7.94
3.05
3.05
3.05
4.58
5.49
7.94
4.58
4.58
4.58
4.58
5.49
7.94
5.49
5.49
5.49
5.49
5.49
7.94
7.94
7.94
7.94
7.94
7.94
7.94
Provided that no guardings are required when an extra high voltage line crosses
over another extra-high voltage, high voltage, medium or low voltage line or a
road or a tram subject to the condition that adequate clearances are provided
between the lowest conductor of the extra-high voltage line and the top most
conductor of the overhead line crossing underneath the extra-high voltage line
and the clearances as stipulated in rule 77 from the topmost surface of the road
is maintained.]
(4) A person erecting or proposing to erect a line which may cross or be in
proximity with an existing line, may normally provide guarding arrangements on
his own line or require the owner of the other overhead line to provide guarding
arrangements as referred to in sub-rule, (3).
(5) In all cases referred to in the preceding sub-rules the expenses of
providing the guarding arrangements or protective devices shall be borne by the
person whose line was last erected.
(6) Where two lines cross, the crossing shall be made as nearly at right
angles the nature of the case admits and as near the support of the line as
practicable, and the support of the lower line shall not be erected below the
upper line.
(7) The guarding arrangements shall ordinarily be carried out by the owner of
the supports on which it is made and he shall be responsible for its efficient
Maintenance.
(8) All work required to be done by or under this rule shall be carried out to
the satisfaction of the Inspector.
1. Subs. by GSR 256, dt. 28.2.1983, w.e.f. 26.3.1983.
2. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
88. Guarding-
(1) Where guarding is required under these rules the provisions of sub-rules
(2) to (4) shall apply.
(2) Every guard-wire shall be connected with earth at each point at which its
electrical continuity is broken.
(3) Every guard-wire shall have an actual breaking strength of not less than
635 kg and if made of iron or steel, shall be galvanised.
(5) Lines crossing trolley-wires- In the case of a crossing over a trolley-wire
the guarding shall fulfil the following conditions, namely:-
(a) Where there is only one trolley-wire, two guard-wires shall be erected as
in diagram A;
(b) Where there are two trolley-wires and the distance between them does not
exceed 40 cms, two guard-wires shall be erected as in diagram B;
(c) Where there are two trolley wires and the distance between them exceeds
40 cms but does not exceed 1.2 metres, three guard-wires shall be erected as in
diagram C;
(d) Where there are two trolley--wires and the distance between them
exceeds 1.2 metres, each trolley-wire shall be separately guarded as in diagram
D;
(e) The rise of the trolley boom shall be so limited that the trolley leaves the
trolley-wire, it shall not foul the guard-wires; and
(f) Where a telegraph-line is liable to fall or be blown down upon an arm,
stay-wire or span-wire and so slide down upon a trolley-wire, guard hooks shall
be provided to prevent such sliding.
20 Cms 20 Cms
0 0
min 60 Cms
0
DIAGRAM-A
20 Cms 20 Cms 20 Cms 20 Cms
0 0 0 0 0
min min min min
60 Cms 60 Cms 60Cms 60 Cms
up to 40 Cms Over 40 Cms &
up to 1.2 M
DIAGRAM B DIAGRAM C
20 Cms 20 Cms 20 Cms 20 Cms
0 0 0 0
MIN. MIN.
60 Cms 60 Cms
over 1.2 mts.
DIAGRAM D
89. Service-lines from Overhead lines- No Service-line or tapping shall be
taken off an overhead line except at a point of support.
1[Provided that the number of tappings per conductor shall not be more than four
in case of low and medium voltage connections.]
1. Added by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
90. Earthing-
(1) All metal supports and all reinforced and prestressed cement concrete
supports of overhead lines and metallic fittings attached thereto, shall be
permanently and efficiently earthed. For this purpose a continuous earth wire
shall be provided and securely fastened to each pole and connected with earth
ordinarily at three points in every km., the spacing between the points being as
nearly equidistance as possible. Alternatively, each support and the metallic
fitting attached thereto shall be efficiently earthed.
1[(IA) Metallic bearer wire used for supporting insulated wire of low and medium
voltage overhead service lines shall be efficiently earthed or insulated.]
(2) Each stay-wire shall be similarly earthed unless insulator has been placed
in it at a height not less than 3.0 metres from the ground.
1. Subs. by GSR 732, dt. 18.6.1985, w.e.f. 3.8.1985.
91. Safety and protective devices-
(1) Every overhead line, (not being suspended from a dead bearer wire and
not being covered with insulating material and not being a trolley-wire) erected
over any part of street or other public place or in any factory or mine or on any
consumers’ premises shall be protected with a device approved by the Inspector
for rendering the line electrically harmless in case it breaks.
(2) An Inspector may by notice in writing require the owner of any such
overhead line wherever it may be erected to protect it in the manner specified in
sub-rule(l).
1[(3) The owner of every high and extra-high voltage overhead line shall make
adequate arrangements to the satisfaction of the Inspector to prevent
unauthorised persons from ascending any of the supports of such overhead lines
which can be easily climbed upon without the help of a ladder or special
appliances. Rails, reinforced cement concrete poles and pre-stressed cement
concrete poles without steps, tubular poles, wooden supports without steps, I-
sections and channels shall be deemed as supports which cannot be easily
climbed upon for the purpose of this rule.]
1. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
92. Protection against lightning-
(1) The owner of every overhead line 1[,sub-station or generating station]
which is so exposed as to be liable to injury from lightning shall adopt efficient
means for diverting to earth any electrical surges due to lightning.
2[(2) The earthing lead for any lightning arrestor shall not pass through any iron
or steel pipe, but shall be taken as directly as possible from the lightning- arrestor
to a separate earth electrode and/or junction of the earth mat already provided
for the high and extra-high voltage sub-station subject to the avoidance of bends
wherever practicable.
Note- A vertical ground electrode shall be connected to this junction of the earth
mat.]
1. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
2. Subs. by GSR 1050, dt. 9.11.1985.
93. Unused overhead lines-
(1) Where an overhead line ceases to be used as an electric supply line, the
owner shall maintain it in a safe mechanical condition in accordance with rule 76
or shall remove it.
(2) Where any overhead line ceases to be used as an electric supply line, an
Inspector may, by a notice in writing served on the owner, require him to maintain
it in a safe mechanical condition or to remove it within fifteen days of the receipt
of the notice.
CHAPTER IX
ELECTRIC TRACTION
94. Additional rules for electric traction-
(1) The rules in this Chapter apply only where energy is used for purposes of
traction.
Provided that nothing in this Chapter shall apply to energy used for the public
carriage of passengers, animals or goods on, or for the lighting or ventilation of
the rolling stock of any railway or tramway subject to the provisions of the Indian
Railways Act, 1890 (9 of 1890).
(2) In this Chapter the conductor used for transmitting energy to a vehicle is
referred to as the “line” and the other conductor as the “return”.
(3) The owner of the line, return, rails or trolley wire, as the case may be, shall
be responsible for the due observance of rules 95 to 108.
95. Voltage of supply to vehicle- No person shall supply energy at high or
extra-high voltage to any trolley-wire or other conductor used in direct electrical
and mechanical connection with any vehicle, except with the written approval of
the Central or the State Government, as the case may be, and subject to such
conditions as the State Government may think reasonable and proper in the
circumstances.
96. Insulation of lines- Every line shall be insulated throughout.
97. Insulation of returns-
(1) Where any rails on which cars run, or any conductors laid between or
within 0.9 metre of such rails, form any part of a return, such part may be
uninsulated. All other returns or parts of a return, shall be insulated, unless they
are of such conductivity as to secure the conditions required by sub-rules (2) and
(3) of rule 98.
(2) Where any part of a return is uninsulated, it shall be connected with the
negative or neutral of the system.