Rule 64A, THE INDIAN ELECTRICITY RULES, 1956: Additional provisions for use of energy at high and extra-high voltage- The following additional provisions shall be observed where energy at high or extra- high voltage is supplied, converted, transferred or used, namely

THE INDIAN ELECTRICITY RULES, 1956 - Rule 64A

Text of rule 64A

Additional provisions for use of energy at high and extra-high voltage- The following additional provisions shall be observed where energy at high or extra- high voltage is supplied, converted, transferred or used, namely

1[64A. Additional provisions for use of energy at high and extra-high voltage- The following additional provisions shall be observed where energy at high or extra- high voltage is supplied, converted, transferred or used, namely: - (1) Inter-locks- Suitable inter-locks shall be provided in the following cases: - (a) Isolators and the controlling circuit breakers shall be interlocked so that the isolators cannot be operated unless the corresponding breaker is in open position; (b) Isolators and the corresponding earthing switches shall be interlocked so that no earthing switch can be closed unless and until the corresponding isolator is in open position; (c) Where two or more supplies are not intended to be operated in parallel, the respective circuit breakers or linked switches controlling the supplies shall be inter- locked to prevent possibility of any inadvertent paralleling or feedback; (d) When two or more transformers are operated in parallel, the system shall be so arranged as to trip the secondary breaker of a transformer in case the primary breaker of that transformer trips; (e) All gates or doors which give access to live parts of an installation shall be inter-locked in such a way that these cannot be opened unless the live parts are made dead. Proper discharging and earthing of these parts should be ensured before any person comes in close proximity of such parts; (f) Where two or more generators operate in parallel and neutral switching is adopted, inter-lock shall be provided to ensure that generator breaker cannot be closed unless one of the neutrals is connected to the earthing system. (2) Protection- All systems and circuits shall be so protected as to automatically disconnect the supply under abnormal conditions. The following protection shall be provided, namely: - (a) Over current protection to disconnect the supply automatically if the rated current of the equipment, cable or supply line is exceeded for a time which the equipment, cable or supply line is not designed to withstand; (b) Earth-fault/earth leakage protection to disconnect the supply automatically if the earth fault current exceeds the limit of current for keeping the contact potential within the reasonable values; (c) Gas pressure type protection to given alarm and tripping shall be provided on all transformers of ratings 1000 KVA and above; (d) Transformers of capacity 10 MVA and above shall be protected against incipient faults by differential protection; and (e) All generators with rating of 100 KVA and above shall be protected against earth fault/leakage. All generators of rating 1000KVA and above shall be protected against faults within the generator winding using restricted earth fault protection or differential protection or by both.] 1. Ins. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987. 65. Testing, Operation and Maintenance- (1) Before approval is accorded by the Inspector under rule 63, the manufacturer’s test certificates shall, if required, be produced for all the routine tests as required under the relevant Indian Standard. (2) No new HV or EHV apparatus, cable or supply line shall be commissioned unless such apparatus, cable or supply line are subjected to site tests as per relevant code of practice of the 1[Bureau of Indian Standards]. (3) No HV of EHV apparatus, cable or supply line which has been kept disconnected, for a period of 6 months or more, from the system for alterations or repair shall be corrected to the system until such apparatus, cable or supply line are subjected to the relevant tests as per code of practice of 1[Bureau of Indian Standards.] (4) Notwithstanding the provisions of sub-rules (1) to (3) (both inclusive) the Inspector may require certain additional tests to be carried out before charging the installations or subsequently. (5) All apparatus, cables and supply lines shall be maintained in healthy conditions and tests shall be carried out periodically as per the relevant codes of practice of the 1[Bureau of Indian Standards]. (6) Records of all tests, trappings, maintenance works and repairs of all equipments, cables and supply lines shall be duly kept in such a way that these records can be compared with earlier ones. (7) It shall be the responsibility of the owner of all HV and EHV installations to maintain and operate the installations in a condition free from danger and as recommended by the manufacturer and/or by the relevant codes of practice of the 1[Bureau of Indian Standards] and/or by the Inspector.] 1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 66. Metal sheathed electric supply lines. Precautions against excess leakage- (1) The following provisions shall apply to electric supply lines (other than overhead lines 1[***] for use at high or extra-high voltage: - (a) The conductors shall be enclosed in metal sheathing which shall be electrically continuous and connected with earth, and the conductivity of the metal sheathing shall be maintained and reasonable precautions taken where necessary to avoid corrosion of the sheathing; Provided that in the case of thermoplastic insulated and sheathed cables with metallic armour the metallic wire or tape armour shall be considered as metal sheathing for the purpose of this rule; Provided further that this rule shall not apply to cable with thermoplastic insulation without any metallic screen or armour. 2[(b) The resistance of the earth connection with metallic sheath shall be kept low enough to permit the controlling circuit breaker or cut-out to operate in the event of any failure of insulation between the metallic sheath and the conductor.] (c) Where an electric supply-line as aforesaid has concentric cables and the external conductor is insulated from an outer metal sheathing and connected with earth, the external conductor may be regarded as the metal sheathing for the purposes of this rule provided that the foregoing provisions as to conductivity are complied with. (2) Nothing in the provisions of sub-rule (1) shall preclude the employment in generating stations, sub-stations and switch-stations (including outdoor substations and outdoor switch-stations) of conductors for use at high or extra- high voltages which are not enclosed in metal sheathing or preclude the use of electric supply lines laid before the prescribed date to which the provisions of these rules apply 1. The words “of a supplier” omitted by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987. 2. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 67. Connection with earth- 1[(1) All non-current carrying metal parts associated with HV/EHV installation shall be effectively earthed to a grounding system or mat which will: - (a) Limit the touch and step potential to tolerable values; (b) Limit the ground potential rise to tolerable values so as to prevent danger due to transfer of potential through ground, earth wires, cables sheath fences, pipe lines, etc.; (c) Maintain the resistance of the earth connection to such a value as to make operation of the protective device effective. (lA) In the case of star-connected system with earthed neutrals or delta connected system with earthed artificial neutral point: - (a) The neutral point of every generator and transformer shall be earthed by connecting it to the earthing system as defined in rule 61(4) and hereinabove by not less than two separate and distinct connections; Provided that the neutral point of a generator may be connected to the earthing system through an impedance to limit the fault current to the earth; Provided further that in the case of multi-machine system neutral switching may be resorted to, for limiting the injurious effect of harmonic current circulation in the system; (b) In the event of an appreciable harmonic current flowing in the neutral connection so as to cause interference, with communication circuits, the generator or transformer neutral, shall be earthed through a suitable impedance; (c) In case of the delta connected system the neutral point shall be obtained by the insertion of a grounding transformer and current limiting resistance or impedance wherever considered necessary at the commencement of such a system.] (2) Single-phase high or extra-high voltage systems shall be earthed in a manner approved by the Inspector. (3) In the case of a system comprising electric supply lines having concentric cables, the external conductor shall be the one to be connected with earth. (4) Where a supplier proposes to connected with earth an existing system for use at high or extra-high voltage which has not hitherto been so connected with earth he shall give not less than fourteen days’ notice in writing together with particulars to the telegraph-authority of the proposed connection with earth. (5) (a) Where the earthing lead and earth connection are used only in connection with earthing guards erected under high or extra-high voltage overhead lines where they cross a telecommunication line or a railway line, and where such lines are equipped with earth leakage relays of a type and setting approved by the Inspector, the resistance shall not exceed 25 ohms. (b) Every earthing system belonging to either the supplier or the consumer shall be tested for its resistance to earth on a dry day during dry season not less than once a year. Records of such tests shall be maintained and shall be produced, if required before the Inspector or any officer appointed to assist him and authorised under sub-rule (2) of rule 4A. (6) In so far as the provisions of rule 61 are consistent with the provisions of this rule, all connections with earth shall also comply with the provisions of that rule. 1. Subs. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987. 68. General conditions as to transformation and control of energy- (1) Where energy at high or extra-high voltage is transformed, converted, regulated or otherwise controlled in sub-stations or switch-stations (including outdoor substations and out-door switch-stations) or in street boxes constructed underground, the following provisions shall have effect: - 1[(a) Sub-stations and switch-stations shall preferably be erected above ground, but where necessarily constructed underground due provisions for ventilation and drainage shall be made and any space housing switchgear shall not be used for storage of any materials especially inflammable and combustible materials or refuse.] (b) Outdoor sub-station is except pole type sub-stations and. outdoor switch- stations shall (unless the apparatus is completely enclosed in a metal covering connected with earth, the said apparatus also being connected with the system by armoured cables) be efficiently protected by fencing not less than 1.8 metres in height or other means so as to prevent access to the electric-supply lines and apparatus therein by an unauthorised person. (c) Underground street boxes (other than sub-stations) which contain transformers shall not contain switches or other apparatus, and switches, cut-outs or other apparatus required for controlling or other purposes shall be fixed in separate receptacles above ground wherever practicable. (2) Where energy is transformed, suitable provisions shall be made either by connecting with earth a point of the system at the lower voltage or otherwise to guard against danger by reason of the said system becoming accidentally charged above its normal voltage by leakage from a contact with the system at the higher voltage. 1. Subs. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987. 69. Pole type sub-stations- Where platform type construction is used for a pole type sub-station and sufficient space for a person to stand on the platform is provided a substantial hand rail shall be built around the said platform and if the hand rail is of metal, it shall be connected with earth; Provided that in the case of pole type sub-station on wooden supports and wooden platform the metal hand-rail shall not be connected with earth. 70. Condensers- Suitable provision shall be made for immediate and automatic discharge of every static condenser on disconnection of supply. 71. Additional provisions for supply to high voltage luminous tube sign installation- (1) Any person who proposes to use or who is using energy for the purpose of operating a luminous tube sign installation, or who proposes to transform or who is transforming energy to a high voltage for any such purpose shall comply with the following conditions: - (a) All live parts of the installation (including all apparatus and live conductors in the secondary circuit, but excluding tubes except in the neighbourhood of their terminals) shall be inaccessible to unauthorised persons and such parts shall be effectively screened. (b) Irrespective of the method of obtaining the voltage of the circuit which feeds the luminous discharge tube sign, no part of any conductor of such circuit shall be in metallic connection (except in respect of its connection with earth) with any conductor of the supply system or with the primary winding of the transformer. (c) All live parts of an exterior installation shall be so disposed as to protect them against the effects of the weather and such installation shall be so arranged and separated from the surroundings as to limit, as far as possible, the spreading of fire. (d) The secondary circuit shall be permanently earthed at the transformer and the core of every transformer shall be earthed. (e) Where the conductors of the primary circuit are not in metallic connection with the supply conductors, (e.g., where a motor-generator or a double-wound convertor is used), one phase of such primary circuit shall be permanently earthed at the motor generator or convertor, or at the transformer. 1[(ee) An earth leakage circuit breaker of sufficient rating shall be provided on the low voltage side to detect the leakage in such luminous tube sign installations.] (f) A final sub-circuit which forms the primary circuit of a fixed luminous discharge tube sign installation shall be reserved solely for such purpose. (g) A separate primary final sub-circuit shall be provided for each transformer or each group of transformers having an aggregate input not exceeding 1,000 volt amperes, of a fixed luminous-discharge tube sign installation. (h) An interior installation shall be provided with suitable adjacent means for disconnecting all phases of the supply except the “neutral” in a three-phase four wire circuit. (i) For installations on the exterior of a building a suitable emergency fire-proof linked switch to operate on all phases except the neutral in a three phase four wire circuit shall be provided and fixed in a conspicuous position at not more than 2.75 metres above the ground. (j) A special “caution” notice shall be affixed in a conspicuous place on the door of every high voltage enclosure to the effect that the low voltage supply must be cut off before the enclosure is opened. (k) Where static condensers are used, they shall be installed on the load side of the fuses and the primary (low voltage) side of the transformers. (1) Where static condensers are used on primary side, means shall be provided for automatically discharging the condensers when the supply is cut off; Provided that static condensers or any circuit interrupting devices on the high or extra-high voltage side shall not be used without the approval in writing of the Inspector. (2) The owner or user of any luminous tube sign or similar high voltage installation shall not bring the same into use without giving to the Inspector not less than 14 days notice in writing of his intention so to do. 1. Ins. by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985. 72. Additional provisions for supply to high voltage electrode boilers- (1) Where a system having a point connected with earth is used for supply of energy at high or extra-high voltage to an electrode boiler which is also connected with earth, the following conditions shall apply: - (a) The metal work of the electrode boiler shall be efficiently connected to the metal sheathing and metallic armouring (if any) of the high voltage electric supply line whereby energy is supplied to the electrode boiler. (b) The supply of energy at high or extra-high voltage to the electrode boiler shall be controlled by a suitable circuit-breaker so set as to operate in the event of the phase currents becoming unbalanced to the extent of 10 per cent of the rated current consumption of the electrode boiler under normal conditions of operation; Provided that if in any case a higher setting is essential to ensure stability of operation of the electrode boiler, the setting may be increased so as not to exceed 15 per cent of the rated current consumption of the electrode boiler under normal conditions of operation. (c) An inverse time element device may be used in conjunction with the aforesaid circuit breaker to prevent the operation thereof unnecessarily on the occurrence of unbalanced phase currents of momentary or short duration. (d) The supplier shall serve a notice in writing on the telegraph-authority at least seven days prior to the date on which such supply of energy is to be afforded specifying the location of every point (including the earth connection of the electrode boiler) at which the system is connected with earth. (2) The owner or user of any high or extra-high voltage electrode boiler shall not bring the same into use without giving the Inspector not less than 14 days’ notice in writing of his intention so to do. 73. Supply to X-ray and high frequency installation- (1) Any person who proposes to employ or who is employing energy for the purpose of operating an X-ray or similar high-frequency installation, shall comply with the following conditions:- (a) Mechanical barriers shall be provided to prevent too close an approach to any high-voltage parts of the X-ray apparatus, except the X-ray tube and its leads, unless such high-voltage parts have been rendered shock-proof by being shielded by earthed metal or adequate insulating material. (b) Where extra-high voltage generators operating at 300 peak KV or more are used, such generators shall be installed in rooms separate from those containing the other equipment and any step-up transformer employed shall be so installed and protected as to prevent danger. (c) A suitable switch shall be provided to control the circuit supplying a generator, and shall be so arranged as to be open except while the door of the room housing the generator is locked from the outside. (d) X-ray tubes used in therapy shall be mounted in an earthed metal enclosure. (e) Every X-ray machine shall be provided with a millimeter or other suitable measuring instrument, readily visible from the control position and connected, if practicable, in the earthed lead, but guarded if connected in the high-voltage lead. 1[(ee) Notwithstanding the provisions of clause (e), earth. leakage circuit breaker of sufficient rating shall be provided on the low voltage side to detect the leakage in such X-ray installations.] (f) This sub-rule shall not apply to shock-proof portable units or shockproof self contained and stationary units. Note: - The expression “shock-proof”, as applied to X-ray and high-frequency equipment, shall mean that such equipment is guarded with earthed metal so that no person may come into contact with any live part. (2) (a) In the case of non-shock-proof equipment, overhead high-voltage conductors, unless suitably guarded against personal contact, shall be adequately spaced and high-voltage leads on tilting tables and fluroscopes shall be adequately insulated or so surrounded by barriers as to prevent inadvertent contact. (b) The low voltage circuit of the step up transformer shall contain a manually operated control device having overload protection, in addition to the over-current device for circuit protection, and these devices shall have no exposed live parts and for diagnostic work there shall be an additional switch in the said circuit, which shall be of one of the following types: (i) A switch with a spring or other mechanism that will open automatically except while held close by the operator, or (ii) A time switch which will open automatically after a definite period of time for which it has been set. (c) If more than one piece of apparatus be operated from the same high or extra-high voltage source each shall be provided with a high or extra-high voltage switch to give independent control. (d) Low frequency current-carrying parts of a machine of the quenched gap or open gap type shall be so insulated or guarded that they cannot be touched during operation, the high frequency circuit proper which delivers high-frequency current normally for the therapeutic purposes, being exempted. (e) All X-ray generators having capacitors shall have suitable means for discharging the capacitors manually. (f) Except in the case of self-contained units, all 200 peak KV or higher, X-ray generators shall have a sphere gap installed in the high-voltage system adjusted so that it will break down on over-voltage surges. (3) (a) All non-current carrying metal parts of tube stands, fluroscopes and other apparatus shall be properly earthed and insulating floors, mats or platforms shall be provided for operator in proximity to high or extra-high voltage parts unless such parts have been rendered shock proof. (b) Where short wave therapy machines are used, the treatment tables and examining chairs shall be wholly non-metallic. (4) The owner of any X-ray installations or similar high frequency apparatus shall not bring the same into use without giving to the Inspector not less than 14 days’ notice in writing of his intention to do so. Provided that the aforesaid notice shall not be necessary in the case of shockproof portable X-ray and high-frequency equipment which have been inspected before the commencement of their use and periodically, thereafter. 1. Ins. by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985. CHAPTER VIII 1[OVERHEAD LINES, UNDER GROUND CABLES AND GENERATING STATIONS] 1. Subs. by GSR 466, dt. 18.7.1991, w.e.f 17.8.1991. 74. Material and strength- (1) All conductors of overhead lines other than those specified in sub-rule (1) of rule 86 shall have a breaking strength of not less than 350 kg. (2) Where the voltage is low and the span is of less than 15 metres and is on the owner’s or consumer’s premises, a conductor having an actual breaking strength of not less than 150 kg may be used. 75. Joints-Joints between conductors of overhead lines shall be mechanically and electrically secure under the conditions of operation. The ultimate strength of the joint shall not be less than 95 per cent of that of the conductor, and the electrical conductivity not less than that of the conductor. 1[Provided that no conductor of an overhead line shall have more than two joints in a span.] 1. Ins. by GSR 730, dt. 7.9.1989, w.e.f. 30.9.1989. 76. Maximum stresses: Factors of safety- (1) (a) The owner of every overhead line shall ensure that it has the following minimum factors of safety:- (i) For metal supports 1.5 (ii) For mechanically processed concrete supports 2.0 (iii) For hand-moulded concrete supports 2.5 (iv) For wood supports 3.0. The minimum factors of safety shall be based on such load as would cause failure of the support to perform its function (assuming that the foundation and other components of the structure are intact). The aforesaid load shall be- (i) Equivalent to the yield point stress or the modulus of rupture, as the case may be, for supports subject to bending and vertical loads, (ii) The crippling load for supports used struts. The said owner shall also ensure that the strength of the supports in the direction of the line is not less than one-fourth of the strength required in the direction transverse to the line. Provided that in the case of latticed steel or other compound structures, factors of safety shall not be less than 1.5 under such broken wire conditions as may be specified by the State Government in this behalf. (b) The minimum factor of safety for stay-wires, guard-wires or bearer wires shall be 2.5 based on the ultimate tensile strength of the wire. (c) The minimum factor of safety for conductors shall be 2, based on their ultimate tensile strength. In addition, the conductors tension at 320C, without external load, shall not exceed the following percentages of the ultimate tensile strength of the conductor: - Initial unloaded tension 35 per cent Final unloaded tension 25 per cent. Provided that in the case of conductors having a cross section of a generally triangular shape, such as conductors composed of 3-wires, the final unloaded tension at 32’C shall not exceed 30 per cent of the ultimate tensile strength of such conductor. (2) For the purpose of calculating the factors of safety prescribed in sub-rule (l)- (a) The maximum wind pressure shall be such as the State Government may specify in each case; (b) For cylindrical bodies the effective area shall be taken as two-thirds of the projected area exposed to wind pressure; (c) For latticed steel or other compound structures the wind pressure on the lee side members shall be taken as one-half of the wind pressure on the windward side members and the factors of safety shall be calculated on the crippling load of struts and upon the elastic limit of tension members; (d) The maximum and minimum temperatures shall be such as the State Government may specify in each case. (3) Notwithstanding anything contained in sub-rules (1) and (2), in localities where overhead lines are liable to accumulations of ice or snow the State Government may, by order in writing, specify the loading conditions for the purpose of calculating the factor of safety. 77. Clearance above ground of the lowest conductor- (1) No conductor of an overhead line, including service lines, erected across a street shall at any part thereof be at a height of less than- (a) For low and medium voltage lines 5.8 metres (b) For high voltage lines 6.1 metres (2) No conductor of an overhead line, including service lines, erected along any street shall at any part thereof be at a height less than- (a) For low and medium voltage lines 5.5 metres (b) For high voltage lines 5.8 metres (3) No conductor of in overhead line including service lines, erected elsewhere than along or across any street shall be at a height less than- (a) For low, medium and high voltages lines upto and including 11,000 volts, if bare 4.6 metres (b) For low, medium and high voltage lines upto and including 11,000 volts, if insulated 4.0 metres (c) For high voltage lines above 11,000 volts 5.2 metres (4) For extra-high voltage lines the clearance above ground shall not be less than 5.2 metres plus 0.3 metre for every 33,000 volts or part thereof by which the voltage of the line exceeds 33,000 volts. Provided that the minimum clearance along or across any street shall not be less than 6.1 metres. 78. Clearance between conductors and trolley wires- 1[(l)] No conductor of an overhead line crossing a tramway or trolley bus route using trolley wires shall have less than the following clearances above and trolley wire- (a) Low and medium voltage lines 1.2 metres. Provided that where an insulated conductor suspended from a bearer wire crosses over a trolley wire the minimum clearance for such insulated conductor shall be 0.6 metre. (b) High voltage lines up to and including 11,000 volts 1.8 metres (c) High voltage lines above 11,000 volts 2.5 metres (d) Extra-high voltage lines 3.0 metres 2[(2) In any case of a crossing referred to in sub-rule (1), whoever lays his line later in time, shall provide the clearance between his own line and the line which will be crossed in accordance with the provisions of said sub-rule. Provided that if the later entrant is the owner of the lower line and is not able to provide adequate clearance, he should bear the cost of modification of the upper line so as to comply with this rule.] 1. Rule 78 renumbered as sub-rule (1) by GSR 528, dt. 11.7.1986, w.e.f. 19.7.1986. 2. Sub-rule (2) ins. by GSR 528, dt. 11.7.1986, w.e.f. 19.7.1986. 79. Clearances from buildings of low and medium voltage lines and service lines- (1) Where a low or medium voltage, overhead line passes above or adjacent to or terminates on any building, the following minimum clearances from any accessible point, on the basis of maximum sag, shall be observed: - (a) For any flat roof, open balcony, verandah roof and lean-to-roof- (i) When the line passes above the building a vertical clearance of 2.5 metres from the highest point, and (ii) When the line passes adjacent to the building a horizontal clearance of 1.2 metres from the nearest point, and (b) For pitched roof- (i) When the line passes above the building a vertical clearance of 2.5 metres immediately under the lines, and (ii) When the line passes adjacent to the building a horizontal clearance of 1.2 metres. (2) Any conductor so situated as to have a clearance less than that specified in sub-rule (1) shall be adequately insulated and shall be attached at suitable intervals to a bare earthed bearer wire having a breaking strength of not less than 350 kg. (3) The horizontal clearance shall be measured when the line is at a maximum deflection from the vertical due to wind pressure. 1[Explanation- For the purpose of this rule, expression “building” shall be deemed to include any structure, whether permanent or temporary] 1. Added by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985. 80. Clearances from buildings of high and extra-high voltage lines- (1) Where a high or extra-high voltage overhead line passes above or adjacent to any building or part of a building it shall have on the basis of maximum sag a vertical clearance above the highest part of the building immediately under such line, of not less than- (a) For high voltage lines upto and including 33,000 volts 3.7 metres (b) For extra-high voltage lines 3.7 metres plus 0.30 metre for every additional 33,000 volts or part thereof. (2) The horizontal clearance between the nearest conductor and any part of such building shall, on the basis of maximum deflection due to wind pressure, be not less than- (a) For high voltage lines upto and including 11,000 volts 1.2 metres (b) For high voltage lines above 11,000 volts and up to and including 33,000 volts 2.0 metres (c) For extra-high voltage lines 2.0 metres plus 0.3 metre for every additional 33,000 volts for part thereof. 1[Explanation- For the purpose of this rule expression “building” shall be deemed to include any structure, whether permanent or temporary] 1. Added by GSR 844, di. 31.7.1985. w.e.f- 7.9.1985. 81. Conductors at different voltages on same supports- Where conductors forming parts of systems at different voltages are erected on the same supports, the owner shall make adequate provision to guard against danger to linesman and others from the lower voltage system being charged above its normal working voltage by leakage from or contact with the higher voltage system and the methods of construction and the clearances between the conductors of the two systems shall be subject to the prior approval of the Inspector. 82. Erection of or alternation to buildings, structures, flood banks and elevation of roads- (1) If at any time subsequent to the erection of an overhead line (whether covered with insulating material or bare), any person proposes to erect a new building or structure or flood bank or to raise any road level or to carry out any other type of work whether permanent or temporary or to make in or upon any building or structure of flood bank or road, any permanent or temporary addition or alternation, he and the contractor whom he employs to carry out the erection, addition or alteration, shall if such work, building, structure, flood bank, road or additions and alterations thereto, would, during or after the construction result in contravention of any of the provisions of rule 77, 79 or 80, give notice in writing of his intention to the supplier and to the Inspector and shall furnish therewith a scale drawing showing the proposed building, structure, flood bank road, any addition or alteration and scaffolding required during the construction. (2) (a) On receipt of the notice referred to in sub-rule (1) or otherwise, the supplier shall examine whether the line under reference was lawfully laid and whether the person was liable to pay the cost of alteration and if so, send a notice without undue delay, to such person together with an estimate of the cost of the expenditure likely to be incurred to so after the overhead line and require him to deposit, within 30 days of the receipt of the notice with the supplier, the amount of the estimated cost. (b) If the person referred to in sub-rule (1) disputes the suppliers estimated cost of alteration of the overhead line or even the responsibility to pay such cost the dispute may be referred to the Inspector by either of the parties whereupon the same shall be decided by the Inspector. (3) No work upon such building, structure, flood bank, road and addition or alternation thereto shall be commenced or continued until the Inspector has certified that the provisions of rule 77, 79 or 80 are not likely to be contravened either during or after the aforesaid construction. Provided that the Inspector may, if he is satisfied that the overhead line has been so guarded as to secure the protection of persons or property from injury, or risk of injury, permit the work to be executed prior to the alteration of the overhead line or in the case of temporary addition or alteration, without alteration of the overhead line. (4) On receipt of the deposit, the supplier shall after the overhead line within one month of the date of deposit or within such longer period as the Inspector may allow and ensure that it shall not contravene the provisions of rule 77, 79 or 80 either during or after such construction. (5) In the absence of an agreement to the contrary between the parties concerned, the cost of such alteration of the overhead line laid down shall be estimated on the following basis, namely: - (a) The cost of additional material used on the alteration giving due credit for the depreciated cost of the material which would be available from the existing line; (b) The wages of Labour employed in affecting the alteration; (c) Supervision charges to the extent of 15 per cent of the wages mentioned in clause (b); and (d) Any charges incurred by the supplier in complying with the provisions of section 16 of the Act in respect of such alterations. (6) Where the estimated cost of the alteration of the overhead line is not deposited the supplier shall be considered as an aggrieved party for the purpose of this rule. 1[82A. Transporting and Storing of material near overhead lines- (1) No rods, pipes or similar materials shall be taken below or in the vicinity of any bare overhead conductors or lines if they are likely to infringe the provisions for clearances under rules 79 and 80, unless such materials are transported under the direct supervision of a competent person authorised in this behalf by the owner of such overhead conductors or lines. (2) Under no circumstances rods, pipes or other similar materials shall be brought within the flash over distance of bare live conductors or lines; and (3) No material or earth work or agricultural produce shall be dumped or stored or trees grown below or in the vicinity of bare overhead conductors lines so as to reduce the requisite safety clearances specified under rules 79 and 80.] 83. Clearances: General- For the purpose of computing the vertical clearance of an overhead line, the maximum sag of any conductor shall be calculated on the basis of the maximum sag in still air and the maximum temperature as specified by the State Government under rule 76(2)(d). Similarly, for the purpose of computing any horizontal clearance of an overhead line the maximum deflection of any conductor shall be calculated on the basis of the wind pressure specified by the State Government under rule 76(2)(a) or may be taken as 350, whichever is greater. 1. Ins. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987. 84. Routes: Proximity to aerodromes- Overhead lines shall not be erected in the vicinity of aerodromes until the aerodrome authorities have approved in writing the route of the proposed lines. 85. Maximum interval between supports- All conductors shall be attached to supports at intervals not exceeding the safe limits based on the ultimate tensile strength of the conductor and the factor of safety prescribed in rule 76. Provided that in the case of overhead lines carrying low or medium voltage conductors, when erected in, over, along or across any street, the interval shall not, without the consent in writing of the Inspector, exceed 65 metres. 86. Conditions to apply where telecommunication lines and power lines are carried on same supports- (1) Every overhead telecommunication line erected on supports carrying a power line shall consist of conductors each having a breaking strength of not less than 270 kg. (2) Every telephone used on a telecommunication line erected on supports carrying a power line shall be suitably guarded against lightning and shall be protected by cutouts. (3) Where a telecommunication line is erected on supports carrying a high or extra-high voltage power line arrangement shall be made to safeguard any person using the telephone against injury resulting from contact, leakage or induction between such power and telecommunication lines. 87. Lines crossing or approaching each other- (1) Where an overhead line crosses or is in proximity to any telecommunication line, either the owner of the overhead line or the telecommunication line, whoever lays his line later, shall arrange to provide for protective devices or guarding arrangements, in a manner laid down in the Code of Practice or the guidelines prepared by the Power and Telecommunication Coordination Committee and subject to the provisions of the following sub-rules:- (2) When it is intended to erect a telecommunication line or an overhead line which will cross or be in proximity to an overhead line or a telecommunication line, as the case may be, the person proposing to erect such line shall give one month’s notice of his intention so to do along with the relevant details of protection and drawings to the owner of the existing line. 1[(3) Where an overhead line crosses or is in proximity to another overhead line, guarding arrangements shall be provided so as to guard against the possibility of their coming into contact with each other. Where an overhead line crosses another overhead line, clearances shall be as under: - 2[Minimum clearances in metres between lines crossing each other. Sl. No. Nominal System Voltage 11-66 KV 110-132 KV 220 KV 400 KV 800 KV 1. 2. 3. 4. 5. 6. Low & Medium 11-66 KV 110-132 KV 220 KV 400 KV 800 KV 2.44 2.44 3.05 4.58 5.49 7.94 3.05 3.05 3.05 4.58 5.49 7.94 4.58 4.58 4.58 4.58 5.49 7.94 5.49 5.49 5.49 5.49 5.49 7.94 7.94 7.94 7.94 7.94 7.94 7.94 Provided that no guardings are required when an extra high voltage line crosses over another extra-high voltage, high voltage, medium or low voltage line or a road or a tram subject to the condition that adequate clearances are provided between the lowest conductor of the extra-high voltage line and the top most conductor of the overhead line crossing underneath the extra-high voltage line and the clearances as stipulated in rule 77 from the topmost surface of the road is maintained.] (4) A person erecting or proposing to erect a line which may cross or be in proximity with an existing line, may normally provide guarding arrangements on his own line or require the owner of the other overhead line to provide guarding arrangements as referred to in sub-rule, (3). (5) In all cases referred to in the preceding sub-rules the expenses of providing the guarding arrangements or protective devices shall be borne by the person whose line was last erected. (6) Where two lines cross, the crossing shall be made as nearly at right angles the nature of the case admits and as near the support of the line as practicable, and the support of the lower line shall not be erected below the upper line. (7) The guarding arrangements shall ordinarily be carried out by the owner of the supports on which it is made and he shall be responsible for its efficient Maintenance. (8) All work required to be done by or under this rule shall be carried out to the satisfaction of the Inspector. 1. Subs. by GSR 256, dt. 28.2.1983, w.e.f. 26.3.1983. 2. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 88. Guarding- (1) Where guarding is required under these rules the provisions of sub-rules (2) to (4) shall apply. (2) Every guard-wire shall be connected with earth at each point at which its electrical continuity is broken. (3) Every guard-wire shall have an actual breaking strength of not less than 635 kg and if made of iron or steel, shall be galvanised. (5) Lines crossing trolley-wires- In the case of a crossing over a trolley-wire the guarding shall fulfil the following conditions, namely:- (a) Where there is only one trolley-wire, two guard-wires shall be erected as in diagram A; (b) Where there are two trolley-wires and the distance between them does not exceed 40 cms, two guard-wires shall be erected as in diagram B; (c) Where there are two trolley wires and the distance between them exceeds 40 cms but does not exceed 1.2 metres, three guard-wires shall be erected as in diagram C; (d) Where there are two trolley--wires and the distance between them exceeds 1.2 metres, each trolley-wire shall be separately guarded as in diagram D; (e) The rise of the trolley boom shall be so limited that the trolley leaves the trolley-wire, it shall not foul the guard-wires; and (f) Where a telegraph-line is liable to fall or be blown down upon an arm, stay-wire or span-wire and so slide down upon a trolley-wire, guard hooks shall be provided to prevent such sliding. 20 Cms 20 Cms 0 0 min 60 Cms 0 DIAGRAM-A 20 Cms 20 Cms 20 Cms 20 Cms 0 0 0 0 0 min min min min 60 Cms 60 Cms 60Cms 60 Cms up to 40 Cms Over 40 Cms & up to 1.2 M DIAGRAM B DIAGRAM C 20 Cms 20 Cms 20 Cms 20 Cms 0 0 0 0 MIN. MIN. 60 Cms 60 Cms over 1.2 mts. DIAGRAM D 89. Service-lines from Overhead lines- No Service-line or tapping shall be taken off an overhead line except at a point of support. 1[Provided that the number of tappings per conductor shall not be more than four in case of low and medium voltage connections.] 1. Added by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 90. Earthing- (1) All metal supports and all reinforced and prestressed cement concrete supports of overhead lines and metallic fittings attached thereto, shall be permanently and efficiently earthed. For this purpose a continuous earth wire shall be provided and securely fastened to each pole and connected with earth ordinarily at three points in every km., the spacing between the points being as nearly equidistance as possible. Alternatively, each support and the metallic fitting attached thereto shall be efficiently earthed. 1[(IA) Metallic bearer wire used for supporting insulated wire of low and medium voltage overhead service lines shall be efficiently earthed or insulated.] (2) Each stay-wire shall be similarly earthed unless insulator has been placed in it at a height not less than 3.0 metres from the ground. 1. Subs. by GSR 732, dt. 18.6.1985, w.e.f. 3.8.1985. 91. Safety and protective devices- (1) Every overhead line, (not being suspended from a dead bearer wire and not being covered with insulating material and not being a trolley-wire) erected over any part of street or other public place or in any factory or mine or on any consumers’ premises shall be protected with a device approved by the Inspector for rendering the line electrically harmless in case it breaks. (2) An Inspector may by notice in writing require the owner of any such overhead line wherever it may be erected to protect it in the manner specified in sub-rule(l). 1[(3) The owner of every high and extra-high voltage overhead line shall make adequate arrangements to the satisfaction of the Inspector to prevent unauthorised persons from ascending any of the supports of such overhead lines which can be easily climbed upon without the help of a ladder or special appliances. Rails, reinforced cement concrete poles and pre-stressed cement concrete poles without steps, tubular poles, wooden supports without steps, I- sections and channels shall be deemed as supports which cannot be easily climbed upon for the purpose of this rule.] 1. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 92. Protection against lightning- (1) The owner of every overhead line 1[,sub-station or generating station] which is so exposed as to be liable to injury from lightning shall adopt efficient means for diverting to earth any electrical surges due to lightning. 2[(2) The earthing lead for any lightning arrestor shall not pass through any iron or steel pipe, but shall be taken as directly as possible from the lightning- arrestor to a separate earth electrode and/or junction of the earth mat already provided for the high and extra-high voltage sub-station subject to the avoidance of bends wherever practicable. Note- A vertical ground electrode shall be connected to this junction of the earth mat.] 1. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 2. Subs. by GSR 1050, dt. 9.11.1985. 93. Unused overhead lines- (1) Where an overhead line ceases to be used as an electric supply line, the owner shall maintain it in a safe mechanical condition in accordance with rule 76 or shall remove it. (2) Where any overhead line ceases to be used as an electric supply line, an Inspector may, by a notice in writing served on the owner, require him to maintain it in a safe mechanical condition or to remove it within fifteen days of the receipt of the notice. CHAPTER IX ELECTRIC TRACTION 94. Additional rules for electric traction- (1) The rules in this Chapter apply only where energy is used for purposes of traction. Provided that nothing in this Chapter shall apply to energy used for the public carriage of passengers, animals or goods on, or for the lighting or ventilation of the rolling stock of any railway or tramway subject to the provisions of the Indian Railways Act, 1890 (9 of 1890). (2) In this Chapter the conductor used for transmitting energy to a vehicle is referred to as the “line” and the other conductor as the “return”. (3) The owner of the line, return, rails or trolley wire, as the case may be, shall be responsible for the due observance of rules 95 to 108. 95. Voltage of supply to vehicle- No person shall supply energy at high or extra-high voltage to any trolley-wire or other conductor used in direct electrical and mechanical connection with any vehicle, except with the written approval of the Central or the State Government, as the case may be, and subject to such conditions as the State Government may think reasonable and proper in the circumstances. 96. Insulation of lines- Every line shall be insulated throughout. 97. Insulation of returns- (1) Where any rails on which cars run, or any conductors laid between or within 0.9 metre of such rails, form any part of a return, such part may be uninsulated. All other returns or parts of a return, shall be insulated, unless they are of such conductivity as to secure the conditions required by sub-rules (2) and (3) of rule 98. (2) Where any part of a return is uninsulated, it shall be connected with the negative or neutral of the system.

Previous and next

All provisions of THE INDIAN ELECTRICITY RULES, 1956

Questions people ask

Is rule 64A of THE INDIAN ELECTRICITY RULES, 1956 still in force?

No repeal of the INDIAN ELECTRICITY RULES, 1956 is recorded.