Rule 98, THE INDIAN ELECTRICITY RULES, 1956: Proximity to metallic pipes, etc
THE INDIAN ELECTRICITY RULES, 1956 - Rule 98
Text of rule 98
Proximity to metallic pipes, etc
98. Proximity to metallic pipes, etc.-
(1) Where an uninsulated return is in proximity to any metallic pipe, structure
or substance not belonging to the owner of the return, he shall, if so required by
the owner of such pipe, structure or substance, connect his return therewith at
the latter’s expense.
(2) Where the return is partly or entirely uninsulated, the owner shall, in the
construction and maintenance of his system, adopt such means for reducing the
difference produced by the current between the potential of the uninsulated
return at any one point and the potential of the uninsulated return at any other
point as to ensue that the difference of potential between the uninsulated return
and any metallic pipe, structure or substance in the vicinity shall not exceed four
volts where the return is relatively positive, or one and one-third volts where the
return is relatively negative.
(3) The owner of any such pipe, structure or substance as is referred to in
sub-rule (2) may, in respect of it require the owner of the uninsulated return at
reasonable times and intervals to ascertain by test in his presence or in that of
his representative, whether the condition specified in sub-rule (2) is fulfilled, and,
if such condition is found to be fulfilled, all reasonable expenses of, and
incidental to, the carrying out of the test shall be borne by the owner of the pipe,
structure or substance.
99. Difference of potential on return- Where the return is partly or entirely
uninsulated, the owner shall keep a continuous record of the difference of
potential, during the working of his system, between every junction of an
insulated return With an uninsulated return and the point on the route most
distant from that junction, and the difference of potential shall not, under normal
running conditions, exceed a mean value of seven volts between the highest
momentary peak and the average for the hour of maximum load.
Previous and next
← Rule 64AAdditional provisions for use of energy at high and extra-high voltage- The following additional provisions shall be observed where energy at high or extra- high voltage is supplied, converted, transferred or used, namelyRule 100 →Leakage on conduit system- Where both the line and the return are placed within a conduit, the following conditions shall be fulfilled in the construction and maintenance of the system