Rule 46, THE INDIAN ELECTRICITY RULES, 1956: Periodical inspection and testing of consumer’s installation
THE INDIAN ELECTRICITY RULES, 1956 - Rule 46
Text of rule 46
Periodical inspection and testing of consumer’s installation
46. Periodical inspection and testing of consumer’s installation. -
(1) (a) Where an installation is already connected to the supply system of
the supplier, every such installation shall be periodically inspected and tested at
intervals not exceeding five years either by the Inspector or any officer appointed
to assist the Inspector or by the supplier as may be directed by the State
Government in this behalf or in the case of installations belonging to, or under the
control of the Central Government, and in the case of installation in mines, oilfields
and railways by the Central Government.
(b) Where the supplier is directed by the Central or the State Government as
the case may be to inspect and test the installation he shall report on the condition
of the installation to the consumer concerned in a form approved by the Inspector
and shall submit a copy of such report to the Inspector or to any officer appointed
to assist the Inspector and authorised under sub-rule (2) of rule 4A.
(c) Subject to the approval of the Inspector, the forms of inspection report
contained in Annexure IX-A may, with such variations as the circumstances of
each case require, be used for the purposes of this sub-rule.
(2) (a) The fees for such inspection and test shall be determined by the
Central or the State Government, as the case may be, in the case of each class of
consumers and shall be payable by the consumer in advance.
(b) In the even it of the failure of any consumer to pay the fees on or before the
date specified in the fee-notice, supply to the installation of such consumer shall
be liable to be disconnected under the direction of the Inspector. Such
disconnection, however, shall not be made by the supplier without giving to the
consumer seven clear days’ notice in writing of his intention so to do.
(c) In the event of the failure of the owner of any installation to rectify the
defects in his installation pointed out by the Inspector or by any officer appointed
to assist him and authorised under sub-rule (2) of rule 4A in the form set out in
Annexure IX and within the time indicated therein, such installation shall be liable
to be disconnected 1[under the directions of the Inspector] after serving the owner
of such installation with a notice.
Provided that the installation shall not be disconnected in case an appeal in made
under rule 6 and the appellate authority has stayed the orders of disconnection.
Provided further that the time indicated in the notice shall not be less than 48
hours in any case.
Provided also that nothing contained in this clause shall have any effect on the
application of rule 49.
(3) Notwithstanding the provisions of this rule, the consumer shall at all times
be solely responsible for the maintenance of his installation in such condition as to
be free from danger.
1. Subs. by GSR 29, dr. 24.12.1983, w.e.f. 14.1.1984.
CHAPTER V
GENERAL CONDITIONS RELATING
TO SUPPLY AND USE OF ENERGY
47. Testing of consumer’s installation-
(1) Upon receipt of an application for a new or additional supply of energy and
before connecting the supply or reconnecting the same after a period of six
months, the supplier shall inspect and test the applicants’ installation.
The supplier shall maintain a record of test results obtained at each supply point to
a consumer, in a form to be approved by the Inspector.
(2) If as a result of such inspection and test, the supplier is satisfied that the
installation is likely to constitute danger, he shall serve on the applicant a notice in
writing requiring him to make such modifications as are necessary to render the
installation safe. The supplier may refuse to connect or reconnect the supply until
the required modifications have been completed and he has been notified by the
applicant.
1[47A. Installation and Testing of Generating Units- Where any consumer or
occupier installs a generating plant, he shall give a thirty days’ notice of his
intention to commission the plant to the supplier as well as the Inspector.
Provided that no consumer or occupier shall commission his generating plant of a
capacity exceeding 10KW without the approval in writing of the Inspector.]
1. Ins. by GSR 218, dt. 18.4.1995, w.e.f. 29.4.1995.
48. Precautions against leakage before connection-
1[(l) The supplier shall not connect with his works the installation or apparatus
on the premises of any applicant for supply unless he is reasonably satisfied that
the connection will not at the time of making the connection cause a leakage from
that installation or apparatus of a magnitude detrimental to safety. Compliance
with this rule shall be checked by measuring the insulation resistance as provided
below:
(i) High Voltage Equipments installations-
(a) High Voltage equipments shall have the IR value as stipulated in the
relevant Indian Standard.
(b) At a pressure of 1000 V applied between each live conductor and earth for
a period of one minute the insulation resistance of HV installations shall be at least
1 Mega ohm or as specified by the 1[Bureau of Indian Standards] from time to
time.
(ii) Medium and Low Voltage Installations- At a pressure of 500 V applied
between each live conductor and earth for a period of one minute, the insulation
resistance of medium and low voltage installations shall be at least 1 Mega ohm or
as specified by the 2[Bureau of Indian Standards] from time to time.]
(2) If the supplier declines to make a connection under the provisions of sub-
rule (1), he shall serve upon the applicant a notice in writing stating his reason for
so declining.
1. Subs. by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
2. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
49. Leakage on consumer’s premises-
(1) If the Inspector or any officer appointed to assist the Inspector and
authorised under sub-rule (2) of rule 4A or the supplier had reason to believe that
there is in the system of a consumer leakage which is likely to affect injuriously the
use of energy by the supplier or by other persons, or which is likely to cause
danger, he may give the consumer reasonable notice in writing that he desires to
inspect and test the consumer’s installation.
(2) If on such notice being given-
(a) The consumer does not give all reasonable facilities for inspection and
testing of his installation, or
1[(b) When an insulation resistance at the consumer’s installation is so low as to
prevent safe use of energy.]
The supplier may, and if directed so to do by the Inspector shall discontinue the
supply of energy to the installation but only after giving to the consumer 48 hours
notice in writing of disconnection of supply and shall not recommence the supply
until he or the Inspector is satisfied that the cause of the leakage has been
removed.]
1. Subs. by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
1[50. Supply and use of energy-
(1) The energy shall not be supplied, transformed, converted or used or
continued to be supplied, transformed, converted or used unless provisions as set
out below are observed:-
(a) The following controls of requisite capacity to carry and break the current
2[are placed] after the point of commencement of supply as defined in rule 58 so
as to be readily accessible and capable of being easily operated to completely
isolate the supply to the installation such equipment being in addition to any
equipment installed for controlling individual circuits or apparatus: -
(i) A linked switch with fuse(s) or a circuit breaker by low and medium voltage
consumers.
(ii) A linked switch with fuse(s) or a circuit breaker by HV consumers having
aggregate installed transformer/apparatus capacity up to 1000 KVA to be supplied
at voltage upto 11 KV and 2500 KVA at higher -voltages (above 11 KV and not
exceeding 33 KV).
(iii) A circuit breaker by HV consumers having an aggregate installed
transformer/apparatus capacity above 1000 KVA and supplied at 11 KV and above
2500 KVA supplied at higher voltages (above 11 KV and not exceeding 33 KV).
(iv) A circuit breaker by EHV consumer;
Provided that where the point of commencement of supply and the consumer
apparatus are near each other one linked switch with fuse(s) or circuit breaker
near the point of commencement of supply as required by this clause shall be
considered sufficient for the purpose of this rule;
(b) In case of every transformer the following shall be provided: -
(i) On primary side for transformers a linked switch with fuse(s) or circuit
breaker of adequate capacity:
Provided that the linked switch on the primary side of the transformer may be of
such capacity as to carry the full load current and to break only the magnetising
current of the transformer:
Provided further that for transformers of capacity 5000 KVA and above a circuit
breaker shall be provided:
Provided further that the provision of linked switch on the primary side of the
transformer shall not apply to the unit auxiliary transformer of the generator.
(ii) On the secondary side of transformers of capacity 100 KVA and above
transforming HV to MV or LV, a linked switch with fuse(s) or circuit breaker of
adequate capacity capable of carrying and breaking full load current and for
transformers transforming HV to EHV as the case may be, a circuit breaker:
Provided that where the transformer capacity exceeds 630 KVA a circuit breaker
of adequate capacity shall be installed on the secondary side;
(c) Except in the case of composite control gear designed as a unit distinct
circuit is protected against excess energy by means of suitable cut-out or a circuit
breaker of adequate breaking capacity suitably located and, so constructed as to
prevent danger from overheating, arcing or scattering of hot metal when it comes
into operation and to permit for ready renewal of the fusible metal of the cut-out
without danger;
(d) The supply of energy of each motor or a group of motors or other apparatus
meant for operating one particular machine is controlled by a suitable linked switch
or a circuit breaker or an emergency tripping device with manual reset of requisite
capacity placed in such a position as to be adjacent to the motor or a group of
motors or other apparatus readily accessible to and easily operated by the person
incharge and so connected in the circuit that by its means all supply of energy can
be cut off from the motor or group of motors or apparatus from any regulating
switch, resistance of other device associated therewith;
(e) All insulating materials are chosen with special regard to the circumstances
of its proposed use and their mechanical strength is sufficient for its purpose and
so far as is practicable of such a character or so protected as to maintain
adequately its insulating property under all working conditions in respect of
Temperature and moisture; and
(f) Adequate precautions shall be taken to ensure that no live parts are so
exposed as to cause danger.
(2) Where energy is being supplied, transformed, converted or used the
3[consumer, supplier or the owner] of the concerned installation shall be
responsible for the continuous observance of the provisions of sub-rule (1) in
respect of his installations.
(3) Every consumer shall use all reasonable mean to ensure that where energy
is supplied by a supplier no person other than the supplier shall interfere with the
service lines and apparatus placed by the supplier on the premises of the
consumer.]
1. Subs. by GSR 11”, dt. 21.1.1986, w.e.f. 8.2.1986.
2. Subs. by GSR 218, dt. 18.4.1995, w.e.f. 29.4.1995.
3. Subs. by GSR 218, dt. 18.4.1995, w.e.f. 29.4.1995.
1[50A. Additional provisions for supply and use of energy in multi-storeyed
building (more than 15 metres in height)-
(1) Before making an application for commencement of supply or
recommencement of supply after an installation has been disconnected for a
period of six months or more the owner/occupier of a multi-storeyed building shall
give not less than 30 days’ notice in writing to the Inspector together with
particulars. The supply of energy shall not be commenced or recommenced within
this period, without the approval or otherwise in writing of the Inspector.
(2) The supplier/owner of the installation shall provide at the point of
commencement of supply a suitable isolating device with cut out or breaker to
operate on all phases except neutral in the 3 phase 4 wire circuit and fixed in a
conspicuous position at not more than 2.75 metres above the ground so as to
completely isolate the supply to the building in case of emergency.
(3) The owner/occupier of a multi-storeyed building shall ensure that electrical
installations/works inside the building are carried out and maintained in such a
manner as to prevent danger due to shock and fire hazards’ and the installation is
carried out in accordance with the relevant codes of practices.
(4) No other service pipes shall be taken along the ducts provided for laying
power cables. All ducts provided for power cables and other services shall be
provided with fire-barrier at each floor crossing.]
1. Ins. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987.
51. Provisions applicable to medium, high or extra-high voltage installations-
The following provisions shall be observed where energy at medium, high or extra-
high voltage is supplied, converted, transformed or used
(1) (a) All conductors (other than those of overhead lines) shall be
completely enclosed in mechanically strong metal casting or metallic covering
which is electrically and mechanically continuous and adequately protected
against mechanical damage unless the said conductors are accessible only to an
authorised person or are installed and protected to the satisfaction of the Inspector
so as to prevent danger;
1[Provided that non-metallic conduits conforming to the relevant Indian Standard
Specifications may be used for medium voltage installations, subject to such
conditions as the Inspector or Officer appointed to assist an Inspector may think fit
to impose.]
2[(b) All metal works, enclosing, supporting or associated with the installation,
other than that designed to serve as a conductor shall be connected with an
earthing system as per standards laid down in the Indian Standards in this regard
and in also accordance with rule 61(4).]
(c) Every switchboard shall comply with the following provisions, namely: -
(i) A clear space of not less than 1 metre in width shall be provided in front of
the switchboard;
(ii) If there are any attachments or bare connections at the back of the
switchboard, the space (if any) behind the switchboard shall be either less than 20
centimetres or more than 75 centimetres in width, measured from the farthest
outstanding part of any attachment or conductor;
(iii) If the space behind the switchboard exceeds 75 centimetres in width, there
shall be a passage-way from either end of the switchboard clear to a height of 1.8
metres.
3[(d) In case of installations provided in premises where inflammable materials
including gases and/or chemicals are produced, handled or stored, the electrical
installations, equipment and apparatus shall comply with the requirements of flame
proof, dust tight, totally enclosed or any other suitable type of electrical fittings
depending upon the hazardous zones as per relevant Indian Standard
Specification.]
4[(2) Where an application has been made to a supplier for supply of energy to
any installation, he shall not commence the supply or where the supply has been
discontinued for a period of one year and above, recommence the supply unless
he is satisfied that the consumer has complied with, in all respects the conditions
of supply set out in sub-rule (1), of this rule, rules 50, 63 and 64.]
(3) Where a supplier proposes to supply or use energy at a medium voltage or
to recommence supply after it has been discontinued for a period of six months,
he, shall, before connecting or reconnecting the supply, give notice in writing of
such intention to the Inspector 5[or any officer of specified rank and class
appointed to assist the Inspector].
6[(4) If at any time after connecting the supply, the supplier is satisfied that any
provision of the sub-rule (1) of this rule or of rules 50 and 64, is not being observed
he shall give notice of the same in writing to the consumer and the inspector,
specifying how the provisions has not been observed and to rectify such defects in
a reasonable time and if the consumer fails to rectify such defects pointed out, he
may discontinue the supply after giving the consumer a reasonable opportunity of
being heard and recording reasons in writing, unless the inspector directs
otherwise. The supply shall be discontinued only on written orders of an officer
duly notified by the supplier in this behalf. The supply shall be restored with all
possible speed after such defects are rectified by the consumer to the satisfaction
of the supplier.]
1. Subs. by GSR 336, dt. 28.3.1988, w.e.f. 23.4.1988.
2. Subs. by GSR 358, dt. 30.4.1987, w.e.f. 9.5.1987.
3. Ins. by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
4. Subs. by GSR 256, dt. 28.2-1983, w.e.f. 26.3.1983
5. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
6. Subs. by GSR 732, dt. 18.6.1985, w.e.f. 3.8.1985.
52. Appeal to Inspector in regard to defects-
(1) If any applicant for a supply or a consumer is dissatisfied with the action of
the supplier in declining to commence, to continue or to recommence the supply of
energy to his premises on the grounds that the installation is defective or is likely
to constitute danger, he may appeal to the Inspector to test the installation and the
supplies shall not, if the Inspector or under his orders, any other officer appointed
to assist the Inspector, is satisfied that the installation is free from the defect or
danger complained of, be entitled to refuse supply to the consumer on the grounds
aforesaid, and shall, within twenty-four hours after the receipt of such intimation
from the Inspector, commence, continue or recommence the supply of energy.
(2) Any test for which application has been made under the provision of sub-
rule (1) shall be carried out within seven days after the receipt of such application.
(3) This rule shall be endorsed on every notice given under the provisions of
rules 47, 48, and 49.
53. Cost of inspection and test of consumer’s installation-
(1) The cost of the first inspection and test of consumer’s installation carried
out in pursuance of the provisions of rule 47 shall be borne by the supplier and the
cost of every subsequent inspection and test shall be borne by the consumer,
unless in the appeal under rule 52, the Inspector directs otherwise.
(2) The cost of any inspection and test made by the Inspector or any officer
appointed to assist the Inspector, at the request of the consumer or other
interested party, shall be borne by the consumer or other interested party, unless
the Inspector directs otherwise.
(3) The cost of each and every such inspection and test by whomsoever borne
shall be calculated in accordance with the scale specified by the Central or the
State Government as the case may be in this behalf.