Rule 37, THE INDIAN ELECTRICITY RULES, 1956: Supply to vehicles, cranes, etc
THE INDIAN ELECTRICITY RULES, 1956 - Rule 37
Text of rule 37
Supply to vehicles, cranes, etc
37. Supply to vehicles, cranes, etc.- Every person owning a vehicle, travelling
crane or the like to which energy is supplied from an external source shall ensure
that it is efficiently controlled by a suitable switch enabling all voltage to be cut off
in one operation and, where such vehicle, travelling crane or the like runs on metal
rails, the owner shall ensure that the rails are electrically continuous and earthed.
38. Cables for portable or transportable apparatus-
(1) Flexible cables shall not be used for portable or transportable motors,
generators, transformer rectifiers, electric drills, electric sprayers, welding sets or
any other portable or transportable apparatus unless they are heavily insulated
and adequately protected from mechanical injury.
(2) Where the protection is by means of metallic covering, the covering shall be
in metallic connection with the frame of any such apparatus and earth.
(3) The cables shall be three core type and four-core type for portable and
transportable apparatus working on single phase and three phases supply
respectively and the wire meant to be used for ground connection shall be easily
identifiable.
39. Cables protected by bituminous materials-
(a) Where the supplier or the owner has brought into use an electric supply line
(other than an overhead line) which is not completely enclosed in a continuous
metallic covering connected with earth and is insulated or protected in situ by
composition or material of a bituminous character-
(i) Any pipe, conduit or the like into which such electric supply line may have
been drawn or placed shall, unless other arrangements are approved by the
Inspector in any particular case, be effectively sealed at its point of entry into any
street box so as to prevent any flow of gas to or from the street box; and
(ii) Such electric supply line shall be periodically inspected and tested where
accessible, and the result of each such inspection and test shall be duly recorded
by the supplier or the owner.
(2) It shall not be permissible for the supplier or the owner after the coming into
force of these rules, to bring into use any further electric supply line as aforesaid
which is insulated or protected in situ by any composition or material known to be
liable to produce noxious or explosive gases on excessive heating.
40. Street boxes-
(1) Street boxes shall not contain gas pipes, and precautions shall be taken to
prevent, as far as reasonably possible, any influx of water or gas.
(2) Where electric supply lines forming part of different systems pass through
the same street box, they shall be readily distinguishable from one another and all
electric supply lines at high or extra-high voltage in street boxes shall be
adequately supported and protected to as to prevent risk of damage to or danger
from adjacent electric supply lines.
(3) All street boxes shall be regularly inspected for the purpose of detecting the
presence of gas and if any influx or accumulation is discovered, the owner shall
give immediate notice to any authority or company who have gas mains in the
neighbourhood of the street box and in cases where a street box is large enough
to admit the entrance of a person after the electric supply lines or apparatus
therein have been placed in position, ample provision shall be made-
(a) To ensure that any gas which may by accident have obtained access to the
box shall escape before a person is allowed to enter; and
(b) For the prevention of danger from sparking.
(4) The owners of all street boxes or pillars containing circuits or apparatus
shall ensure that their covers and doors are so provided that they can be opened
only by means of a key or a special appliance.
41. Distinction of different circuits- The owner of every generating station, sub-
station, junction-box or pillar in which there are any circuits or apparatus, whether
intended for operation at different voltages or at the same voltage, shall ensure by
means of indication of a permanent nature that the respective circuits are readily
distinguishable from one another.
1[41A. Distinction of the installations having more than one feed- The owner of the
every installation including sub-station, double pole structure, four pole structure or
any other structure having more than one feed, shall ensure by means of
indication of a permanent nature, that the installation is readily distinguishable
from other installations.]
1. Ins. by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
42. Accidental charge- The owners of all circuits and apparatus shall so
arrange them that there shall be no danger of any part thereof becoming
accidentally charged to any voltage beyond the limits of voltage for which they are
intended.
Where A.C. and D.C. circuits are installed on the same support they shall be so
arranged and protected that they shall not come into contact with each other when
live.
43. Provisions applicable to protective equipment-
(1) Fire buckets filled with clean dry sand and ready for immediate use for
extinguishing fires, in addition to fire extinguishers suitable for dealing with electric
fires, shall be conspicuously marked and kept in all generating stations, enclosed
sub-stations and switch stations in convenient situation.
The fire extinguishes shall be tested for satisfactory operation at least once a year
and record of such tests shall be maintained.
(2) First-aid boxes or cupboards, conspicuously marked and equipped with
such contents as the State Government may specify, shall be provided and
maintained in every generating station, enclosed sub-station and enclosed switch
station so as to be readily accessible during all working hours. All such boxes and
cupboards shall, except in the case of unattended sub-stations and switch
stations, be kept in charge of responsible persons who are trained in first-aid
treatment and one of such person shall be available during working hours.
1[(3) Two or more gas masks shall be provided conspicuously and installed and
maintained at accessible places in every generating station with capacity of 5 MW
and above and enclosed sub-station with transformation capacity of 5 MVA and
above for use in the event of fire or smoke.
Provide that where more than one generator with capacity of 5 MW and above is
installed in a power station, each generator would be provided with at least two
separate gas masks in accessible and conspicuous position.
Provided further that adequate number of gas masks would be provided by the
owner of every generating station and enclosed sub-station with capacity less than
5MW and 5MVA respectively, if so desired by the Inspector.]
1. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
44. Instructions for restoration of persons suffering from electric shock-
(1) Instructions, in English or Hindi and the local language of the district and
where Hindi is the local language, in English and Hindi for the restoration of
persons suffering from electric shock, shall be affixed by the owner in a
conspicuous place in every generating station, enclosed sub-station, enclosed
switch-station and in every factory as defined in clause (m) of section 2 of the
Factories Act, 1948 (63 of 1948) in which electricity is used and in such other
premises where electricity is used as the Inspector or any officer appointed to
assist the Inspector may, by notice in writing served on the owner, direct.
(2) Copies of the instructions shall be supplied on demand by an officer or
officers appointed by the Central or the State Government in this behalf at a price
to be fixed by the Central or the State Government.
(3) The owner of every generating station, enclosed sub-station, enclosed
switch-station and every factory or other premises to which this rule applies, shall
ensure that all authorised persons employed by him are acquainted with and are
competent to apply the instructions referred to in sub-rule (1).
(4) In every manned high voltage or extra-high voltage generating station, sub-
station or switch station, an artificial respirator shall be provided and kept in good
working condition.
1[44A. Intimation of Accident- If any accident occurs in connection with the
generation, transmission, supply or use of energy in or in connection with, any part
of the electric supply lines or other works of any person and the accident results in
or is likely to have resulted in loss of human or animal life or in any injury to a
human being or an animal, such person or any authorised person of the State
Electricity Board/Supplier, not below the rank of a Junior Engineer or equivalent
shall send to the Inspector a telegraphic report within 24 hours of the knowledge of
the occurrence of the fatal accident and a written report in the form set out in
Annexure XIII within 48 hours of the knowledge of occurrence of fatal and all other
accidents. Where practicable a telephonic message should also be given to the
Inspector immediately the accident comes to the knowledge of the authorised
officer of the State Electricity Board/ Supplier or other person concerned.]
1. Subs. by GSR 1049, dt. 17.10.1985, w.e.f. 9.11.1985.
45. Precautions to be adopted by consumers 1[owners occupiers], electrical
contractors, electrical workmen and suppliers-
(1) No electrical installation work, including additions, alterations, repairs and
adjustments to existing installations, except such replacement of lamps, fans,
fuses, switches, low voltage domestic appliances and fittings as in no way alters
its capacity or character, shall be carried out upon the premises of or on behalf of
any 2[consumer, supplier, owner or occupier] for the purpose of supply to such
2[consumer, supplier, owner or occupier] except by an electrical contractor
licensed in this behalf by the State Government and under the direct supervision of
a person holding a certificate of competency and by a person holding a permit
issued or recognised by the State Government.
Provided that in the case of works executed for or on behalf of the Central
Government and in the case of installations in mines, oil fields and railways, the
Central Government and in other cases the State Government may, by notification
in the Official Gazette, exempt, on such conditions as it may impose, any such
work described therein either generally or in the case of any specified class of
2[consumers, suppliers, owners or occupiers] from so much of this sub-rule as
requires such work to be carried out by an electrical contractor licensed by the
State Government in this behalf.
3[(2) No electrical installation work which has been carried out in contravention of
sub-rule (1) shall either be energised or connected to the works of any supplier.]
4[(3) * *]
1. Ins. by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
2. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
3. Subs. by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
4. Sub-rule (3) omitted by GSR 844, dt. 31.7.1985, w.e.f. 7.9.1985.
Previous and next
Questions people ask
Is rule 37 of THE INDIAN ELECTRICITY RULES, 1956 still in force?
No repeal of the INDIAN ELECTRICITY RULES, 1956 is recorded.