Rule 30, Rajasthan Factories Rules,1951: Lighting of interior parts

Rajasthan Factories Rules,1951 - Rule 30

Text of rule 30

Lighting of interior parts

30. Lighting of interior parts. — (1) The general illumination over those interior parts of a factory where persons are regularly employed shall be not less than @[30 lux] measured in the horizontal plane at a level of @[90 cm] above the floor: Provided that in any such parts in which the mounting height of the light source for general illumination necessarily exceeds @[7.5 metres] measured from the floor or where the structure of the room or the position or construction of the fixed machinery or plant prevents the uniform attainment of this standard, the general illumination at the said level shall be not less than @[10 lux] and where work is actually being done the illumination shall be not less than @[30 lux]. (2) The illumination over all other interior parts of the factory over which persons employed pass shall, when and where a person is passing, be not less than @[5 lux] at floor level. (3) Artificial lighting in accordance, with the following standards shall be provided and used in the interior of cotton ginning factories at times when artificial lighting is necessary and is ordinarily used:- (i) by means of electricity, to the satisfaction of the Inspector, one lamp per six gins, each lamp not less than 25 candle power, or (ii) by candles places in glass lanterns of a pattern approved by the Inspector not less than one such lantern for every two gins. (4) The standard specified in this rule shall be without prejudice to the provision of any additional illumination required to render the lighting sufficient and suitable for the nature of the work.

Previous and next

All provisions of Rajasthan Factories Rules,1951

Questions people ask

Is rule 30 of Rajasthan Factories Rules,1951 still in force?

No repeal of Rajasthan Factories Rules,1951 is recorded.