LawGrids logoLAWGRIDS.ORG

Rule 31, Rajasthan Factories Rules,1951: Prevention of glare

Rajasthan Factories Rules,1951 - Rule 31

Text of rule 31

Prevention of glare

31. Prevention of glare. — (1) Where any source of artificial light in the factory is less than @[5 metres] above floor level, no part of the light source or of the lighting fitting having a brightness greater than @[5 laberts] shall be visible to persons whilst normally employed within @ [30 metres] of the source, except where the angle of elevation from the eye to the source or part of the fitting as the case may be exceeds 20 degree. (2) Any local light, that is to say, an artificial light designed to illuminate particularly the area or part of the area of work of a single operative or small group of operatives working near each other, shall be provided with a suitable shade of opaque material to prevent glare or with other effective means by which the light source is completely screened from the eyes of every person employed at a normal working place, or shall be so placed that no such person is exposed to glare therefrom.

Previous and next

All provisions of Rajasthan Factories Rules,1951

Questions people ask

Is rule 31 of Rajasthan Factories Rules,1951 still in force?

No repeal of Rajasthan Factories Rules,1951 is recorded.