Rule 28, Rajasthan Factories Rules,1951: How to introduce steam for humidification
Rajasthan Factories Rules,1951 - Rule 28
Text of rule 28
How to introduce steam for humidification
28. How to introduce steam for humidification. — In any room in which steam pipes are
used for the introduction of steam for the purpose of artificial humidification of the air the
following provisions shall apply:—
(a) The diameter of such pipes shall not exceed @[50 mms.] and in the case of pipes
installed after 1st day of January, 1950 the diameter shall not exceed @[25 mms.]:
(b) Such pipes shall be as short as is reasonably practicable:
(c) All hangers supporting such pipes shall be separated from the bare pipes by an
efficient insulator not less than @[13 ms.] in thickness:
(d) No uncovered jet from such pipe shall project more than @[110 mms.] beyond the
outer surface of any cover;
(e) The steam pressure shall be as low as practicable and shall not exceed [5kg/square
cm]
(f) The pipe employed for the introduction of steam into the air in a department shall be
effectively covered with such non- conducting material as may be approved by the
Inspector in order to minimise the amount of heat radiated by them into the
department.
--------------------------------------------------------------------------------------------------------------------------
@. Substituted vide Notification No. F1(112)L&E/76 dated 24.3.1979; Rajasthan Gazette
Part IV-Ga(1). dated 26.4.1979
Rules 29 to 33 prescribed under sub-section (4) of section 17
#29.[x x x]
Previous and next
Questions people ask
Is rule 28 of Rajasthan Factories Rules,1951 still in force?
No repeal of Rajasthan Factories Rules,1951 is recorded.