Specifications of Hygrometer-:
23. Specifications of Hygrometer-:.-
(1) Each hygrometer shall comprise two mercurial thermometers of wet bulb of
similar construction and equal in dimensions, scale and divisions of scale. They
shall be mounted on a farm with a suitable reservoir containing water.
(2) The wet bulb shall be closely covered with a single layer of muslin, kept wet by
means of a wick attached to it and dropping into the water in the reservoir. The
muslin covering and the wick shall be suitable for the purpose, clean and free
from size or grease.
(3) No part of the wet bulb shall be within 3 inches from the dry bulb or less than 1
inch from the surface of the water in the reservoir and the water reservoir shall
be below it, on the side of it away from the dry bulb.
(4) The bulb shall be spherical and of suitable dimensions and shall be freely exposed
on all sides to the air of the room.
(5) The bores of the stems shall be such that the position of the top of the mercury
column shall be readily distinguishable at a distance of 2 feet.
(6) Each thermometer shall be graduated so that accurate readings may be taken
between 50 and 120 degrees.
(7) Every degree from 50 degrees upto 120 degrees shall be clearly marked by
horizontal lines on the stems. Each fifth and tenth degree shall be marked by
longer marks than the intermediate degrees and the temperature marked
opposite each tenth degree, i.e., 50, 60, 70, 80, 90, 100, 110 and 120.
(8) The markings as above shall be accurate that is to say, at no temperature
between 50 and 120 degrees shall the indicated readings, be in error by more
than two tenths of a degree.
(9) A distinctive number shall be indelibly marked upon the thermometer.
(10) The accuracy of each thermometer shall be certified by the National Physical
Laboratory, London, or some competent authority appointed by the Chief
Inspector and such certificate shall be attached to the Humidity Register .
Previous and next
← Rule 18When artificial humidification not allowed- There shall be no artificial humidification in any room of a cotton spinning or weaving factoryRule 24 →Thermometers to be maintained in efficient order- Each thermometer shall be maintained at all times during the period of employment in efficient working order, so as to give accurate indications and in particular