Rule 18, Delhi Factories Rules, 1950: When artificial humidification not allowed- There shall be no artificial humidification in any room of a cotton spinning or weaving factory
Delhi Factories Rules, 1950 - Rule 18
Text of rule 18
When artificial humidification not allowed- There shall be no artificial humidification in any room of a cotton spinning or weaving factory
18. When artificial humidification not allowed-
There shall be no artificial humidification in any room of a cotton spinning or weaving
factory :-
(a) by the use of steam during any period when the dry bulb temperature of that room
exceeds 85 degrees;
(b) at any time when the wet bulb reading of the hygrometer is higher than that
specified in the following Schedule in relation to the dry bulb reading of the
hygrometer at that time; or as regards a dry bulb readings intermediate between
any two dry bulb readings indicated consecutively in the Schedule when the dry
bulb reading does not exceed the wet bulb reading to the extent indicated in
relation to the lower of these two dry bulb readings-
SCHEDULE
Dry bulb Wet bulb Dry bulb Wet bulb Dry bulb Wet bulb
60.0 58.0 77.0 75.0 94.0 86.5
61.0 59.0 78.0 76.0 95.0 87.0
62.0 60.0 79.0 77.0 96.0 87.5
63.0 61.0 80.0 78.0 97.0 88.0
64.0 62.0 81.0 79.0 98.0 88.5
65.0 63.0 82.0 80.0 99.0 89.0
66.0 64.0 83.0 80.5 100.0 98.5
67.0 65.0 84.0 81.0 101.0 90.0
68.0 66.0 85.0 82.0 102.0 90.0
69.0 67.0 86.0 82.5 103.0 90.5
70.0 68.0 87.0 83.0 104.0 90.5
71.0 69.0 88.0 83.5 105.0 91.0
72.0 70.0 89.0 84.0 106.0 91.0
73.0 71.0 90.0 84.5 107.0 91.5
74.0 72.0 91.0 85.0 108.0 91.5
75.0 73.0 92.0 85.5 109.0 92.0
76.0 74.0 93.0 86.0 110.0 92.0
Provided, however, that Clause (b) shall not apply when the difference between the wet
bulb temperature as indicated by the hygrometer in the department concerned and the
wet bulb temperature taken with a hygrometer outside in the shade is less than 3.5
degrees.
19. Provision of Hygrometer-
In all departments of cotton spinning and weaving mills wherein artificial humidification
is adopted hygrometers shall be provided and maintained in such position as are
approved by the Inspector.
The number of hygrometers shall be regulated according to the following scale:-
(a) Weaving departments- One hygrometer for departments with 500 looms, and one
additional Hygrometer for every 500 or part of 50 looms in excess of 500.
(b) Other departments- One Hygrometer for each room of less than 300.00 cubic feet
capacity and one extra hygrometer for each 200.00 cubic feet or part thereof, in
excess of this.
(c) One additional hygrometer shall be provided and maintained outside each cotton
spinning and weaving factory wherein artificial humidification is adopted, and in a
position approved by the Inspector, for taking hygrometer shade readings.
http://labour.delhigovt.nic.in/act/details_rules/the%20delhi%20factory%20rules,%201950//factoryrules/
20. Exemption from maintenance of hygrometers-
When the Inspector is satisfied that the limits of humidity allowed, by the Schedule of
Rule 18 are never exceeded, he may, for any department other than the weaving
department grant exemption from the maintenance of the hygrometer. The Inspector
shall record such exemption in writing.
21. Copy of Schedule to Rule 18 to be affixed near every hygrometer-
A logible copy of the Schedule to Rule 18 shall be affixed near each hygrometer.
22. Temperature to be recorded at each hygrometer-
At each hygrometer maintained in accordance with Rule 19, correct wet and dry bulb
temperature shall be recorded thrice daily during each working day by competent person
nominated by the Manager and approved by the Inspector. The temperature shall be
taken between 7 a.m. and 9 a.m. between 11 a.m. and 2 p.m. (but not in the rest
interval) and between 4 p.m. and 5.30 p.m. In exceptional circumstances such additional
readings and between such hours, as the Inspector may specify shall be taken. The
temperatures shall be entered in a Humidity Register in the prescribed Form No.6,
maintained in the factory. At the end of each month, the persons who have taken the
readings shall sign the Register and certify the correctness of the entries. The Register
shall always be available for inspection by the Inspector.