Regulation 123, Indian Boiler Regulations, 1950: Furnaces of Vertical Boilers
Indian Boiler Regulations, 1950 - Regulation 123
Text of regulation 123
Furnaces of Vertical Boilers
123. Furnaces of Vertical Boilers.—(a) The vertical portion shall be in one
plate and shall be bent to oircular form in a similar manner to the shell plates.
(b) Circular furnaces shall preferably be tappered, a taper of 1J in. in diameter
per 1 foot of height being recommended. The minimum water spaco at the bottom
between the furnaces and the shell shall not be less than 2 in. for boilers up to 2 ft.
6 in. in diameter and shall be not less than 2J in. for boilers over 2 ft. 6in. in diameter.
(o) Where hemispherical furnace crowns are pressed from one plate they shall
be pressed to form by machine in progressive stages without thinning and on oom-
pletion shall be annealed.
(d) Ogee flanging where integral with the firebox or in a separate ring shall
preferably be formed at one heat by suitable machinery and shall be allowed to
cool gradually to avoid internal stresses,
(e) Furnaces of vertical type boilers may be attached to the shell at the fire"
hole by a solid rectangular section steel ring riveted together or by a circular ring
of substantial section fusion welded to shell and firebox. Where the latter cons-
truction is employed the opening in the shell for fireholc shall be substantially com-
pensated by a i ing welded on the outside of the shell plate.
(f) At the firehole the firebox plate and the shell plate may be flanged and fusion
welded together.