Regulation 42, Indian Boiler Regulations, 1950: Hydraulic Test

Indian Boiler Regulations, 1950 - Regulation 42

Text of regulation 42

Hydraulic Test

42. Hydraulic Test.—Each tube shall be tested at the makers works by hydrau- lic pressure in accordance with the following table governing the rolation between the test pressuro and tho design pressure to which tho tube will bo subjected in aei-vioe. Design pressure lb/nq. in. Up to and including 500 . Abovo COO upto tind including 1000 . Abovo 1000 Hydraulic toat prosHUro lb/sq. ni. minimum inoo Twice tho design pressure: 1000 ubove the design pressure. -#18 THE GAZETTE OF INDIA EXTRAORDINARY [PART U In all i-nses the tensile strews (S) on the material when under these tests shall DP not exceed 10 tons, per sq. in. as doterminod by the formula S «= -5— Where D =aoutsido diameter of tho tube in inches P a tea t pressure in tons per sq. in. t =inominal thickness of tube wall in inches. HOT FINISHED SEAMLESS STEEL BOILER AND SUPERHEATER. TUBES FOR DESIGNED TEMPERATURES NOT EXCEEDING 850nF (454°C)