LawGrids logoLAWGRIDS.ORG

Regulation 225, Indian Boiler Regulations, 1950.: Foundations oi Vertical Boiler Furnaces

Indian Boiler Regulations, 1950. - Regulation 225

Text of regulation 225

Foundations oi Vertical Boiler Furnaces

225. Foundations oi Vertical Boiler Furnaces.—Whore circular furnaces or fireboxes of vertical boilers are not connected to tho shell crown by uptake tube, smoke tubes or bolt stays and the whole load on the firebox vertically is borne by the bottom part of the firebox where it is connected to the shell the working preumire for the part, if firebox is joggled out to meet the shell or if an ogee ring is fitted, shall not exceed that found by the following formula :— 140(t—I)1 W. P. = — — Eqn. (62) D(D—Dj) t is tho thioknoss of the joggled firebox plate or ogee ring in 32nds of an inch, D is tho inside diameter of the boiler shell in inchos. Di is the outside diameter of tho joggled firebox at the commencement of our- vaturo abovo joggled part or tho outside diameter of the firebox where it joins the ogeo ring.

Previous and next

All provisions of Indian Boiler Regulations, 1950.

Questions people ask

Is regulation 225 of Indian Boiler Regulations, 1950. still in force?

No repeal of Indian Boiler Regulations, 1950. is recorded.