Regulation 225, Indian Boiler Regulations, 1950.: Foundations oi Vertical Boiler Furnaces
Indian Boiler Regulations, 1950. - Regulation 225
Text of regulation 225
Foundations oi Vertical Boiler Furnaces
225. Foundations oi Vertical Boiler Furnaces.—Whore circular furnaces or
fireboxes of vertical boilers are not connected to tho shell crown by uptake tube,
smoke tubes or bolt stays and the whole load on the firebox vertically is borne
by the bottom part of the firebox where it is connected to the shell the working
preumire for the part, if firebox is joggled out to meet the shell or if an ogee ring is
fitted, shall not exceed that found by the following formula :—
140(t—I)1
W. P. = — — Eqn. (62)
D(D—Dj)
t is tho thioknoss of the joggled firebox plate or ogee ring in 32nds of an inch,
D is tho inside diameter of the boiler shell in inchos.
Di is the outside diameter of tho joggled firebox at the commencement of our-
vaturo abovo joggled part or tho outside diameter of the firebox where it joins the
ogeo ring.