LawGrids logoLAWGRIDS.ORG

Regulation 221, Indian Boiler Regulations, 1950.: Corrugated Furnaces oi. Horizontal Boilers

Indian Boiler Regulations, 1950. - Regulation 221

Text of regulation 221

Corrugated Furnaces oi. Horizontal Boilers

221. Corrugated Furnaces oi. Horizontal Boilers.—Tho maximum working pressure to be allowed on corrugated furnaces shall be determined by the following formula— 0 W.P. = — (t—1) Eqn. (59) D D is the least external diameter in inches measured at the bottom of the corrugations on the water side, t is the thiokness of the furnaoe plate in 32nds of an inch measured at the bottom of the corrugation or chamber, C = 480 for the Fox, Morrison, Deighton, Purves, and other similar furnaces and 510 for the Leeds Forge Bulb Suspension Furnace.

Previous and next

All provisions of Indian Boiler Regulations, 1950.

Questions people ask

Is regulation 221 of Indian Boiler Regulations, 1950. still in force?

No repeal of Indian Boiler Regulations, 1950. is recorded.