Regulation 222, Indian Boiler Regulations, 1950.: Plain Furnaces ot Vertical Boilers
Indian Boiler Regulations, 1950. - Regulation 222
Text of regulation 222
Plain Furnaces ot Vertical Boilers
222. Plain Furnaces ot Vertical Boilers.—The same formula as for tho plain
furnacea of horizontal boilers shall be used, but where the furnaces are tapered, the
diameter to be taken for calculation purposes shall be the mean of that at the top
and of that at the bottom where it meets the substantial support from flange or ring.
The length for the same purpose shall be the distance from the oentre of the row of
rivets connecting the crown and the body of the furnace to the substantial support
at the bottom of the furnaoe, or to a row of screwed stays connecting the furnace
to the shell, provided that the pitoh of stays at the furnace does not exoeed 14 times
the thickness of the furnaoe plate when the stays are riveted at their ends, or 16 times
when the stays are fitted with nuts. Suoh screwed stays shall be in diameter over
the throads not less than twice the thickness of the furnaoe plate and in no case
less than £"—diameter (see Reg. 135(d).)