Plain Furnaces of Horizontal Boilers

220. Plain Furnaces of Horizontal Boilers.—For plain fumacos or furnaces •lengthened by Adamson or other joints or stiffeners of sufficient strength and for the semi-oylindrioal tops of fire-boxes and bottoms of combustion chambers where the sides are securely stayed, the working pressure shall not exceed the smaller of the values obtained from the following formulas— C (t—1)' W.P. -= — x — Eqn. (57) D (L +24) Pi W.P. = — x [10 (t—1)—L] Eqn. (58) D I) is the external diameter of the furnace or chamber top or bottom in inches, t is the thickness of the furnace plate in 32nds of an inch, L is the length of the furnaoo or other part in inches measured between points of substantial support, i.°., centres of rows of rivets in end seams or commencement of curvature of flange, whiohever is applicable, C = 1450 where the longitudinal seams of steel furnaces are welded and 1300 where they are riveted, C = 725 where the longitudinal soams of oiroular copper fire-boxes or furnaoe are fitted with double butt straps and 050 where they are lapped, Cx =• 50 -where the longitudinal seams of steel furnaces are welded and where they aro riveted. G1 = 25 where the longitudinal seams of oiroular copper fire-boxes or furn&oes are fitted with double butt straps and 22 • 5 where thoy are lapped.