Regulation 220, Indian Boiler Regulations, 1950.: Plain Furnaces of Horizontal Boilers
Indian Boiler Regulations, 1950. - Regulation 220
Text of regulation 220
Plain Furnaces of Horizontal Boilers
220. Plain Furnaces of Horizontal Boilers.—For plain fumacos or furnaces
•lengthened by Adamson or other joints or stiffeners of sufficient strength and for
the semi-oylindrioal tops of fire-boxes and bottoms of combustion chambers where
the sides are securely stayed, the working pressure shall not exceed the smaller of
the values obtained from the following formulas—
C (t—1)'
W.P. -= — x — Eqn. (57)
D (L +24)
Pi
W.P. = — x [10 (t—1)—L] Eqn. (58)
D
I) is the external diameter of the furnace or chamber top or bottom in inches,
t is the thickness of the furnace plate in 32nds of an inch,
L is the length of the furnaoo or other part in inches measured between points of
substantial support, i.°., centres of rows of rivets in end seams or commencement of
curvature of flange, whiohever is applicable,
C = 1450 where the longitudinal seams of steel furnaces are welded and 1300
where they are riveted,
C = 725 where the longitudinal soams of oiroular copper fire-boxes or furnaoe
are fitted with double butt straps and 050 where they are lapped,
Cx =• 50 -where the longitudinal seams of steel furnaces are welded and
where they aro riveted.
G1 = 25 where the longitudinal seams of oiroular copper fire-boxes or furn&oes
are fitted with double butt straps and 22 • 5 where thoy are lapped.