Regulation 6, Indian Boiler Regulations, 1950.: Modification of formulae
Indian Boiler Regulations, 1950. - Regulation 6
Text of regulation 6
Modification of formulae
6. Modification of formulae.—(i) Under the "Regulations for determining the
working pressure to be allowed on various parts of boilers, the material to which
the formulae apply shall in the absoncc of express provision to the contrary be steel
complying with the requirements of Chapter II .
(ii) Wheie no test certificates for shell plates and rivets are produced, the mate-
rial may be treated as iron, if the Chief Inspector is satisfied that tho material is of
suitable boiler quality. If in such cases the Chief Inspector is dearly satisfied that
the material is of good quality, n, higher strength than that allowed for iron may be
permitted but tho strength of the shell plates shall not, save for special reasons,
bo assumed to be more than 20 tons. In such cases S and Sx in equations 1, 3 and
4 of Chapter IV may be respectively 20 and 21 for steel and 21 and 18 for iron.
For iron across tho grain S may be 18.
(iii) Where end plates, furnaces, flat plates, girders, gusset and other stays, etc.
are made of stool or iron for which no test certificates are produced, the working
pressure as found from the formulae in which S is to be taken at tho lowest limit
proscribed for the pert, reduced by lfi per cent, shall, oxcept where such material
is specifically provided for m nny founulH, be tho working pressure permitted. For
flat plates of copper, the working pressure fts found from the formulae, reduced by
50 per cent, shall be the working pressure permitted.
6. Standard speoifloations for materials.—-The standard specifications for steel
wrought iron and copper plates and barn, and for east steel shall be those prescribed
iu Chapter II, but certificates of tests of material for wrought iron (exoept for special
wrought iron for screw stays) copper and cast steel shall not be required unless special
allowances are required. Suoh spocial allowances shall be in the discretion of the
Chief Inspector.