Rule 53, Atomic Energy (Factories) Rules, 1996: OVENS AND DRIERS
Atomic Energy (Factories) Rules, 1996 - Rule 53
Text of rule 53
OVENS AND DRIERS
53. OVENS AND DRIERS.-
(1) Application - This rule shall apply to ovens and driers, except those used in laboratories
or kitchens of any establishment and those which have a capacity below 325 litres.
(2) Definition:- For the purpose of this rule, "oven or drier" means any enclosed structure,
receptacle, compartment or box which is used for baking, drying or otherwise processing
of any article or substance at a temperature higher than the ambient temperature of the air
in the room or space in which explosive mixture of air and a flammable substance is
likely to be evolved within the enclosed structure, receptacle, compartment or box or part
thereof on account of the article or substance which is baked, dried or otherwise
processed within it.
(3) Separate electrical connection.- Electrical power supplied to every oven or drier shall be
by means of a separate circuit provided with an isolation switch.
(4) Design, Construction, examination and testing.-
(a) Every oven or drier shall be properly designed on sound engineering practice and
be of good construction, sound materials and adequate strength, free from any
patent defects and safe if properly used.
(b) No oven or drier shall be taken into use in a factory for the first time unless a
competent person has thoroughly examined all its parts and carried out the tests as
are required to establish that the necessary safe systems and controls provided for
safety in operation for the processes for which it is to be used and a certificate of
such examination and tests signed by that competent person has been obtained and
is kept available for inspection.
Atomic Energy Factory Rules, 1996
83
Rule 53
(c) All parts of any oven or drier which has undergone any alteration or repair which
has the effect of modifying any of the design characteristics, shall not be used
unless a thorough examination and tests as have been mentioned in clause (b) has
been carried out by a competent person and a certificate of such examination and
tests signed by that competent person has been obtained and is kept available for
inspection.
(5) Safety Ventilation.-
(a) Every oven or drier shall be provided with a positive and effective safety
ventilation system using one or more motor-driven centrifugal fans so as to dilute
any mixture of air and any flammable substance that may be formed within the
oven or drier and maintain the concentration of the flammable substance in the air
at a safe level of dilution.
(b) The safe level of dilution referred to in clause (a) shall be so as to achieve a
concentration of the concerned flammable substance in air of not more than 25
percent of its lower explosive limit:
Provided that a level of concentration in air up to 50 percent of the lower
explosive limit of the concerned flammable substance may be permitted to exist
subject to installation and maintenance of an automatic device which -
(i) shows continuously the concentration of the flammable substances in air
present in the oven or drier at any instant;
(ii) sounds an alarm when the concentration of the flammable substance in air
in any part of the oven or drier reaches a level of 50 percent of its lower
explosive limit; and
(iii) shuts down the heating system of the oven or drier automatically when the
concentration in air of the flammable substance in any part of the oven or
drier reaches a level of 60 percent of its lower explosive limit, is provided
to the oven or drier and maintained in efficient working condition.
(c) No oven or drier shall be operated without its safety ventilation system working in
an efficient manner.
(d) No oven or drier shall be operated with a level of dilution less than what is
referred to in clause (b).
(e) Exhaust ducts of safety ventilation systems should be so designed and placed that
their ducts discharge the mixture of air and flammable substance away from
workrooms and not near windows
Atomic Energy Factory Rules, 1996
84
Rule 53
or doors or other openings from where the mixture could re-enter the workrooms.
(f) The fresh air admitted into the oven or drier by means of the safety ventilation
system shall be circulated adequately by means of circulating fan or fans through
all parts of the oven or drier so as to ensure that there are no locations where the
flammable substance can accumulate in the air or become pocketed to any
dangerous degree.
(g) Throttling dampers in any safety ventilation system shall be so designed, by
cutting away a portion of damper or otherwise, that the system shall handle at
least the minimum ventilation rate required for safety when they are set in their
maximum throttling position.
(6) Explosion panels.-
(a) Every oven or drier having an internal total space of not less than half cubic meter
shall be provided with suitably designed explosion panels so as to allow release of
the pressure of any possible explosion within the oven or drier through explosion
vents. The area of openings to be provided by means of such vents together with
the area of openings of any access doors which are provided with suitable
arrangements for their release in case of any explosion, shall be not less than 2200
sq.cm. for every one cu.m. of volume of the oven or drier. The design of the
explosion panels and doors as mentioned above shall be such as to secure their
complete release under an internal pressure of 25 kPa (0.25 kg./sq.cm.).
(b) The explosion releasing panels, shall, as far as practicable, be situated at the roof
of the oven or drier or at those portions of the walls where persons do not remain
in connection with operation of the oven or drier.
(7) Interlocking arrangements.-In each oven or drier efficient inter-locking arrangements
shall be provided and maintained to ensure that-
(a) all ventilating fans and circulating fans whose failure would adversely effect the
ventilation rate or flow pattern, are in operation before any mechanical conveyor
that may be provided for feeding the articles or substances to be processed in the
oven or drier is put into operation;
(b) failure of any of the ventilating or circulating fans will automatically stop any
conveyor as referred to in clause (i) as may be provided, as well as stop the fuel
supply by closing the shut off valve and shut off the ignition in case of gas or oil
fired ovens, and in the case of electrically heated ovens switch off the electrical
supply to the heaters;
Atomic Energy Factory Rules, 1996
85
Rule 53
(c) the above said mechanical conveyor is set in operation before the above said shut
off valve can be energized; and
(d) the failure of the above said conveyor will automatically close the above said shut
off valve in the case of ovens and driers heated by gas, oil or steam and deactivate
the ignition system, or cut off the electrical heaters in the case of electrically
heated ovens or furnaces.
(8) Automatic preventilation.- Every oven or drier heated by oil, gas , steam or electricity
shall be provided with an efficient arrangement for automatic preventilation consisting of
at least 3 volume changes with fresh air by operation of the safety ventilation fans and the
circulating fans (if used)so as to effect purging of the oven or drier of any mixture of air
and a flammable substance before the heating system can be activated and before the
conveyor can be placed in position.
(9) Temperature control.- Every oven or drier shall be provided with an automatic
arrangement to ensure that the temperature within does not exceed a safe upper preset
limit to be decided in respect of the particular processing being carried on.
(10) Multistage processes.- Wherever materials are to be processed in ovens or driers in
successive operations, suitable arrangement shall be provided to ensure that the operating
temperatures necessary for safe operation at each stage are maintained with the design
limits.
(11) Combustible substances not to drip on electrical heaters or burner flames.- Effective
arrangements shall be provided in every oven or drier to prevent dripping of combustible
substances on electric heaters or burner flame used for heating.
(12) Periodical examination testing and maintenance.-
(a) All parts of every oven and drier shall be properly maintained and thoroughly
examined and the various controls as mentioned in this rule and the working of
the oven or drier tested at frequent intervals to ensure its safe operation by a
competent person.
(b) A register shall be maintained in which the details of the various tests carried out
from time to time under clause (a) shall be entered and every entry made shall be
signed by the person doing the tests.
(13) Training of Operators.- No person shall be assigned any task connected with operation of
any oven or drier unless he has completed 18 years of age and he is properly trained.
Atomic Energy Factory Rules, 1996