Rule 54, Atomic Energy (Factories) Rules, 1996: REACTION VESSELS AND KETTLES
Atomic Energy (Factories) Rules, 1996 - Rule 54
Text of rule 54
REACTION VESSELS AND KETTLES
54. REACTION VESSELS AND KETTLES.-
(1) This rule applies to reaction vessels and kettles, here in after referred to as reaction
vessels, which normally work at a pressure not above the atmospheric pressure but in
which there is likelihood of pressure being created above the atmospheric pressure due to
reaction getting out of control or any other circumstances.
(2) In the event of the vessel being heated by electrical means, a suitable thermostatic control
device shall be provided to prevent the temperature exceeding the safe limit.
(3) Where steam is used for heating purposes in a reaction vessel, it shall be supplied through
a suitable pressure reducing valve or any other suitable automatic device to prevent the
maximum permissible steam pressure being exceeded, unless the pressure of the steam in
the supply line itself cannot exceed the said maximum permissible pressure.
(4) A suitable safety valve or rupture disc of adequate size and capacity shall be provided to
effectively prevent the pressure being built up in the reaction vessel beyond the safe limit.
Effective arrangements shall be made to ensure that the released gases, fumes, vapours,
liquids or dusts, as the case may be, are led away and disposed of through suitable pipes
without causing any hazard. Where flammable gases or vapours are likely to be vented
out from the vessel, the discharge end shall be provided with a flame arrester.
(5) Every reaction vessel shall be provided with a pressure gauge having the appropriate
range.
(6) In addition to the devices as mentioned in the foregoing provisions, means shall be
provided for automatically stopping the feed into the vessel as soon as process conditions
deviate from the normal limits to an extent which can be considered as dangerous.
(7) Wherever necessary, an effective system for cooling, flooding or blanketing shall be
provided, for the purpose of controlling the reaction and process conditions within the
safe limits of temperature and pressure.
(8) An automatic audio-visual warning device shall be provided for clear warning whenever
process conditions exceed the preset limits. This device, wherever possible, shall be
integrated with automatic process correction systems.
(9) A notice pointing out the possible circumstances in which pressures above atmospheric
pressure may be built up in the reaction vessel, the dangers involved and the precautions
to be taken by the operators shall be displayed at a conspicuous place
Atomic Energy Factory Rules, 1996
87
Rules 54-56
near the vessel.
Previous and next
Questions people ask
Is rule 54 of Atomic Energy (Factories) Rules, 1996 still in force?
No repeal of Atomic Energy (Factories) Rules, 1996 is recorded.