Regulation 131, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Fencing of filter banks
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 131
Text of regulation 131
Fencing of filter banks
131. Fencing of filter banks. – (1) Alternating Current and Direct Current filter banks area shall be efficiently
protected by fencing or other means, not less than 1.8 metre in height, so as to prevent access to the conductors
and apparatus therein by any unauthorised person and the fencing of such area shall be effictively earthed.
(2) The gate of fencing and earth switch of the filter bank shall be interlocked such that the gate can be opened
only after the disconnection and discharging of the filter bank completely.
(3) The air core smoothing reactor shall be fenced all around and the fence shall not fall in the Magnetic
Clearance Contour of the smoothing reactor.
(4) Common neutral bus in Alternating Current filters shall be earthed at one point only.
Previous and next
Questions people ask
Is regulation 131 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?
No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.