LawGrids logoLAWGRIDS.ORG

Regulation 130, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: General safety requirements

Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 130

Text of regulation 130

General safety requirements

130. General safety requirements. – (1) A wire mesh shall be provided beneath the walk way; wherever constructed above the hanging valves in the valve hall. 146 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4] (2) Cables used for sensitive measurements shall be laid in separate and completely screened or covered channels or galvanised steel pipes. (3) A separate emergency source of illumination with automatic initiation shall be provided in every room or compartment of high voltage direct current station. (4) No oil immersed apparatus shall be kept within the valve hall. (5) All doors of compartments containing modules equipped with laser diodes and junction boxes of the fibre optic cables shall be locked and marked with laser warning symbols.

Previous and next

All provisions of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.

Questions people ask

Is regulation 130 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?

No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.