Regulation 130, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: General safety requirements
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 130
Text of regulation 130
General safety requirements
130. General safety requirements. – (1) A wire mesh shall be provided beneath the walk way; wherever constructed
above the hanging valves in the valve hall.
146 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
(2) Cables used for sensitive measurements shall be laid in separate and completely screened or covered
channels or galvanised steel pipes.
(3) A separate emergency source of illumination with automatic initiation shall be provided in every room or
compartment of high voltage direct current station.
(4) No oil immersed apparatus shall be kept within the valve hall.
(5) All doors of compartments containing modules equipped with laser diodes and junction boxes of the fibre
optic cables shall be locked and marked with laser warning symbols.