Conditions to apply where telecommunication lines and power lines are carried on same supports

70. Conditions to apply where telecommunication lines and power lines are carried on same supports. – (1) Every overhead telecommunication line laid on supports of an electric line shall consist of conductors each 128 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4] having a breaking strength of not less than 270 kgf. (2) Every telecommunication line laid on supports of an electric line shall be protected against lightning as per relevant standards. (3) Where a telecommunication line is laid on supports of an electric line of voltage exceeding 650 V, a suitable arrangement shall be made to safeguard any person against injury resulting from contact, leakage or induction between such electric and telecommunication lines.

Previous and next

All provisions of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.

Questions people ask

Is regulation 70 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?

No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.