Regulation 70, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Conditions to apply where telecommunication lines and power lines are carried on same supports
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 70
Text of regulation 70
Conditions to apply where telecommunication lines and power lines are carried on same supports
70. Conditions to apply where telecommunication lines and power lines are carried on same supports. – (1)
Every overhead telecommunication line laid on supports of an electric line shall consist of conductors each
128 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
having a breaking strength of not less than 270 kgf.
(2) Every telecommunication line laid on supports of an electric line shall be protected against lightning as per
relevant standards.
(3) Where a telecommunication line is laid on supports of an electric line of voltage exceeding 650 V, a suitable
arrangement shall be made to safeguard any person against injury resulting from contact, leakage or induction
between such electric and telecommunication lines.
Previous and next
Questions people ask
Is regulation 70 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?
No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.