Regulation 9, The Himachal Pradesh Electricity Regulatory Commission (Rooftop Solar PV Grid Interactive Systems based on Net Metering) Regulations, 2015: Metering arrangement
The Himachal Pradesh Electricity Regulatory Commission (Rooftop Solar PV Grid Interactive Systems based on Net Metering) Regulations, 2015 - Regulation 9
Text of regulation 9
Metering arrangement
9. Metering arrangement.-
1
[(1) The eligible consumer shall, for recording the
electricity generation install and maintain main Solar Meter of 0.2s class accuracy with
facility for recording meter reading using Meter Reading Instrument (MRI) or Wireless
equipment. Check meter shall be mandatory for Rooftop Solar PV System having capacity
of more than 20 kW. For installation of capacity of less than or equal to 20 kW, the solar
check meter would be optional. The cost of such meter(s) shall be borne by the eligible
consumer.; and]
(2) Net meter capable of measuring the net flows shall be installed and maintained, at
the cost of eligible consumer, by the distribution licensee and the meter shall be compliant to
the system of recording meter reading through Meter Reading Instrument (MRI) or through
wireless:
Provided that if bills are prepared on the basis of MRI downloads or if meter reading
is taken on the basis of remote meter reading and the consumer wants to have a record of the
reading taken, he shall be so provided by the licensee.
(3) The meters installed as per sub-regulation (1) and (2) shall be jointly inspected
and sealed on behalf of both the parties.
(4) Not withstanding anything contained in sub-regulation (3), the
2
[ the meter
readings of the Net Meter as well as the Solar Meter (main as well as check meter where
installed) taken by the distribution licensee] shall form the basis of commercial settlement.
1
Subs. vide Not. No. HPERC-H(1)-11/2015dated 6
th
November, 2018 published in R.H.P. dated 14
th
November, 2018 at p. 6010-6016 and before its substitution read as under:
“(1) The eligible consumer shall, for recording the electricity generation, install and maintain the
Solar Meter at his cost and a;”
2
Subs. of sub-regulation (4) for the words “meter reading taken by the distribution licensee” vide
Not. No. HPERC-H(1)-11/2015dated 6
th
November, 2018 published in R.H.P. dated 14
th
November, 2018 at p.
6010-6016.
10 Compendium of HPERC Regulations, March 2021
(5) All the meters shall adhere to the standards as specified in Central Electricity
Authority (Installation and Operation of Meters) Regulations, 2006 as amended from time to
time.
(6) All the meters to be installed for net metering shall be of the same or of better
Accuracy Class Index than the existing meter installed for measuring the supply of the
power to the consumer.
(7) The net meter to be installed for the eligible consumer shall be compliant to the
requirements as per the applicable tariff including those relating to Time of Day (ToD) tariff
and in case of consumer availing open access, shall also have the requisite features of special
energy meters.