Rule 20, The Maharashtra Economiser Rules, 1965: Preparation for Hydraulic Test
The Maharashtra Economiser Rules, 1965 - Rule 20
Text of rule 20
Preparation for Hydraulic Test
20. Preparation for Hydraulic Test :- (a) The chest of all mountings, subject to the
water pressure, shall be in place and shut tight or blank flanged. The relief value
shall either be secured or removed and the chest opening blank flanged. The
attachment for the Dy. Director’s pressure gauge and the nipple for connecting
the Dy. Directors’ test pump hose shall be in order. All caps shall be properly
fitted and tightened up. The economiser shall be completely filled with water,
care being taken to allow all air to escape, and if possible, a preliminary test not
exceeding the working pressure of the economiser, shall be taken before the Dy.
Director visits to test the tightness of the joint. When an economiser is
hydraulically tested it shall be offered entirely bare.
THE MAHARASHTRA ECONOMISER RULES, 1965
6
(b) Hydraulic tests of economiser shall be made after the inspection. The test
pressure to be applied to economisers at such subsequent examinations shall be
from one and a quarter to one and a half times the working pressure of the
economiser :
Provided that the Director may, at his discretion, waive the requirement of
hydraulic test of an economiser, if he deems fit.