Form C, The Maharashtra Boiler Rules, 1962: FORM C
The Maharashtra Boiler Rules, 1962 - Form C
Text of form C
FORM C
FORM C
GENERAL WORKING OF BOILERS
(See Rule 8)
Instruction to Boiler Attendants
These instructions should be frequently and carefully studied with
a view to keeping in mind the precautions to be observed and ordinary
procedure to be followed in the safe working of boilers.
Precautions before starting the Fires
Before starting the fires in a boiler the attendants should—
(1) see that here is sufficient water in the boiler and that the gauge cocks
are working freely;
(2) see safety valves, or open cock on top of boiler to allow air to escape ;
(3) see that the blow-off cock is fully closed and tight;
(4) see that safety valves and fee check valve are free and workable;
(5) note if the pressure gauge pointer is at zero;
(6) see that the feed pump is in working order’
He must not rely on the supposition that the water he has previously put
in it still in the boiler, as it may have tun out without the knowledge through a
leak or open cock, nor can he be sure that the gauge glass shows the true water
level until he has tested it. This is done in the following manner; shut off the
lower gauge cock and empty the glass by the drain cock; then shut the drain cock
and open the gauge cock; if everything is in order, the water will then rise in the
glass to the same height as before.
Raising steam :-In getting up steam in all types of boilers, the operation
should be as gradual as circumstances will allow. Nothing turns a new boiler into
an old one sooner than getting up steam too quickly. Forcing the fires when
starting work is liable to cause straining of the steams and tubes of the boiler. In
the case of large boilers generally steam should not be got up in less than six
hours. Before getting up steam the water level should be observed, to ensure
that water is at the proper heights, in the glass, the pressure gauge noted and the
safety valves tried to see they are free. The blow-off cock should be examined to
see that it is completely shut and tight.
Pressure gauge :- The pressure or steam gauge should be kept in order
and be in such a position as to be easily seen by the boiler attendant. There
should be a plain mark on it showing the highest pressure allowed for the boiler
and the dial should be kept clean so that the figures may easily be read.
Steam pressure : Ordinarily, the safety valves will prevent the steam
from rising much above the working pressure, but if the steam gauge shows is
rapid an increase of pressure as to indicate danger of exceeding the highest limit,
The Maharashtra Boiler Rules, 1962 32
water should be immediately fed into the boiler, and the dampers partially
closed in order to diminish the effect of the fire. If however, the water has fallen
so low that there is danger of an accident from this cause the fires should be
withdrawn before feeding in water the safety valves eased and if the engine is at
rest it should be started so as to reduce the pressure.
The safety valves are provided to guard against over-pressure. They should be
moved by hand every day so as to prevent them from sticking. If moved only
occasionally, they are liable to leak.
The valve can be tested by slowly raising it a little and when let down, it should
closed perfectly tight. It should never be opened by a sudden knock or pull. If it
does not closed tight turn it on its seat until it fit, or when its construction does
not permit this, rise it slowly a few times and let it down again, but on no
account must the valve be screwed down further or loaded more than what has
been allowed by the Inspector.
Safety valves must never be over-loaded and spring valve should have ferrules
or other provisions against the valves being screwed down too far. In case of an
accident resulting from wilful overloading culprit might be held criminally
responsible at the official inquiry or inquest.
Low water safety valves—If there is low water safety valves, test it occasionally
by lowering the water level to see that valve begins to blow at the right point. It
should give warning “before” the water level has sunk too low and before
damage can be done when the boiler is open, examine the floats and lever and
see that they are free and that they give the valve the fuel rise. With the ordinary
type of high steam and low water safety valve the float should be down at its
lowest position and the valve full open when the boiler is empty.
The water gauge :- These will be kept in best order by frequently blowing
through. The cocks are thus kept in good working condition without Jeaking.
Blow through the drain cock at the bottom of the gauge and shut and open the
steam and water cocks every few hours. These cocks should be blown through
more frequently when the water is dirty. Should either of the passage become
choked, or whenever the water in the gauge glass moves sluggishly the passage
must be cleaned. This is best done with a wire. The gauge glass is so arranged
that its top cock connects with the steam space and its bottom cock is below the
water line. The water line will ordinarily be near the middle of the glass tube.
Always test the glass water gauges thoroughly the first thing in the morning and
at the commencement of every shift. This is done by first opening rain cock and
then shutting the upper cock which should give water; the upper cock should
then be opened and the bottom cock closed which should give steam during this
test the drain cock should be kept open.
If water and steam do not appear in proper order the cocks are choked and the
passage should be cleaned. To lessen the risk of breaking the gauge glass the
water cock should always be re-opened after the steam cock.
The Maharashtra Boiler Rules, 1962 33
Gauge glasses with a narrow white strip running the whole length of the glass on
the side next the boiler are recommended as they show the water line more
clearly specially when the water is dirty.
The boiler regulations framed by the Board require every water gauge glass to
be fitted with, a guard to prevent injury to the attendants. See that it is always in
place and clean when there is steam in the boiler.
Special Note :- It does not follow that there is plenty of water in the boiler
because there in plenty of water in the gauge glass. The passages may be choked
and empty gauge glasses are some times mistaken for full ones and explosions
have resulted there form. Hence the importance of keeping the gauge, cocks
perfectly tight and clean and of blowing through the test cocks frequently.
A large number of accidents have been due to inoperative water gauges and to
negligence of the attendants in not carefully reading the water level.
The blow-off cock :- The blow-off should be used daily if the water is at all dirty
or sedimentary, especially with Locomotive type and Vertical Boilers as their
narrow water spaces are liable to get choked with mud, which soon hardness
into a solid mass. The amount of water to be blown out depends on the size of
the boiler and can be determined only from experience. When blowing out the
best result is obtained if the water has been at rest for some time ( say before the
engine is stared) thus giving the sediment time to settle; if the feed waters
cleaned merely turn the cock round.
The scum cock :- When scum cocks are fitted, if the feed water is dirty, a little
should be blown off daily; if the water is clean, merely turn the cock round.
Before opening the scum cock, see that the water is at the height indicated by the
water level pointer; otherwise the scumming will be ineffective. Water should be
blown from the surface through the scum cock when steam is being drawn off,
i.e. when the engine or other machinery is working.
Manhole and other door joints.- When making such joints the jointing
materials should never be of round sectioned packing. Care must be taken that
the spigot of the door is centrally placed in the hole, as many accidents have
resulted from packing bring blown out between the spigot and side of hole, even
when the clearance was only 3 mm. The nuts must be carefully and evenly
tightened. Further tightening should be made during the process of heating up
the boiler when raising steam.
Steam-pipes :- When properly arranged should give no trouble. Frequently
however, they are so designed as to contain pickets, in which, while out of us,
condensed steam accumulates. Such water is exceedingly, dangerous and great
care should be taken to see that the pipes are properly drained before the stop-
valve is opened otherwise “water hammer” will take place even with the best
designed steam pipes, and disastrous explosions causing loss of life and property
may occur.
The Maharashtra Boiler Rules, 1962 34
Scale and grease :- Roughly speaking, scale offers a hundred times as much
resistance to the passage of beat as does a similar thickness of the steel or iron. A
12mm furnace plate covered with 2 mm. scale is as efficient a heat retarder as
steel furnace 0.250 mm, thick. Grease is about ten times worse than scale. In a
boiler at work the temperature of a clean furnace plate is only slightly in excess
of that of the water in the boiler; but is scale or grease is interposed between the
water and the plate, the latter acquires a temperature more nearly
approximately that of the flame with which it is in contact. If the fire is fierce
(artificial draught) the furnace tube may grow so hot that it elongates
considerable. If in addition, cold air is admitted during each firing, a concerting
action of the furnace takes place, which is one of the worst causes of boiler wear
and tear.
Wear and Tear can be reduced and the life of a boiler prolonged if scale and
grease are prevented from accumulating in a boiler. The combined effects of
scale or grease and artificial draught are disastrous. Scale or grease also causes
waste of fuel.
Grease :- A mixture of sedimentary water , soda and grease produces an
adhesive scum, Where this is suspected, the water level should never be lowered
below the furnace top unless the boiler is afterwards entered and this scum
cleaned off the furnace plate before the firing again.
Scale removal :- The customary method is not a satisfactory one. The boiler is
emptied and then cooled down by opening all the manholes, and the result is
that the scale which would otherwise be soft, hardens through contact with the
air and requires laborious chipping off.
A very effective, but slower method is to retain the water in the boiler until cool,
and not to run it out until the men are ready to enter the boiler with water house
brushers and scrapers, The scale will then be soft and easily removable.
If time is a consideration, the cooling can be accelerated by adding cold feed to
the hot water in the boiler and slowly running off the cold water. Another
method is to blow off the boiler with the lowest possible pressure (not more
than 1 Kilogram per sq.cm) and to keep it closed until cold. The scale will then be
easily removed.
Treatment of feed water :- Many feed waters require soda or other chemicals
to arrest corrosion or to change the nature of the scale.
There is no harmless chemical which will remove scale or sediment when it has
once got into the boiler and the only effective process is to purify the feed water
before it enters the boiler. By this means, the sediment, and generally too, the
added chemical, can be deposited in tanks or in filters, and therefore never goes
into the boiler, excepting when the water obtainable is very good, water-
purifying apparatus ought to pay any boiler-owners, particularly at those works
where three or more boilers are in constant work. Boiler Owners wishing to
have definite advice as to the best treatment of their feed water should have it
The Maharashtra Boiler Rules, 1962 35
analyzed at some chemical laboratory and ascertain the best treatment in the
particular circumstances.
Special attention is drawn to the not in frequent but very bad practice of
allowing the waste steam from the Engine Cylinders or Pumps to be drained into
the Boiler Feed Water Tanks. The waste steam from cylinders is always mixed
with a certain amount of oily matter which will be deposited in the feed water
tanks and ultimately be pumped into the boiler, with possible disastrous results,
as it will be obvious to every careful boiler attendant that should the oil be
deposited on the furnace crowns, they may become overheated and collapse.
It should be the first care of the boiler-owner, and the Boiler Attendant to see
that the feed water is kept as pure as possible. Impure feed water means
additional expense on the upkeep of the boiler.
Preservation of boilers when not in use:- steam boilers, when not in use are
liable to deterioration from corrosion and unless well cared for and made rust-
proof; they may depreciate more rapidly than when in use. They should be
thoroughly drained and thoroughly dried and all valves, cocks and openings
closed so as to exclude moisture. Another plan is to fill the boiler with water to
which about 1/100 per cent caustic soda has been added.
Special instructions for Boiler No. :- this boiler should be opened up and
thoroughly cleaned after a period of work which should not exceed (as indicated
in certificate). A record of such cleanings should be maintained and produced,
when required by the Deputy Director.