Rule 24, The Factory rules 1962: When artificial humidification not allowed
The Factory rules 1962 - Rule 24
Text of rule 24
When artificial humidification not allowed
[24. When artificial humidification not allowed. - There shall be no artificial
humidification in any room of a cotton spinning or weaving factory-
(a) by the use of steam during any period when the dry-bulb temperature of that room
exceeds 29.5 degrees celsius; and
(b) at any time when the wet-bulb reading of the hygrometer is higher than that
specified in the following Schedule in relation to the dry-bulb reading of the
hygrometer at that time; or as regards a dry-bulb reading intermediate between any
two dry-bulb readings indicated consecutively in the schedule when the dry-bulb
reading does not exceed the wet-bulb reading to the extent indicated in relation to the
lower of these two dry-bulb readings :-
Schedule
Reading in degrees celsius
Dry-bulb Wet-bulb
Dry
bulb
Wet-bulb Dry-bulb Wet-bulb
(1) (2) (1) (2) (1) (2)
15.5 14.5
25.
0
24.0 34.5 30.0
16.0 15.0
25.
5
24.5 35.0 30.5
16.5 15.5
26.
0
25.0 35.5 31.0
17.0 16.0
26.
5
25.5 36.0 31.0
17.5 16.0
27.
0
26.0 36.5 31.5
18.0 16.5
27.
5
26.0 37.0 31.5
18.5 17.0
28.
0
26.5 37.5 31.5
19.0 18.0
28.
5
27.0 38.0 32.0
19.5 18.5
29.
0
27.0 38.5 32.0
20.0 19.0
29.
5
28.0 39.0 32.0
20.5 19.5
30.
0
28.0 39.5 32.5
21.0 20.0
30.
5
28.5 40.0 32.5
21.5 20.5
31.
0
28.5 40.5 33.0
22.0 21.0
31.
5
29.0 41.0 33.0
22.5 21.0
32.
0
29.0 41.5 33.0
23.0 21.5
32.
5
29.0 42.0 33.0
23.5 22.0
33.
0
29.5 42.5 33.0
24.0 23.0
33.
5
29.5 43.0 33.5
24.5 23.5
34.
0
30.0 43.5 33.5
Provided, however, that clause (b) shall not apply when the difference between the
wet-bulb temperature as indicated by the hygrometer in the department concerned
and the wet-bulb temperature taken with a hygrometer outside in the shade is less
than 2 degrees.]