Rule 23, The Factory rules 1962: Ventilation and temperature
The Factory rules 1962 - Rule 23
Text of rule 23
Ventilation and temperature
[23. Ventilation and temperature. - (1) Limits of temperature and air movement. - In
any factory the maximum wet-bulb temperature of air in a work room at a height of 1.5
meters above the floor level shall not exceed 30 degrees Celsius and adequate air
movement of at least 30 meters per minute shall be provided and in relation to
dry-bulb temperature, the wet-bulb temperature in the work-room at the said height
shall not exceed that shown in the schedule annexed hereto, or as regards a dry-bulb
reading intermediate between the two dry-bulb readings that specified in relation to
the higher of these two dry-bulb readings :
Schedule
Dry-bulb
temperature
Wet-bulb
temperature
30°C to 34°C 29°C
35°C to 39°C 28.5°C
40°C to 44°C 28°C
45°C to 47°C 27.5°C :
Provided that if the temperature measured with a thermometer inserted in a hollow
globe of 15 centimeter coated met black outside and kept in the environment for not
less than 20 minutes exceeds the dry-bulb temperature of air, the temperature so
recorded by the globe thermometer shall be taken in place of the dry-bulb
temperature :
Provided further that when the reading of the wet-bulb temperature outside in the
shade exceeds 27 degree celsius, the value of the wet-bulb temperature allowed in
the schedule for a given dry-bulb temperature may be correspondingly exceeded to
the same extent :
Provided further that this requirement shall not apply in respect of factories covered
by Section 15 and in respect of factories where the nature of work carried-on involves
production of excessively high temperatures referred to in clause (ii) of sub-section (1)
to which workers are exposed for short periods of time not exceeding one hour
followed by an interval of sufficient duration in thermal environments not exceeding
those otherwise laid down in this rule :
Provided further that the Chief Inspector, having due regard to the health of the
workers, may in special and exceptional circumstances, by an order in writing exempt
any factory or part of a factory from the foregoing requirement, in so far as restricting
the thermal conditions within the limits laid down in the schedule are concerned, to the
extent that he may consider necessary subject to such conditions as he may specify.
(2) Provision of thermometers. - (a) If it appears to the Inspector that in any factory,
the temperature of air in a work room is sufficiently high and is likely to exceed the
limits prescribed is sub-rule (1), he may serve on the manager of the factory an order
requiring him to provide sufficient number of whirling hygrometers or any other type of
hygrometers and direct that the dry-bulb and wet-bulb reading in each such workroom
shall be recorded at such positions as approved by the Inspector twice during each
working shift by a person especially nominated for the purpose by the manager and
approved by the Inspector.
(b) If the Inspector has reason to believe that a substantial amount of heat is added
inside environment of a workroom by radiation from walls, roof or other solid
surroundings, he may serve on the manager of the factory an order requiring him to
place the globe thermometers referred to in the first proviso in sub-rule (1) at place
specified by him and keep a record of the temperature in a suitable register.
(3) Ventilation. - (a) In every factory the amount of ventilating openings in a workroom
below the caves shall, except where mechanical means of ventilation as required by
clause (b) below are provided, be of an aggregate area of not less than 15% of the
floor area and so located as to afford a continued supply of fresh air :
Provided that the Chief Inspector may relax the requirements regarding the amount of
ventilating openings if he is satisfied that having regard to the location of the factory
orientation of the workroom, prevailing winds, roof height and the nature of
manufacturing process carried on, sufficient supply of fresh air into the workroom is
afforded during most part of the working time :
Provided further that this requirement shall not apply in respect of workrooms of
factories-
(i) covered by Section 15; or
(ii) in which temperature and humidity are controlled by refrigeration, and air
conditioning.
(b) Where in any factory owing to special circumstances such situation with respect to
adjacent buildings and height of the building with respect to floor space, the
requirements of ventilation openings under clause (a) of this sub-rule he may serve on
the manager of the factory an order requiring him to provide additional ventilation
either by means of roof ventilators or by mechanical means.
(c) The amount of fresh air supplied by mechanical means of ventilation in an hour
shall be equivalent to at least six times the cubic capacity of the workroom and shall
be distributed evenly throughout the workroom without dead air pockets or undue
draughts cansed by high inlet velocities.
(d) In regions where in summer (15th March, 15th July) dry-bulb temperature of
outside air in the shade during most part of the day exceed 35 degrees Celsius and
simultaneous wet-bulb temperatures are 25 degrees celsius or below and in the
opinion of the Inspector the manufacturing process carried on the workroom of a
factory permits thermal environments with relative humidity of 50% or more, the
Inspector may serve on the manager of the factory an order to have sufficient supply
of outside air for ventilation cooled by passing it through water sprays either by means
of unit type of evaporative air coolers (desert coolers) or, where supply of outside air
is provided by mechanical means through ducts in a plenum system, by means of
central air washing plants.]
Rules 24 to 34 prescribed under sub-section (1) of Section 15
Previous and next
Questions people ask
Is rule 23 of the Factory rules 1962 still in force?
No repeal of the Factory rules 1962 is recorded.