Form III, THE INDIAN ELECTRICITY RULES, 1956: FORM III
THE INDIAN ELECTRICITY RULES, 1956 - Form III
Text of form III
FORM III
FORM III
INSPECTION REPORT
(Under rule 46 of the Indian Electricity Rules, 1956)
High and Extra-high Voltage Installation of a Consumer
Report No…………………… Date of Inspection
Challan No…………………… Dated
Inspection Fee Rs……………. Date of Last inspection
1. Consumer No
2. Voltage and system of supply:
(i) Volts…………………….
(ii) No. of phases……………
(iii) AC/DC…………..
3. Name of the consumer/owner…………………….
4. Address of the consumer/owner……………………
5. Location of the premises……………………………
6. Particulars of the installation
I. Motors:
Make No. H.P. Amps. Voltage
(1)………………
(2)……………….
(3)………………..
II. Transformers:
Make No. KVA Power Voltage
H.V L.V.
(1)…………………..
(2)…………………..
(3)………………….
III. Other equipment (complete details to be furnished):
(1)……………………
(2)……………………
(3)……………………….
IV Total capacity in h.p./KVA…………………………………..
V. Generators (in the case of consumer himself generating energy):
(1)……………………..
(2)…………………….
(3)…………………….
7. General condition of the installations:
Rule of the Indian
Electricity Rules, 1956
Requirement Report
1 2 3
3. (i) Is the list of authorised persons properly made and kept upto date
duly attested?
(ii) Whether the authorised persons are competent for the work
assigned to them?
29. (i) Is/are there any sign(s) of over-loading in respect of any
apparatus?
(ii) State if any unauthorised temporary installation exists.
(iii) Whether the H.V motors and controlling equipment are being over
hauled periodically and record kept of the same in a register?
(iv) Whether the transformer oil samples are being tested periodically
and results recorded in a register?
(v) Whether suitable lightning arrestors have been provided near the
transformers for protection against lightning?
(vi) Whether earth resistance is being measured periodically and results
recorded in a register?
(vii) Any other defect or condition which may be source of danger.
(viii) Any other general remarks.
30. Service line and apparatus of the supplier on consumer’s
premises:
Give report on the condition of service lines, cables, wires, circuit
breaker, isolating switches, protective recording and integrating
apparatus and such other fittings placed by the supplier/owner on the
premises.
31. Has the supplier provided suitable cutouts, within consumer’s
premises, in an accessible position? Are they within an adequately
enclosed fire proof receptacle?
33. (i) State if earth terminal is provided by the supplier.
(ii) Is the consumer’s separate earth efficient? (State the earth
resistance, if measured).
(iii) Report on the efficiency of the earthing arrangement.
34. (i) Are bare conductors (if any) in building inaccessible?
(ii) Whether readily accessible switches have been provided for
rendering them dead?
(iii) Whether any other safety measures are considered necessary?
35. State if “Danger Notices” in Hindi and the local language of the
district and of the type approved by the Electrical Inspector are affixed
permanently in conspicuous position as per this rule.
36. Whether the practice of working on live lines and apparatus is
adopted? If so, have the safety measure been approved by the
Electrical Inspector?
41. State if the circuits or apparatus intended for operating at different
voltage (s) are distinguishable by means of indications) of permanent
nature.
42. Whether all circuits and apparatus are so arranged that there is no
danger of any part(s) becoming accidentally charged to any voltage
beyond the limits of voltage for which it/they is/fire intended?
43. (i) In the case of generating and enclosed stations have fire-buckets,
filled with clean dry sand, been conspicuously marked and kept in
convenient situations in addition to fire-extinguishers suitable for dealing
with electric fires?
(ii) State if First Aid Boxes or Cupboards conspicuously marked and
properly equipped are provided and maintained.
(iii)Is some staff trained in First Aid Treatment?
44. (i) State if instructions in 1[English or Hindi and the local language of
the district and where Hindi is the local language, in English and Hindi,]
for the restoration of persons suffering from electric shock have been
affixed in a conspicuous place.
(ii) Are the authorised persons able to apply instructions for
resuscitation of persons suffering from electric shock?
1. Ins. by GSR 735, dt. 4.9.1982.
49. Leakage on premises:
State insulation resistance between conductors and earth in Megaohms.
50. (i) Whether a suitable linked switch/circuit breaker is placed near
the point of commencement of supply so as to be readily accessible and
capable of being easily operated to completely isolate the supply?
(ii) Is there a suitable linked switch or a circuit breaker to carry and
break the full load current on the secondary side of a transformer?
(iii) Whether every distinct circuit is protected against excess energy
by means of a suitable circuit breaker or cut-outs?
(iv) State if a suitable linked switch or circuit breaker is provided near
the High Voltage motor or other apparatus for controlling supply to the
motor or apparatus.
(v) State if adequate precautions are taken to ensure that no live
parts are so exposed as to cause danger.
51. (i) State the condition of metallic coverings provided for various
conductors.
(iii) (a) State whether clear space of 90 cm is provided in front of the
main switch-board.
(b) State whether the space behind the switch-board exceeds 75 cm.
in width or is less than 23 cm.
(c) In case the clear space behind the switch-board exceeds 75 cm
state whether a passage way from either end of the switch board to a
height of 1.80 meters is provided.
64. (i) State if all conductors and apparatus including live parts thereof
are inaccessible.
(ii) State if all windings of motors or other apparatus are suitably
protected.
(iii) State the method adopted to guard lower voltage circuits in
transformers becoming accidentally charged above its/their normal
voltage.
(iv) State in case of transformers or switches or static condensers
involving the use of more than 2,275 litres of oil in one chamber, if
suitable oil soak pits are provided.
(v) Where 9,000 litres or more of oil is used in any one oil tank, has
provision been made for draining away or removal of oil which may leak
or escape from such tank(s)?
(vi) State if trenches inside sub-station containing cables are filled
with noninflammable material or completely covered with non-
inflammable slabs.
(vii) Are conductors and apparatus so arranged that they may be
made dead in sections for carrying out work thereon?
66. In case of metal sheathed electric supply lines, are the metal
sheaths connected with earth properly?
67. (i) Have the frame of every generator, stationary motor, and so far
as
practicable portable motor and metallic parts not intended as conductors
of all transformers and an other apparatus used for regulating or
controlling energy and all high voltage energy consuming apparatus
been earthed by two separate and distinct connections with earth?
(ii) Is the earth-wire free from any mechanical damage?
(iii) Have two separate and distinct connections with earth, each
having its own electrode, been provided for the earth neutral point?
(iv) Have the metal casings or’ metallic coverings containing or
protecting any electric supply line or apparatus been properly earthed
and so joined and connected across all junctions boxes as to make good
mechanical and electrical connections throughout their whole length?
68. Is the outdoor (except poletype) sub-station efficiently protected
by fencing not less than [1.8]1 metres in height?
69. (i) Where platform type construction is used for pole type
substation, has sufficient space for a man to stand on the platform been
provided?
(ii) Has hand-rail been provided and connected with earth (if metallic
and if sub-station has not been erected on wooden supports)?
70. Has suitable provision been made for immediate and automatic
discharge of every static condenser on disconnection of supply?
Overhead lines:
74. What is the minimum size of the conductors of overhead lines
used? State the type of conductors.
77. Are clearances above ground of the lowest conductor of overhead
lines, including services lines, as per this rule?
80. (i) On the basis of maximum sag, are verticle clearances where the
high or extra-high voltage line passes above or adjacent to any building
or part of a building as per this rule?
(ii) On the basis of maximum deflection due to wind pressure, are
horizontal clearances between the nearest conductor and any part of
such building as per this rule?
81. Where conductors forming parts of system at different voltages
are erected on the same supports, has adequate provision been made to
guard against danger to linemen and others from the lower voltage
system being charged above its normal working voltage by leakage from
or contact with the higher voltage system?
87. Where overhead lines cross or are in proximity to each other have
they been suitably protected to guard against possibility of their coming
in contact with each other.
88.(i) Has every guard wire, been properly earthed at each point at
which its electrical continuity is broken?
(ii) What is the type and size of guard wire?
90.(i) Are the metal supports of overhead lines and metallic fittings
attached thereto permanently and efficiently earthed?
(ii) Has each stay-wire (except in case where an insulator has been
placed in it at a height not less than 3 metres from the ground) been
similarly earthed?
91. (i) Has the overhead line been suitably protected with a device for
rendering the line electrically ]Harmless in case it breaks? Whit type of
device is used?
(ii) Whether anticlimbing devices have been provided for each of the
high voltage and extra high voltage supports?
92. (i) Has the owner of overhead lines adopted efficient means for
diverting to earth any electrical surges due to lightning in every overhead
line which is so exposed as to be liable to injury from lightning? What
type of means are used?
(ii) Has earthing lead from the lightning arrestors been connected to a
separate earth electrode?
93. Are unused overhead lines being maintained in a safe mechanical
condition?
Any other remarks.
Dated:…….. Inspecting Officer’s Signiture…………
Name…………
Designation…………..
File No…………..