Regulation 46, Indian Boiler Regulations, 1950: Hydraulic Teit
Indian Boiler Regulations, 1950 - Regulation 46
Text of regulation 46
Hydraulic Teit
46. Hydraulic Teit.—Each tube shall be tested at tho makers' works by hydraulic
pressure in accordance with the following table governing the relation between
the test pressure and the design pressure to which, the tube will be subjeoted in
service.
Deugn pretmur* lb/»q. iu.
Up to and including 500
Above fiOO up to »nd including 1000
Above 1000 . -
Hydrnuho test pressure Ib./sq. in.
minimum
1000
Twice the danign pressure
1000 above the design preaauro.
In all cases the tensile stress (S) on. the material when under these terti eh all
not exceed 10 tons per sq. in. as determined by tho formula :—
DP
S ~ —
2t
Whore D =* outside diameter of tubo in inches.
P = test pressure in Ions per sq. in.
t =• Nominal thk'knesN ot tube wall in inches.
SEAMLESS HALF-PER CENT. MOLYBDENUM STEEL BOILER AND'
SUPERHEATER TUBES EOR DESIGN STEAM TEMPERATURES
NOT EXCEEDING 950cr (51()°O)