Regulation 32, Indian Boiler Regulations, 1950: Special Iron for Screw Stays for Fireboxes and Combustion Chambers
Indian Boiler Regulations, 1950 - Regulation 32
Text of regulation 32
Special Iron for Screw Stays for Fireboxes and Combustion Chambers
32. Special Iron for Screw Stays for Fireboxes and Combustion Chambers.—I»
order that iron screw wi ays may be approved of the same size an would be required
for mild steel, the iron must withstand the following tebts:—
(a) Tensile Tests.- -The tensile breaking strength.shall not bo less than 211 ton*
per square inch, with an elongation of not less than 25 per cent, measured on the
Standard Test Piece B or 30 por cent, measured on the Standard Test Piece Bx.
(b) Bend Tests. —Tost pioces oither of tho bar as rolled, or turned down to 1
inch diameter, ^hall stand bending cold until the sides ate parallel and the space
between the two sides is not greater than tho diameter of the test pieoe,
(o) Number of Tensile Tests.—The bare us rollod shall bo placed in batohes of
twenfcv, nnd one tensile test shall be t aken from each batoh, If this is unsatisfactory
two other bars shall be selected for test, and should either of these fail tho batch
shall be rejected.
(d) Number of Bend Tests.—One ordinary bond tost shall bo taken from eaoh
batch, and a similar test piece from each batch shall be lightly and evenly nicked on
one side with a sharp cutting tool and bent back at this point through an anglo of
180 degrees by piossure or by a succession of light blows. The fraoture must be
clean, fibrous, free fiom slag or dirt or any coarse crystalline structure, If cither
of these is unsatisfactory, two other bars shall be selected for test, and should either
of these fail the batoh shall be rejected.
(e) In all cases the selection of tho test pieces shall be made by the Inspector
or the Inspecting Officer.