Regulation 209, Indian Boiler Regulations, 1950.: Compression of tulbe plates
Indian Boiler Regulations, 1950. - Regulation 209
Text of regulation 209
Compression of tulbe plates
209. Compression of tulbe plates.- (a) For fire-box or combustion chuinbu lube
plates which are subject to compression due to the pressure on the roof plate, the
maximum working pressure shall be :—
C x ( P - D ) x t
W.P. =. Eqn. (46)
LxP
t is the thickness of the tube plate in 32nds of an inch,
P is the pitch of the tubes in inches, rueasurod horizontally where the tubes are
. ohain pitohod, arid diagonally where the 1 ubos are zigzag pitched and the diagonal
pitch is less than the horizontal,
D is the internal diameter of the plain tubes in inches,
L is the internal length of the fire-box or combustion chamber in inohes measured
at top between tube plate and firehole plate or baok plate, or between tube platea
in doublo ended boilers with combustion chambers common to two opposite fur-
naces,
C = 875 for steel and 437-5 for copper.
Provided that the above formula shall not apply in the case of fire-boxes where
the girders do not rest on the tubo plate, or where the roof plate is stayed direct to
* tho outer shell or to girders supported by the shell.
(b) where girders rest on the side plutos or tlie roof plate is so formed that the
load is» carried both by side and end platos, in no case shall tho compressive stress on
the platos exoeed 14,000 Iba. per square inch for steel of 7,000 Tbs. per square inch
for copper.
Previous and next