Regulation 200, Indian Boiler Regulations, 1950.: Flat plate margins
Indian Boiler Regulations, 1950. - Regulation 200
Text of regulation 200
Flat plate margins
200. Flat plate margins.—The amount of support in relief of stays which may-
be credited to the sides of shells, furnanrcs, uptakes, fireholes and foundation rings
to which flat plates are attached shall noi exceed that found by the following
formula:—
W i d t h o f m a r g i n i n i n c h e s = - — = L = ^ . . . . . E o n . ( 3 7 )
* VW.?.
t •= Thiokness in 32nds of an inch
W.P. ™= Working pressure in lb per sq inch
C = 3 • 47 for plates exposed to flame
C = 3-70 for plates not exposed to flame.
Where the platos are flanged the margin shall be measured from the oommen-
oement. of curvature or from a line 2$- times the tlj iokness of the plate distant from the
side of the flange next to the inner radius of the corner whichever is tbe less. In
othsr easeH, the margin shall be measured from the oentre line of rivets in th&
nearest row of the seam by which the flat plato is attached.
Doubling plates shall cover tho area supported between the stays and extend
beyond the stays so that the oontre of tho rivets securing the doubling plate to
the end plate shall be at least half tho distance from the outermost stays to the noareat
substantial point of support.
Where flat end plates are flanged for connection to the shell, the inside radius
of flanging shall be not less than 1 • 75 times the plate thickness with a minimum of
1J inches.
8*0. 8] THE GAZETTE OF INDIA EXTBAOEDINA#T| " 667