Regulation 188, Indian Boiler Regulations, 1950.: Complete hemisphere without stays or other support made of one or more plates and subjeot to internal pressure
Indian Boiler Regulations, 1950. - Regulation 188
Text of regulation 188
Complete hemisphere without stays or other support made of one or more plates and subjeot to internal pressure
188. Complete hemisphere without stays or other support made of one or more
plates and subjeot to internal pressure.—The maximum working pressuw shall be
determined by the following formula :—
( t - 2 ) x S x J
W.P. =- Eqn. (23)
OxB
W.P. ie the working pressure in lbs. per square inch,
t le the thiokness of the end platea in 32nds of inoh,
S is the minimum tensile breaking strength of the end plates in tons per square
taoh, or whatever strength is allowed for them,
J is the least percentage of strength of the riveted joints of the plates forming
the hemisphere or seouring it to the cylindrical shell,
R ia the inner radius of ourvature in inohes,
C for single riveting is 3 -3,
C for double riveting is 2-9,
0 for treble riveting is 2-83.
Previous and next
Questions people ask
Is regulation 188 of Indian Boiler Regulations, 1950. still in force?
No repeal of Indian Boiler Regulations, 1950. is recorded.