LawGrids logoLAWGRIDS.ORG

Regulation 46, Indian Boiler Regulations, 1950.: Hydraulic Teit

Indian Boiler Regulations, 1950. - Regulation 46

Text of regulation 46

Hydraulic Teit

46. Hydraulic Teit.—Each tube shall be tested at tho makers' works by hydraulic pressure in accordance with the following table governing the relation between the test pressure and the design pressure to which, the tube will be subjeoted in service. Deugn pretmur* lb/»q. iu. Up to and including 500 Above fiOO up to »nd including 1000 Above 1000 . - Hydrnuho test pressure Ib./sq. in. minimum 1000 Twice the danign pressure 1000 above the design preaauro. In all cases the tensile stress (S) on. the material when under these terti eh all not exceed 10 tons per sq. in. as determined by tho formula :— DP S ~ — 2t Whore D =* outside diameter of tubo in inches. P = test pressure in Ions per sq. in. t =• Nominal thk'knesN ot tube wall in inches. SEAMLESS HALF-PER CENT. MOLYBDENUM STEEL BOILER AND' SUPERHEATER TUBES EOR DESIGN STEAM TEMPERATURES NOT EXCEEDING 950cr (51()°O)

Previous and next

All provisions of Indian Boiler Regulations, 1950.

Questions people ask

Is regulation 46 of Indian Boiler Regulations, 1950. still in force?

No repeal of Indian Boiler Regulations, 1950. is recorded.