Bend. Testa

19. Bend. Testa.—(a) Cold Bends.—Test pieces shall bo sheared lengthwise or crosswise from plates or bnrs, and shall not be less than 1 | inches wide, but for small bars the whole soetion may be used. For rivet bars bend tests aro Hot required, (b) In all cold bend tests, on samples 0" 5 inch in thickness and above., tho rough edge or arris caused by shearing may be removed by filing or grinding, and samples 1 inch in thiokness and above, may have the edges maohinod, but the test pieces shall receive no other preparation. The test pieoos shall not be annoaled unless the material from which they are out is similarly annealed in which case tho test piece shall be Similarly and simultaneously treated with tho material boforo testing. (o) For oold bend tests the test pieoe shall withstand, without fracture, being doubled over until tho internal radius is equal to 1£ times the thickness of the test pieoe and the sides are parallel. (d) For small sectional material these bond tests nmy be made from the flatten- ed bar. (e) Bond tests may be made either by pressure or by blows.

Previous and next

All provisions of Indian Boiler Regulations, 1950.

Questions people ask

Is regulation 19 of Indian Boiler Regulations, 1950. still in force?

No repeal of Indian Boiler Regulations, 1950. is recorded.