Form Ill, This regulation repealed as on 08.06.2023-- Central Electricity Authority (Measures relating to Safety & Electric Supply) Regulations, 2010: FORM Ill
This regulation repealed as on 08.06.2023-- Central Electricity Authority (Measures relating to Safety & Electric Supply) Regulations, 2010 - Form Ill
Text of form Ill
FORM Ill
FORM Ill
( Installations of voltage exceeding 650V )
Report No. ----- Date oflnspection
Date of Last inspection-------,----
SI. Regulation
No. Nos
1. Regulation-3
2. · Regu]ation-
12
Requirements Report.
'
Is the register of the . designated persons Yes/No
properly made and kept up to date duly
attested? ..
(i) Is/Are there. any visible sigh(s) of Yes/No
overloading in respect of any apparatus?
(ii) Whether any unauthorised temporary Yes/No
installation exist?
(iii) Whether the motors and controlling Yes/No
equipment are being over hauled
periodically and record kept of the same in
a register?
(iv) Whether the transformer oil samples are Yes/No
being tested periodically and results
recorded in a register?
(v) Whether suitable lightning arrestors have Yes/No
been provided near the transformers for
protection against lightning?
(vi) Whether earth resistance is being Yes/No
measured periodically and results recorded
in a register?
(vii) Any other defect or condition which may Yes/No
be a source of danger. If Yes· please
explain?
(viii) Whether operation and maintenance Yes/No
data has been clarified, categorized and
computerized for . prompt and easy
retrieval?
(ix) Whether predictive maintenance is. being Yes/No
performed .· for installation of voltage
exceeding 650V?
(x) Whether residual life assessment and life Yes/No
extension progrannnes are being
undertaken for installations or equipment
of voltage exceeding 650V (applicable for
installations or equipment more than } 5
years old)?
(xi) Whether all required type and routine tests at Yes/No
.factory·done for equipments. Deficiencies and
Discrepancies in above test report and results,
if any, shall be reported?
(xii) Are there deficiencies in . construction with yes/No
'----'--------'--------
351
352
- ---- ------- -
3.
4.
5.
6.
Regulation-
13
Regulation-
14
Regulation-
15"
.Regulation-
16
THEGAZETTEOFIND~:EXTRAORDmARY
reference to Indian Standard requirements.
Please soecify. ·
Give report on condition of service lines,
cables; wires, apparatus and such other fittings .
placed by the supplier or owner of the
premises. If not satisfactorv give details.
Whether suitable cut-outs provided by the
supplier at the consumer's premises .are within
enclosed fire proof receptacle?
(i) Whether switches are · provided on live
conductors?.
(ii) Whether indication of a permanent nature
is provided. as per Regulation so as to
distinguish neutral conductor from the live
conductor?.
(iii) Whether a direct line is provided on the
neutral in the case of single phase double
oole iron clad switches instead of fuse ?
(i) Whether earthed terminal is provided by
the supplier?.
[PART III-SEC. 4]
Satisfactory/Not
Satisfactory
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
.
(ii) General visible condition of the earthing S~tisfactory/Not
arrangement. Satisfactory !-c,---t---,--,----1---cc,---~~----,---~-.,-~,---+---=----'-----,'
7. Regulation- (i) Are bare conductors in building Yes/No
8.
9.
10.
11.
12.
17 inaccessible?
Regulation-
18
Regulation-
19
Regulation-
21
Regulation-
22
Regulation-
24
(ii) Whether readily accessible switches have
been orovided for rendering them dead?
Whether "Danger Notice" in Hindi and the
local language of the district and of a design as
per relevant Indian · Standard is affixed
Yes/No
Yes/No
permanently in conspicuous position?. ·
(i) Whether the practice cif working on live Yes/No
lines and apparatus is adopted ? If so, have
the safety measure been adopted as per
Schedule-III?
(ii) Whether insulating floor or mats
conforming to IS-15652:2006 have been
provided?
14. · (iii) Whether identification of panel has
been provided on the front and the rear of
the panel?
Whether flexible cables used for portable or
transportable equipment covered under tb.e
Regulation, are heavily insulated and
adeQuately protected from mechanical injury? ..
State · the condition of metallic coverings
· orovided for various conductors.
Whether the circuits or apparatus intended for
operating at differen~ voltage(s) are
distinguishable by means of indication(s) of
permanent nature?.
Yes/No
Yes/No
Yes/No
Satisfactory/Not
Satisfactory
Yes/No
f-
·,
I
,.
•
•
J
['ll'l lll-= 4]
13. Regulation-
26
14. Regulation-
27
15. Regulation-
28
.
.
16. Regulation~
34
17. Regulationc
35
3747 Gl/10---45
Whether all circuits and apparatus are so Yes/No
arranged that there is no danger of any part(s)
becoming accidentally charged to any voltage
beyond the limfts ·of voltage for which it/they
is/are intended ?
(i) In the case of generating stations and Yes/No
enclosed sub stations, whether fireabuckets
filled with clean dry sand have been
conspicuously marked and kept in
convenient situations in addition to fire
extinguishers suitable for dealing with
electric fires ?
' · (ii) Whether First Aid Boxes :or cupboards Y es!N9
conspicuously markecl and properly
equipped are provided and maintained?.
(iii) Is adequate staff trained· in First. 'Aid Yes/No
Treatment and fire fighting?
(i) Whether instructions in English or Hindi Yes/No
and -the local language of the district and.
' where Hindi is the local langua_ge, in
English and Hindi, for the resuscitation of
persons suffering .from electric shock have
been affixed in a "conspicuous place" ? .
(ii) Are, the designated persons able to apply Yes/No
instructions for resuscitation of persons -
suffering from electric shock ?
Leakage on premises:.
State insulation resistance between conductors ' ----- M Ohms
. and earth in Mega Ohms. ..____
(i) · Whether a suitable linked switch, or circuit Yes/No
breaker, or emergency tripping device is
placed near the point of commencement of
supply. so as to be readily accessible and
capable of being easily operated to
completely isolate the supply? ..
. (ii) Whetheri suitable linked switch or a circuit Yes/No
breaker to carry and break the full load
current on the secondary side of a
transformer? ..
(iii) Whether every distinct circuit is .protected Yes/No
against excess electricity by means of a
suitable circuit breaker or cut-out?
(iv) Whether linked switch or circuit breaker or -Yes/No
· emergency tripping device is provided
near the motor or other apparatus at
voltage exceeding 650V but not exceeding Yes/No
33kV for controlling supply to>the motor
or apparatus?
(v) .Whether adequate precautions are taken to Ye~/No
ensure that no live parts are so exposed as
to cause danger? -
. 353
.
354
.I
!
18.. -Regulation~
..
19.
20.
21.
31
Regulation-
44
Regulation-
45
Regulaeion-
48
THE GAZETTE OF INDIA : EXTRAORDINAR.Y [PART m.-:sEC. 4]
(i) Whether clear space of 100 cm is provided. Yes/No
in front of the main switchboard?.
(ii) Whether the space behind the switchboard Yes/No
exceeds 75 cm in width or is less than 20
cm?.
(iii) . In case the clear space behind the Yes/No
switchboard exceeds 7 5 cm. State whether
a passage way from either end of the
switchboard to a height of 1.80 meters is
provided.
(i) Whether all conductors and apparatus Yes/No
including live parts thereof are
inaccessible?
(ii) Whether all windings of motors or other Yes/No
apparatus are suitably protected? .
(iii) State in case of transformers or reactors or Yes/No
switches or static condensers involving the
use of more than 2,000 litres of oil in one
chamber, if suitable oil soak pits are
provided?
(iv) Where 9,000 litres or more of oil is used in Yes/No
any one oil tank, has provision, been made
for draining away or removal of oil which
may leak or escape from such tank(s)?
(v) Whether trenches inside sub-station Yes/No
containing cables 11re filled with non
inflanunable material or completely
covered with non- inflammable slabs?
(vi) Are conductors and apparatus so arranged Yes/No
that they. may be made dead in sections
for carrying out work thereon?
Whether protections and interlocks have been Yes/No
provided? If not, give details.
(i) Have the frames of every generator, Yes/No
stationary motor, and so far as practicable
portable motor and metallic parts not
intended as conductors of all transformers
and any other apparatus used for
regulating or controlling electricity and all
electricity consumin~ apparatus at voltage
exceeding 650V but not exceeding 33kV
been earthed by two separate and distinct
connections with earth ?
(ii) Is the earth wire free from any mechanical Yes/Ne
damage?
(iii) Has the neutral point at the transformer and Yes/No
generator been earthed by two separate
and distinct connections with earth?
'(iv) Have the metal casings or metallic Yes/No
coverings containing or protecting any
electric supply line or apparatus been
(
p
j
•
'
•.
'
•
J
[ '11'1 III-1s11J;s 4 l
.
22. · Regulation-
49
.
.
properly earthed and so joined and
- connected across all junction boxes as to
make good mechanical ana electrical
connections throughout their whole
length?
(v) Whether earthing has been properly Yes/No
executed and has been tested. If yes, give -------Ohms
value of earth resistance .
Is the outdoor ( except pole type) sub-station Yes/No
efficiently protected by fencing not less than
. L 8 metres in height?
23 Regulation- (i) Where platform type .construction is used Yes/No
50 for pole type sub-station, has sufficient.
space for a man to stand on the platform
been provided?
(ii) Has hand-rail been provided and connected Yes/No
wjth earth (if metallic and if sub-station
has not been erected on wooden supports
and wooden blateform)?
24. Regulation-
51
Has suitable provision been made for Yes/No
immediate and automatic or manual discharge
of every static condenser on disconnl)ction- of
suooly?
25
l
Overhead
Lines (i) What is the minimum size of the conductors
of overhead lines used ? State the type of
conductors.
Size of
Conductor ---
.
(ii) Whether clearances above ground of the
lowest conductor of overhead lines are as
per regulation 58?
(iii) On the basis of maximum sag, Whether
vertical clearances where the line of
voltage exceeding 650V passes above or
adjacent to any building or part of a
building are as per regulation 61?
(iv) On the basis of maximum deflection due
to wind pressure, whether horizontal
clearances between the nearest conductor
and any part of such building are as per
regulation 61?
(v) Where conductors forming parts of system
at different voltages are erected on the
same supports, whether adequate provision
· has been made as per regulation 62 to
guard agilinst danger to linemen and others
from the lower voltage system being
_charged above its normal working voltage
by leakage from or contact with the higher
voltage system?
(vi) Where overhead lines cross or are in
proximity to each other whether they have
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
355·
.
356
···_
..
Date:·
nre GAZETTE OF INDIA : EXTRAORDINARY [PART m~ssc. 4]
. been suitably protected to guard against
possibility of their coming in contact with
each other as per regulation 69?
I
(vii) Has every guard wire been properly Yes/No
earthed as per regulation 70 at each point
at which its electrical continuity is
broken?
(viii)(a) Whether metal supports of overhead Yes/No
lines _and metallic fittings attached thereto
are permanently earthed as per regulation
72?
(b) Has each stay-wire ( except in case Yes/No
where an insulator has been placed in it at
a height not less than 3 meters from the
ground) been earthed as per .regulation
72?
(ix)(a) Whether overhead line is suitably Yes/No
protected with a device for rendering the
line ,electrically harmless in case it breaks
as,perregulation 73?
(b) Whether anti-climbing devices have Yes/No
been provided at each support as per
rc;gulation 73?
(~):(a);Has,the owner of overhead lines adopted Yes/No
efficient means for diverting to earth any
· electrical surges due to lightning in every
overhead line which is so exposed as to be
liable to injury from lightning • as 'per
regulation 7 4? 1
(b} Whether earth lead from the lightning Yes/No
arrestors, is connected to a separate earth
electrode as per regulation 74? ·
(xi) Whether unused overhead lines are Yes/No
maintained in a safe mechanical condition
as perregulation 75?
(xii) Whether statutory clearances from Yes/No
Authorities i.e. . Forest
Department/Railways/ PTCC/Defence
(AHQ)/Civil Aviation have been taken as
per Indian standard. If yes, enclose copies
of .the same.
(xii) Any.other remarks. .
Signature of the Inspecting· Officer/
Name ________ _
Designation ______ _
File No. _______ _
'
Copy:forwarded to Chief Electrical Inspector for .................... .
---- - - -=-·--------~-- ----
f
r
' ,,
•
['11'1 III-~ 4]
I.
2.
3.
4.
5,
Sehedule~v
Form for obtaining results during inspection by supplier.ateach'suppiyc11,ointto·
consumer
[See sub-regulation (2) ofregullitionc,(31)]
Name and address of the consumer
Details of installation
Short circuit fault level of the installation
Date-of conunissioning of installation(iµ case of additional supply or
reconnection)
Results of tests conducted:
357
SI Equipment Test Conducted TestResults ·aemarks
No
1 · Linked Switch
with fuse( s)
1 a Isolator
2 Circuit
Breaker
SI.No. ------
Circuit
I3reaker
Control
Circuits
( i)Mechanical operation
(ii) Rating of fuse
(iii) Contact ofblades
i) Mechanical,operation
ii) Remote operation
iii) Local operation
iv) Measurement of contact
resistance
v) Interlocking with' earth ,switch
vi) Interlocking ,with CB
vii) IR V aluys
Open condition
Closed condition
(1) Rating ofCircuitBreaker
(a) Type
(b) Voltage
(c) Normal Current
( d) Rupturing capacity
(2) IR Values
Open condition
Close condition
(3) Contact Resistance :
( 4) Mechanical operation:
(5) Remote opera1ion:
( 6) .Local operation:
(7) Interlocking with Jsolator:
(8) Interlocking with earth switch
(9) Alarm and Trip for
OTI/WTI/Buchholz/PRV
(10) Earth FaultRelay:
(11) Over current Relav :
·Smooth/troublesome
. Amp.
Ftill/Partial
OK/not:OK
0K/notOK
OK/nobOK.
--~-----------micro Ohm
OK/not,QK
OK/not.OK
------ -----· -M ,Ohm
Ph~Ph Ph~E
----- ---------------------
-----------· ·-- kV
------- Amps ·
---- ---KA·
--------------M Ohm
Ph-Ph Ph.E ·
. hm/ -------------micro o . ,
• Instant.smooth/time. ·
gap{ Sec:)
0K/not,0K
0K/not•0K
0K/not0K
OK/not0K
OK/not·0K
OK/riot,QK
0K/riot0K
358
3 Transformer
SI. No.----
.
4 DGSet
SI. Nos. for
1. Alternator:
2. Engine:
5 Cables
Size: Sq. mm
6 Earthing;
TilE <;;AZETTE OF INDIA : EXTRAORDINARY [l'ART III-SEC. 4]
(12) Under Voltage Relay:
(13) SF6 pressure alarm and trip
operation test
(A) Insulation Resistance Values:
1. HTtoLT:
2. HT to Earth:
3. LT to Earth:
(B) Break down Voltage Test
Oil Sample-I(Toj,)
Oil Sample - II (Bottom)
(C) Vector Group Test:
(D) Polarity Tests:
(E) Magnetizing Balance:
(F) Tan Delta Test ( as per capacity)
(G) Oil level in conservator Tank:
(H) Oil level in breather cup:
(I) OTI/WTI settings :
( J) OTI/Vy'TI alarm and trip
operation
(K) Operation of Buchholz relay :
(L) Operation of PRY
(M) Oil leakage
(N) Interlock of door switch for dry
transformer
(0) Clearances for
Side clearance :
Between two Transformers:(P) Body
earth resistance
Neutral earth resistance
(A) Interlocking with other Supply
Sources:
(B) Body-earth resistance
Neutral earth resistance
.
(A) Insulation.Resistance Values: · ·
1. Ph-Ph:
2. ~h - Earth :
3. Ph - Earth + other Ph :
(B) Bending Radius;
.
B)
A) Metal and Size of
Earth Strips:
Type of Earthings: .
( 1) Plate Earthing:
(2) Pipe Earthing:
(3) Counter poise Earthing
(C) Values of Earth resistances of
OK/not OK
·oKJnotOK
----Mohm
--------------M ohm
------··· ----M ohm
--···-----·•--kV
kV
OK/not OK
OK/not OK
OK/not OK
OK/not OK
OK/not OK
OK/not OK
NT---- 0c NT----0c
OK/not OK
. OK/notOK
OK/not OK
OK/not OK
OK/not OK
---------Cms
----------Meters
---------· Ohm' ,
Ni-·•Ohm
. N2---0hm
OK/not OK
---Ohm
N,~--Ohm
N2---0hm
--------- M Ohm
·---------M Ohm
---------M Ohm
OK/not OK
Cu/ Al/GI --- Sq.
Yes/No
Yes/No
Yes/No
mm
N 1 ----ohm N2 ----ohm
•
' .
'
'
•
•
•
\
[ <!T'1 III-~ 4 l
359
earth electrodes for (R) ---ohm (Y) ---ohm
(1) Reactor Neutral: (B)----ohm
(2) LAs: ohm
ohm
(3). Structure:
(4) Frames/Bodies of ohm
Equipment:
(5) Motors:
7 Potential (i) Ratio test OK:/notOK
Transformer (ii) Polarity test OK/not OK
(iii) BDVofoil kV
-
• (iv) IR test (R) P-E-------M Ohm
(Y) P-E-------M Ohm
8. -Current (i)
(B) P~E-------M Ohm
Ratio test OK/not OK
Transformer (ii) Po lantytest OK/not OK
(iii) BDVofoil -- -------kV
(iv) IR test (R) P-E-------M Ohm
(Y) P-E-------M Ohm
9. Transmission (i)
(B) P-E-~-----M Ohm
Physical condition of OK/not OK
line conductor/tower
. (ii) Check of tower accessories OK/not OK
(iii) .Tower footing resistance Ohm
(iv) .Conductor ccmtinuity test QK/notOK
(v) Check of ground clearance OK/not OK
(vi) Check of electrical clearance OK/not OK
along the route
General Observations : .
.
SI.No. Item Observations
l. Check of required phase to phase, phase to ground and -
.sectional clearance.
2. Check of equipment lay out and over all installation
details.
.
3. Test of resistance of earth mat or earth electrodes as
applicable.
4. Check.of consumer's pre-commissioning test reports
-of individual equipment.
-
.·
5. Check of manufacturer's routine/type test reports of
individual equipment.
'6. Whether Inspector's approval if applicable is obtained?
r· - -· ·-· ~ - ------ ----
360
7.
8.
TIIE GAZETTE OF INDIA : EXTRAORDINARY [PART III-SEC. 4]
Whether owner) s self certification about compliance
with The Regulations is obtained?
,·
Generalobservation,and views (specific deviation from
, the requirements of the Regulations shall be clearly
brought out).
Name, Signature and Seal of the Authority
Schedule-VI
Form for notice in respect of failure of supply
[S.ee sub•regulation (3) of regulation (39)]· ·
(1) Nameandaddress of the supplier
(2) Date,andtime of failure of supply
(3} Arem,•affected due to failure
(4) ·· Causes ofTailure
(5) Probable.time forrestoration of supply
(6) Additionalinformation, if any
Date:
Place:
Time:
(Name, Signature, Designation
and Sealof Authoity)
.l
·~-----------------~~--~- -·-·--
J
Schedule-Vil
Minimum safety working clearances where electricity at voltage exceeding 650 V
is supplied, converted, transformed or used
(See suh•regulation (2)(iii) of regulati!)n (44))
Highest System Voltage (kV)
12
36
72.5
}45
245
420
800
Safety Working Clearance (Metres)
2.6
2.8
3.1
3.7
4.3
6.4
10.3
( 1) The above values are valid for altitude not exceeding 1000 m. A correction
factor of 1.25 per cent per 100 m is to be applied for increasing the clearance for
altitude more than 1000 m and upto 3000 m; ·
(2) The above safety working clearances are based on an insulation height of
2.44 m which is the height of lowest point on the insulator, wheieit meets the
earthed metal, from the ground;
(3) "Safety Working Clearance" is the minimum clearance to be maintained in
air between the live part of the equipment on one hand and earth or another piece
of equipment or conductor on which it is necessary to carry out the work, on the
· other;
( 4) The "Highest System Voltage" is defined as the highest rms phase to phase
voltage which occurs under normal operating conditions at any time and at any
point of the system. It excludes voltage transients (such as those due to system
switching) and temporary · voltage variations due to abnormal system conditions
(such as those due to fault conditions or the sudden disconnection oflarge loads).
3747 Gl/10-46
361
362 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III--SEC. 4]
Schedule-VIII
Minimum safety clearances to be maintained for bare conductors or live parts of
any apparatus.in out-door sub-stations, excluding overhead lines ofHVDC
istallations
[See sub•regulation (5) of regulation (44)]
.
S.No. DC Voltage (kV) Pole to Earth. Clearance Ground Clearance
(Metres) (Metres)
.
I. lOOkV 1.17 4.55
2. 200kV 1.80 5.65
3. 300kV 2.45 6.75
. .
4. 400 kV. 3.04 8.00
5. 500kV 3.65 9.00 .
6. 600kV 3.98 JO.I
7. 800kV 5.3 I 1.2
(1) The above ground clearances are not applicable to equipment that are housed
within fence or a building and where access is prevented under er\eigised condition
through a suitable safety interlocking scheme;
(2) The above pole to earth c.learances · are · for conductor-structure electrode
configuration using gap factor k equal to 1.35.
..r,.·
(3) It is recognised that within a substation many different types . of electrode
configurations shall be there with different values ofk, therefore, the above clearance
shall be modified based upon the values of gap factor for a particular electrode
configuration subjected to the minimum ground clearance.
(4) Clearance shaJl be provided for electrical apparatus so that sufficient space is
available for easy operation and maintenance without any hazard to the operating and
maintenance personnel working near the equipment_ and for ensuring adequate
ventilation.
•
•
•
,.
[
[ "ll'l IIl-l§!U,l" 4 l
Schedule-IX
Form for reporting failure of Transformers or Reactors of rating
20 MV A/MVAR and above
[See sub-regulation (8) of regulation (46)]
(1) Type of Equipment (Transformer or Reactor)
(2) Capacity (MV A/MV AR)
(3) Location (Address) .
( 4) Owner and address of owner
(5) Date of failure
{ 6) Year of manufacture
(7) Date ofinstallation
(8) Make
(9) Reasons for failure
( 10) Measures being taken to avoid recurrence of failure
Date:
(Signature and name of Manager/Executive
Engineer of the installation)
363
-~-'=.::.-.
364 TI-IE GAZETTE OF INDIA : EXTRAORDINARY , [PART .UI~SEC. 4]
'Schedille-X
Ground, Vertical and Horizontal clearances
[See sub-regulation (6) of regulation 58, sub-regulation {SJ Qf rsegulation (60) and
· sub-regulation (5) o!.regulation .(;1] • ·
GCL
,. • .. .. • •• _. • • • • .. , M11xm.
VCL
Daflectlcl'i
"l
'~
I •• ..
I • .. •
VC.L
GCL: Cleai·ai1cH as pel' Regulation 59
VCL: C'lea1·ances as per.Regulation 6(1.,t 61.
HCL: C'lea1:n11ces as pel' Regulation 60 ... ~ 61
!! Qffld1atar
j J,atlfll!l~i
. . ! . .
MCL, • ·--=-.. .. .. .
GCL
'
' t
D
Previous and next
Questions people ask
Is form Ill of This regulation repealed as on 08.06.2023-- Central Electricity Authority (Measures relating to Safety & Electric Supply) Regulations, 2010 still in force?
No repeal of This regulation repealed as on 08.06.2023-- Central Electricity Authority (Measures relating to Safety & Electric Supply) Regulations, 2010 is recorded.