Form II, This regulation repealed as on 08.06.2023-- Central Electricity Authority (Measures relating to Safety & Electric Supply) Regulations, 2010: FORM II
This regulation repealed as on 08.06.2023-- Central Electricity Authority (Measures relating to Safety & Electric Supply) Regulations, 2010 - Form II
Text of form II
FORM II
FORM II
(Installations of voltage level more than 250V np to and including 650V)
Report No. ___ ~--- Date of Inspection ________ _
Date oflast Inspection---~--
1. Consumer No. ----------
2. Voltage and system of supply:
(i) Volts _____ (,ii) No. of Phases (iii) AC/DC
3. Name of the consumer or owner -------------
4. Address of the consumer or owner -------~-----
5. Location of the premises---------'---~----
6. Particulars of the installations
(a) Motors:
I Make I No. I H.P. I Amps. I Voltage
(i) ________________ ~------
(ii) ----------------------------
(b), Other equipment (complete details to be furnished):
(i) (ii) _______________________ _
Total connected load h.p./KV A·
( c ) Generators details i.e. Make, S. No, KV A rating and Voltage:
(i) ---------------------------
(ii) ___________ ~-------------
General condition of the installation:
SI. Regulation Requirements Report
No. Nos.
7. Regulation-3 Is the register of designated persons properly Yes/No
. made and kept up to date duly attested ?
8. Regulation- (i) Is/Are there any visible sign(s) of . Yes/No
12 overloading in respect of any apparatus
wiring?
(ii) Whether any unauthorised temporary Yes/No
installation exist?.
(iii) Are the electric supply lines and apparatus Yes/No
so installed, protected, worked and
- maintained as to prevent danger ? -
(iv) Any other general remarks.
9. Regulation- Give report_ on condition of service lines, Sat'
13 cables, wires, apparatus and such other fittings s
placed by the supplier or owner of the
premises. If not satisfactory give details .
.
347
.
.
.
.
'
.
- -~~--- -~----c-- ----
348 THE GAZETTE OF IND)t\ : EXTRAORDINARY [PART III-SEC. 4]
10. Regulation- Whether suitable cut-outs provided by the Yes/No
14 supplier at the consumer's premises are within
.
enclosed fire oroofreceotacle?
. 11. Regulation- (i) Whether switches are provided on live Yes/No
15 conductors?.
(ii) Whether indication of a permanent nature Yes/No
is provided as per Regulation so as to
distinguish neutral conductor from the Ii ve '
conductor?.
(iii) Whether a direct line is provided on the Yes/No
neutral in the case of single phase double
pole iron clad switches instead of fuse ?
12. Regulation- (i) Whether earthed terminal is provided by Yes/No
.
16 the supplier?.
(ii) General visible condition of the earthing Satisfactory/Not
arrangement. Satisfactory
13. Regulation- (i) Are bare conductors in building Yes/No
17 inaccessible?
.
(ii) Whether readily accessible switches have Yes/No
. been orovided for rendering them dead?
14. Regulation- Whether "Danger Notice" in· Hindi and the Yes/No
18 local language of the district and of a design as
relevant Indian Standard is affixed
.
per
permanently in conspicuous position?.
15. Regulation- (i) Whether insulating floor or mats conforming Yes/No
19 to IS-15652:2006 have been provided?
(ii) Whether identification of panel has been· Yes/No
provided on the front and the rear of the
panel?
16. Regulation- Whether flexible cables used for portable or Yes/No
21 transportable equipment covered under the ·
Regulation, are heavily insulated and
adequately protected from mechanical injury? .
17. Regulation- State the condition of metallic . coverings Satisfactory/Not
22 provided for various conductors. Satisfactory
18. Regulation- Whether the. circuits or apparatus 'intended .for Yes/No
24 operating at different • voltage(s) are
distinguishable by means of indication(s) of
permanent nature? .
.
19. Regulation- Whether all circuits and apparatus are so Yes/No
26 arranged that there is no danger of any part(s)
becoming accidentally charged to any voltage
beyond the limits of voltage for which it/they . .
is/are intended? -
20. Regulation- (i) In the case of generating stations, whether Yes/No
27 fire-buckets filled with clean dry sand
have been conspicuously marked and kept
in convenient situations in addition to fire-
extinguishers suitable for dealing with.
electric fires ?
.
['11'1Ill-<!!U64]
21.
22.
23.
.
24.
25.
Regulation-
28
Regulation-
34
Regulation-
35
Regulation-
37
Regulation- .
41
(ii) Whether First Aid Boxes or cupboards
conspicuously marked and · properly
equipped are provided and maintained?.
(ii_i) Is adequate staff trained in First Aid
Treatment and fire fi<>hting?
(i) Whether instructions in English or Hindi
and the local language of the dis.trict and
where Hindi is the local language; in
English and Hindi, for the resuscitation of
persons suffering from electric shock have
been affixed in a "conspicuous place" ? .
(ii) Arn the designated persons able to apply
instructions for resuscitation of persons
suffering from electric shock ?
Leakage on premises:
State insulation resistance between conductors
and earth in Mega Ohms.
(i) Whether a suitable linked switch, or circuit
breaker 1s placed near the point of
commencement of supply so as to be
readily accessible and capable of being
easily operated to completely isolate the
supply?
(ii) Whether every distinct circuit is protected
against excess electricity by means of a
suitable circuit breaker or cut-out?
Yes/No
Yes/No
Yes/No
Yes/No
-----M Ohms
Yes/No
Yes/No
(iii) Whether suitable linked switch or circuit
breaker is provided near each · motor or , .
apparatus for controlling supply to the
motor or apparatus?.
Yes/No
(iv) Whether adequate precautions are taken to·
ensure that no live parts are so exposed as
' to cause danger?.
(i) Whether clear space of I 00 cm is provided
in front of the main switchboard?.
(ii) Whether the space behind the switchboard
exceeds 75 cm in width or is less than 20
cm?.
(iii) In case the clear space behind the
switchboard exceeds 75 cni. state whether
a passage way from either end of the
switchboard to a height of 1.80 metres is
provided.
(i) Has the neutral point at the transfortner and
generator been earthed by two separate
and distincrt:onnections with earth?
(ii) Have the frame of every generator,
stationary'motor and so far as practicable
portable motor and the metallic parts (not
intended as conductors) of all transformers
and any other apparatus used for
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
349
350
26. Regulation-
45
27.. Overhead
Lines
Date:
. 'THE GAZETTE OF INDIA : EXTRAORDINARY [PART Ill-,-Soc. 4]
regulating or controlling electricity and all
apparatus consuming electricity at voltage
exceeding 250V but not exceeding 650V
been earthed by two separate and distinct
connections with earth ?
(iii) Have the metal casings or metallic Yes/No
covenngs containing or protecting any
electric supply line or apparatus been
properly earthed and so joined and
connected across all junction boxes as to
make good mechanical and electrical
connection?
(iv) Whether the consumer's earth-electrode is Yes/No
properly executed and has been tested. If
· yes, give value of earth resistance?. ------- Ohms.
(v) Is the earth wire free from any mechanical Yes/No
damage?
Have the protections and interlocks for the Yes/No
generating units been provided. If not, give
details?.
(i) State if the consumer has any overhead Yes/No
lines.
(ii) Does the overhead line near the premises Yes/No
of consumer meets the requirement of
regulations 58, 60 and 61? If not, give
details. ·
(iii) Is guarding provided for overhead lines Yes/No
at road crossings?
(iv) Any other remarks.
Signature of the Inspecting Officer
Name -------~-
Designation _______ .
File No. --------
.
Copy forwarded to Chief Electrical lli.spector for .................... .
l
,
•
'
•
1
·.f
[ 'Ill'! ]Il-1g1l;s 4]