Regulation 11, Central Electricity Authority (Grid Standards) Regulations, 2010: Categorisation of grid incidents and grid disturbance based on severity of trippings
Central Electricity Authority (Grid Standards) Regulations, 2010 - Regulation 11
Text of regulation 11
Categorisation of grid incidents and grid disturbance based on severity of trippings
11. Categorisation of grid incidents and grid disturbance based on severity
of trippings.- The categorisation of grid incidents and grid disturbances shall be as
follows:-
(1) Categorisation of grid incidents in increasing order of severity,-
Category GI-1 - Tripping of one or more power system elements of the
grid like a generator, transmission line, transformer, shunt
reactor, series capacitor and Static VAR Compensator,
which requires re-scheduling of generation or load,
without total loss of supply at a sub-station or loss of
integrity of the grid at 220 kV (132 kV in the case of
North-Eastern Region);
Category GI-2 - Tripping of one or more power system elements of the
grid like a generator, transmission line, transformer, shunt
reactor, series capacitor and Static VAR Compensator,
which requires re-scheduling of generation or load,
without total loss of supply at a sub-station or loss of
integrity of the grid at 400 kV and above (220 kV and
above in the case of North-Eastern Region).
(2) Categorisation of grid disturbance in increasing order of severity,-
Page 11 of 19
Category GD-1 - When less than ten per cent. of the antecedent
generation or load in a regional grid is lost;
Category GD-2 - When ten per cent. to less than twenty percent of the
antecedent generation or load in a regional grid is lost.
Category GD-3 - When twenty per cent. to less than thirty per cent. of the
antecedent generation or load in a regional grid is lost;
Category GD-4 - When thirty per cent. to less than forty per cent. of the
antecedent generation or load in a regional grid is lost ;
Category GD-5 - When forty per cent. or more of the antecedent
generation or load in a regional grid is lost.
Explanation: For the purpose of categorisation of grid disturbances,
percentage loss of generation or load, which ever is higher shall be
considered.
Previous and next
All provisions of Central Electricity Authority (Grid Standards) Regulations, 2010
Questions people ask
Is regulation 11 of Central Electricity Authority (Grid Standards) Regulations, 2010 still in force?
No repeal of Central Electricity Authority (Grid Standards) Regulations, 2010 is recorded.