Regulation 20, Central Electricity Authority (Installation & Operation of Meters) Regulations, 2006: Adoption of new technologies
Central Electricity Authority (Installation & Operation of Meters) Regulations, 2006 - Regulation 20
Text of regulation 20
Adoption of new technologies
20. Adoption of new technologies. -
The distribution licensee shall make out a plan for introduction and adoption of new
technologies such as pre-paid meters, time of the day meters (TOD), automatic
remote meter reading system through appropriate communication system with the
approval of the Appropriate Commission or as per the regulations or directions of
the Appropriate Commission or pursuant to the reforms programme of the
Appropriate Government.
14
SCHEDULE
(see regulations 2,5,8,12 and 16)
Standards on Installation and Operation of Meters
Part I Standards Common To All Type of Meters
(1) These standards provide for specification of meters, immunity to external factors,
sealing points and functional requirements that are required from regulatory perspective.
Detailed technical specification shall be prepared by the purchaser of the meter.
(2) Specifications of meters
Standard Reference Voltage As per IS
Voltage Range As per IS
Standard Frequency As per IS
Standard Basic Current
As per IS
(Current range of consumer meters shall be so
chosen as to record the load current corresponding
to the sanctioned load)
Accuracy Class
Meters shall meet the following requirements
of Accuracy Class:
Interface meters 0.2S
Consumer meters
Up to 650 volts 1.0 or better
Above 650 volts and
up to 33 kilo volts
0.5S or better
Above 33 kilo volts 0.2S
Energy accounting and audit meters
The accuracy class of meters in generation and
transmission system shall not be inferior to that
of 0.2S Accuracy Class. The accuracy class of
meters in distribution system shall not be inferior
to that of 0.5S Accuracy Class
Starting Current and Maximum
Current
As per IS
15
Power Factor Range As per IS
Power Frequency Withstand
Voltage
As per IS
Impulse Voltage Withstand Test for
1.2/50 micro sec
As per IS
Power Consumption As per IS
(3) Meter shall have downloading facilities of metered data through Meter Reading
Instrument (MRI).
(4) Immunity to External Factors
The meter shall be immune to external influences like magnetic induction,
vibration, electrostatic discharge, switching transients, surge voltages, oblique
suspension and harmonics and necessary tests shall be carried out in accordance with
relevant standard.
(5) Sealing Points
Sealing shall be done at the following points (as applicable):
(a) Meter body or cover
(b) Meter terminal cover
(c) Meter test terminal block
(d) Meter cabinet
(6) The accuracy class of Current transformers (CTs) and Voltage transformers (VTs)
shall not be inferior to that of associated meters. The existing CTs and VTs not
complying with these regulations shall be replaced by new CTs and VTs, if found
defective, non-functional or as per the directions of the Appropriate Commission. In
case the CTs and VTs of the same Accuracy Class as that of meters can not be
accommodated in the metering cubicle or panel due to space constraints, the CTs
and VTs of the next lower Accuracy Class can be installed.
(7) The Voltage Transformers shall be electromagnetic VT or Capacitive Voltage
Transformer (CVT).
16
Part II Standards for interface meters
(1) Functional Requirements:
(a) The Interface meters suitable for ABT shall be static type, composite meters , as
self –contained devices for measurement of active and reactive energy, and certain
other parameters as described in the following paragraphs. The meters shall be
suitable for being connected directly to voltage transformers (VTs) having a rated
secondary line-to-line voltage of 110 V, and to current transformers (CTs) having a
rated secondary current of IA (Model-A :3 element 4 wire or Model C: 2 element , 3
wire) or 5A (model-B: 3 element , 4 wire or Model D: 2 element 3 wire). The
reference frequency shall be 50Hz.
(b) The meters shall have a non-volatile memory in which the following shall be
automatically stored:
(i) Average frequency for each successive 15-minute block, as a two digit
code (00 to 99 for frequency from 49.0 to 51.0Hz).
(ii) Net Wh transmittal during each successive 15-minute block, upto second
decimal, with plus/minus sign.
(iii) Cumulative Wh transmittal at each midnight, in six digits including one
decimal.
(iv) Cumulative VArh transmittal for voltage high condition, at each midnight, in
six digits including one decimal.
(v) Cumulative VArh transmittal for voltage low condition, at each midnight,
in six digits including one decimal.
(vi) Date and time blocks of failure of VT supply on any phase, as a star(*)
mark.
(c) The meters shall store all the above listed data in their memories for a period of at
least ten days. The data older than ten days shall get erased automatically. Each
meter shall have an optical port on its front for tapping all data stored in its memory
using a hand held data collection device. The meter shall be suitable for
transmitting the data to remote location using appropriate communication medium.
(d) The active energy (Wh) measurement shall be carried out on 3-phase, 4-wire
principle, with an accuracy as per class 0.2 S of IEC-687/IEC-62053-22. In model-
A and C, the energy shall be computed directly in CT and VT secondary quantities,
and indicated in watt-hours. In model-B and Model D , the energy display and
recording shall be one fifth of the Wh computed in CT and VT secondary quantities.
(e) The Var and reactive energy measurement shall also be on 3-phase, 4-wire
principle, with an accuracy as per class 2 of IEC-62053-23 or better. In model-A or
Model C, the Var and VArh computation shall be directly in CT and VT secondary
quantities. In model-B or Model D, the above quantities shall be displayed and
recorded as one-fifth of those computed in CT and VT secondary quantities. There
shall be two reactive energy registers, one for the period when average RMS
voltage is above 103% and the other for the period the voltage is below 97%.
17
(f) The 15-minute Wh shall have a +ve sign when there is a net Wh export from
substation busbars, and a –ve sign when there is a net Wh import. The integrating
(cumulative) registers for Wh and Varh shall move forward when there is Wh/Varh
export from substation busbars, and backward when there is an import.
(g) The meters shall also display (on demand), by turn, the following parameters :
(i) Unique identification number of the meter
(ii) Date
(iii) Time
(iv) Cumulative Wh register reading
(v) Average frequency of the previous 15-minute block
(vi) Net Wh transmittal in the previous 15-minute block, with +/-sign
(vii) Average percentage voltage
(viii) Reactive power with +/- sign
(ix) Voltage-high VArh register reading
(x) Voltage-low VArh register reading.
(h) The three line-to-neutral voltages shall be continuously monitored, and in case any
of these falls below 70%, the condition shall be suitably indicated and recorded.
The meters shall operate with the power drawn from the VT secondary circuits,
without the need for any auxiliary power supply. Each meter shall have a built-in
calendar and clock, having an accuracy of 30 seconds per month or better.
(i) The meters shall be totally sealed and tamper-proof, with no possibility of any
adjustment at site, except for a restricted clock correction. The harmonics shall be
filtered out while measuring Wh, Var and VArh, and only fundamental frequency
quantities shall be measured/computed.
(j) The Main meter and the Check meter shall be connected to same core of CTs and
VTs.
Part III Standards for consumers meters
(1) Measuring Parameters
(a) The consumer meter shall be suitable for measurement of cumulative active
energy utilized by the consumer.
(b) The consumer meter may have the facilities to measure, record and display one
or more of the following parameters depending upon the tariff requirement for
various categories of consumers. All parameters excluding instantaneous
electrical parameters shall also be stored in memory.
(i) Cumulative reactive energy
(ii) Average power factor
(iii) Time of use of energy
18
(iv) Apparent power
(v) Maximum demand
(vi) Phase voltage and line currents
(2) All the three phase meters shall have data storage capacity for at least 35 days
in a non-volatile memory.
(3) Anti-Tampering Features
(a) The meter shall not get damaged or rendered non-functional even if any
phase and neutral are interchanged.
(b) The meter shall register energy even when the return path of the load
current is not terminated back at the meter and in such a case the circuit
shall be completed through the earth. In case of metallic bodies, the earth
terminal shall be brought out and provided on the outside of the case.
(c) The meter shall work correctly irrespective of the phase sequence of supply
(only for poly phase).
(d) In the case of 3 phase, 3 wire meter even if reference Y phase is removed,
the meter shall continue to work. In the case of 3 phase, 4 wire system, the
meter shall keep working even in the presence of any two wires i.e., even in
the absence of neutral and any one phase or any two phases.
(e) In case of whole current meters and LV CT operated meter, the meter shall
be capable of recording energy correctly even if input and output terminals
are interchanged.
(f) The registration must occur whether input phase or neutral wires are
connected properly or they are interchanged at the input terminals.
(g) The meter shall be factory calibrated and shall be sealed suitably before
dispatch.
(h) The meter shall be capable of recording occurrences of a missing potential
(only for VT operated meters) and its restoration with date and time of first
such occurrence and last restoration along with total number and duration of
such occurrences during the above period for all phases.
(i) Additional anti-tampering features including logging of tampers such as
current circuit reversal, current circuit short or open and presence of
abnormal magnetic field may be provided as per the regulations or
directions of the Appropriate Commission or pursuant to the reforms
programme of the Appropriate Government.
19
20
Part IV Standards for energy accounting and audit meters
(1)The energy accounting and audit meters shall be suitable for measurement, recording
and display of cumulative active energy with date and time.
(2) The energy accounting and audit meters may also have the facility to measure, record
and display one or more of the following parameters depending upon the energy
accounting and audit requirement. All parameters excluding instantaneous electrical
parameters shall also be stored in memory.
(a) Apparent power
(b) Phase wise kilowatt at peak KVA
(c) Phase wise KVA(reactive) at peak KVA
(d) Phase wise voltage at peak KVA
(e) Power down time
(f) Average power factor
(g) Line currents
(h) Phase voltages
(i) Date and time
(j) Tamper events
(3) The energy accounting and audit meter shall have data storage capacity for at least
35 days in a non-volatile memory.
(4) Energy accounting and audit meters shall have facility to download the parameters
through meter reading instruments as well as remote transmission of data over
communication network.
Sd/-
(R. Dahiya)
Secretary, Central Electricity Authority
20180308120858
meter_reg
(Published in the Gazette of India, Extraordinary, Part III, section iv)
Central Electricity Authority
New Delhi, dated the 17th March, 2006
NOTIFICATION
No. 502/70/CEA/DP&DIn exercise of the powers conferred by sub-section (1) of section 55 and clause (e) of section 73 read with sub-section (2) of section 177 of Electricity Act, 2003, the Central Electricity Authority hereby makes the following reg
Short title and commencement. -
SCHEDULE
(see regulations 2,5,8,12 and 16)
Standards on Installation and Operation of Meters
Part I Standards Common To All Type of Meters
(6) The accuracy class of Current transformers (CTs) and Voltage transformers (VTs) shall not be inferior to that of associated meters. The existing CTs and VTs not complying with these regulations shall be replaced by new CTs and VTs, if found
Part III Standards for consumers meters
Part IVStandards for energy accounting and audit meters
Previous and next