Regulation 19, Central Electricity Authority (Installation & Operation of Meters) Regulations, 2006: atfaRckt ~
Central Electricity Authority (Installation & Operation of Meters) Regulations, 2006 - Regulation 19
Text of regulation 19
atfaRckt ~
19. atfaRckt ~--
~Wxr~ci5l~~~¢1 Rcl>1~~rcf>~~~~
c5 31 RIR@. ~ "3l faRcR1 "41cx·, .,~ "l-fi.r {ic$(ict>" m
31~ '34cfj'{Uj ~ cffi "lfT "ffi ~ cvl .~ .cBl ~ ~ ~ c61
1fP-TT cp"f ~ ~1 ~ 3lWTT ftj~ll~ct ~ 3l~ tlcT c$T WIT Fvif1<:B
~ ~ ~ vITTft t 3f~IDTT-wm~~ ~ ~R;n, ~~
~ cn1 • cn1 uf@) ~ 3l2TTTT ~T cJ?T ~~ "{1 °'1~ ~ ~ --ll
lff~l 31~ ~-Pr~ cf>T 41.iT cf71T.?f "i:fi ~~ Bfilcf ~~- <'i1T ~~~~ g- .
,•j 7 7 c, _; / o l- - -- -:~
l7
18 THE GAZETTE OF lNDIA: EXTRAORDlNARY [PARTIIl-SEc.4] \
~@ ~ t; fcn ~ {4cf>ach 3T~ '3445-<0I ~q~a fP-l ~~a ~ ~ ll
~ ~tITTT cB" ~a~o! W mfr fcITTfi ~ ~ c5 ~ ~ -ltf <1Jll~I
\Jl l~ll ] I
~~mi Fcn vrm ~ ffi ~ ~ ~ ~-~-~ ~~ ~*
~ ~ ~<iJ"R ~ ~. fi~acn m 0qcn~o1 cfi tRFf m . ~ 'Clx ~
~ i, ~ ~ fclq~a tF1~1a *' ~ lf, ~ ~
'3qcbi{o1 cWTT xicli ci<'h cITT. ~ ffllTI" I
fq a'<ot ~ '34 'ji:ki 3TT<TT1T ~ 3ljB1~~ or~ '3 4g<K'l 3TT<TTTf *
Rlf1lli-i'i ~~ R~ll~~:;!11 q5" ~ ~~ '34 ~cffi '8'11451~ cf; ~ 4>14W'-l
c5 3lj~xo1 1f Wl'-c@ ~ sio,,c.4) cfi 1TIU'.Pl ~ "Sft-~ ~ .~ 3ITQJ G ~
(a 31.,- ~) ~1c{, ~ ~ ~ ~ ~u,1c41 ~ ~ snrni=r1m,~ti
cITT ~ .lft¢1 .;: (\!ilc~11) ~ cfi ~ a 2TT ~-q•c+i . (~~-scn11) 1f ~ * ~
lll\Jl-il iFll~•II I
31j,qill
(f4Pt~"f 2,5,8, 12 3tR 16 ~)
~ ~ -~ ~ UT.il<1ii ~ +lliitb
(1) _- ~ +ll1cb'i 1l ~ cf> fq f:)~~1'1, ™ clll~ch) ~ ~. -«}f~PI ~
am cnllllci-t$ ~1c1~llcn<11arr cpT ~ t "fl" RlPll1r'-tcfi ~~ ~
~ t I f4~~a acf>'i1cv1 ~Pi~~,1 ~ ~ ~ am-~~~ ~ 1
(2) ~ ~ fclPt~~M (~~~<fi1li-« aifq; iffca) .
cffirn)
~ ~cf> ~jtll'!
(~ ~ ctft ~ \:lffi ~ 4R'41111 ~ ~
. tj~Pt~ ~ \Jll(!lfl TTfi f<ftpct 1JR cfi c1Gj'64 ~
'llR~cn)-Rct,1,g fcfimuTT~ I
~ qR~~a, ~ cfft f~p--1R;!rtla 3Nman cm -
~ cfRlt:
0.2 ~
650~cf<n .1.0 ~ ~
0.2 ~
'3\'G 1c;-1 ~ sH11-<01- !A 0 Lf cl'I ~ ~-~ 4Ri{!caa,
~ 0.2 1[{f ~ ~ ~ m-ft" I ~i;f-<01 3,fU[lct} 1t
lftw mt qR~m ~ 0.5 ~ ~ q;., ~ m1ft I
19
THE GAZETTE OF INDIA: EXTRAORDINARY (P,\RT lll-SF.c. 4)
1WR ~ cfc'< {GT ~.~. cfi--~-j-!11"< ·-----------·----- ··-
r--·-=-------.:---=:--:=-----;-;----,--c---------- ----· - -- ----- · ----·
1WR fih cN ~ f.4 cff~'5 cfl <R.\Jf ~-~ . ~ at j~i I"<
(3) ~it~ &RT~~ cpT ~ ~ ~~e (-crl &N·3Tff)
a@ -sl'31cll~JI <fft ~ mlft I
~ ~ WffclT ~ 4~.)feqj ~"\Si:K!l1, (1(~~~11, ~~~~Ref> -~fi!iui,
f<f1RlJ1 <;_1,:i:,ih~~. ~ ct't&ut, ;.si1i1cllc:fl! t1,tq~I~ : ~ €W~l-f)PicRt ~
~ ~ ~ n~ ~ 1Wfcn -~ ~ ~ cn1 ~afOT ~
'JJl~ 111 I
(5) ift~•I ~ ·
(en) ~~~q'icR
(~) ~ c~ 'i <'1 q;cR"
(•r) lftcx~ d1J..:ic-1 ~
.
(u) 4tcx ~Rl~c:
(6) q,R ~ff4>1'l-<1 crm m~vi c;jt1lb14~ <lft. qR~.aa1 Wlft t1~ca ~ cJft
4R:{!~dl ~ ~ t1fe.Q1 ~ N1ft _ I ~ f<h:.ti:i1..:i -~ ·-tt ~ cft it ~
FclRl ~Ji'i q)f ·tm-f.l ~ iITT-. ~ g oq" ~ ~ m · ~ ~ -~rit ~ ~
~ vtl~'l1, ~ ~ ~~~<Ri t ~fiwll 'g- m '34Y,cRt ~ ~ ~ ~ I
~ ~ vRfi m qR~~a1 Wlft m ~ tl_ ow- ~ it 41d~i1_ cRj4'l4Je>i
3l~ ~ 1l ~ ~ ~ cpRUT flJilmRiJa ~ -~ vfT ~ W cf6l
~ f.'f9ct'{ llR~~~11 ~ cf> ~ ~ cf211 cft it ~ ~ \ilT ~
ii
(7) <fl~"1 <;.i"<itnl4-<, ~trl~1'•4fe.ct> ~ tt 3mcIT ifiqR-ffect ql&e,\Jf c;_ifllf>liix
(m ctr~)~ I
(cp) ~.rfi.~. cfi" ~ '349,cRl ~.-c-<lfifl lficx ~ m cf>, ~ ~
x<ra: ~ If';f m-ri- ~ ~-llffi{l q l,{Rlt11cfl ~ cn1" ~ ~ ~ ~ ~
3Rl ~x1Ji1c-<i ~ ftp- ~l-.i~~d ~-<lmlb -q cf$, ~ 7fliT t 1IT'T I
~ ~ 110 er.ere ~ ~ ~ ~ ~<:6-s~ ql&e."1 ~ c(l~\il
c;;:iflct>140 aw ~ \!fiG<l-< ~ fcrqa mxr (~-~= 3 ~<.4'l~k. 4
cITTR) 3f~ (1,1~ tfi : 2 ~ ~ ~ c, 3 cITTR) 3l~ s 1-! fl.cl {j ~ (~ - at
: 3 ~cfi4c:, 4 cfPR) 3T~ (~ ~ : 2 ~c11qc, 3 cIT<R) ~ ~
<;:ifilf>IB~ cm- ~* cfj~<.F,ll'i ~ cf> ~ '3qg@ "ITT11" I ~ ~
(fibcN'<ll) so~~ I
(&) lftcx li ~ ~-ci1clcl~ ~ m1fi fGfflii Pt1-1R-i~a qft "{<fcf: ~
R<hl~•I -gpfi:
(i) ~ ¢~<h 1s ~ ~ ~ ~ 3fRfa" &5cr4:rt), m RsRile
m cf>~ -ij (oo ~ 99, 49.0 ~ ~ 51.0 ~ ~ ~
~)I
(ii) ~ wf445 1s ~ cfi ~ cf>" ctRR ;)z ~ ~ <;:i{i~c&i,
~ ~"c1q ~. ~/~1~1fl ~ ~ I
(iii) ~ 3ltl~ tR ~ ~ ~ c;J-8~ect, 6 ~ "#, ftttiil ~
~ ~Rel qJ"f {1fil!R;(a ~ I
(iv) ~ dr&eGi ~ rfi ~ ~ ~ ~ ™ ~ c;:ifl~ccl,
~ ~ lR. ci ~ lf, ftiti'l ~ ~ -G~li<"l~ cm
{4fi:tifc1a ~ I
21
(v) ~ crt~vl ~ ~ ~ ~ ell ~ ~ -~ ~fl~ccl, -
-~~ __ 31tT~f) ~ 6 ~ - if. R;ifts) . ~ ~ ql4C"lct <ITT -
mit1fc;@ -~ I
(vi) fq;·,R1 ~(J{ q-f ~tr ~ 11 mnft qfi fi'rfu am wm ~.
m~tf~ (·) 1n<t ~ ffi ~ 1
22 THE GAZETTE OF INDIA: EXTRAORDINARY (P AKT Ill - Snc. 4 J
(ll) cf)ll ~ cf)ll 10 ~ cfiT ~ ~ ~ \Jq'{li'.hi ~ ~ ~ cBT
~ 1l ~ ~ I 10 f0 ~ ~ ~ ~ ~= fffc ~ I ~cp
~ 1t ~ ~ ~ .'llllT 1l ~ 3llte'lcf>~ lTTZ -tWTT ~{I~•~
~-<f>~i:Fll~ f%qj~{l
1
~ tl§l4ctl ~ ~ -q ~ ~ cf>1 ~ f<trm· \.jff
~ I \i49,cfa fii:11~01 li!F)P-1 cfil {H51lldl ~ ~ ~ ~ m cnl ma
~ q,R ct\- fc;rq ~ ~ I
(ti) tiUh~ ~ (~ ~) 1'.fN-f ~-t-~.-687/3TTW.t~.62053-22 <lft 0.2S
4R~<&dl WJft cf> ~j{ilx 3 WGT, 4 cITTR f°ficiiia "CR ~ ~ I ~ ~
~ ~ -q, ~- x:fr tr ~ <ft tr ~ ~~,$~ ~3it ct ~ ~ ~h)
4Rc6~a qft \it1~1Yl ctm cite~ -q ~ \JJ1~ 1n I w;c-1 ~ ff~T ~~
~ -q_ ~ J.1~it1 elm Rif>l~11 -fft tl ~ cft iT ~ x')·cfi~1T ~T~lT (~
ffi•mfl xl qRcJ>fc.!ct ·~ l[q' cnr q'fqzj m-sr -g)lft I
(~ cfR ~m J.1Rit11cft ~ ~ ~-t~. 62053-23 qft ~u)T if .<li 3fj-~R
31;2lql ~ \TIPl qR~ctl ~ 3 $Jr, 4 cJT<R ~i;f ~{ cfi1" vir;MT !
~ ~ ~ ~ ~ if, cTR (V Ar) wn V Arh qRmc-11 ~ tl cn>n
cfi tr 'fl<fi-s~ ~3it -ir ~* N'TT I ~ tft 3mcIT ~cl ~ 1l mx ~n
~ ThvIT ~ tt -a2JT ~ tl ~ st1cB-i5~ ll0IT3TT cB" f%mc-l x1 qf~--fcia
lfP-TT q)f ~ 1fflT f%aj cJm Rif>I~ fcl>"m 0ill;! 111 I ·c;) m<ltf@I ~~,n
~FG!t=e'-! m-rr, ~ \.fxl ~ cf> ~ um ~ 1TTur ~ ql ~,n 103'7<- ,q
~ om ~ ~ ~ ~ ~ ~ ci1 creu1 97¼. xf coli ·ITT11t I
('i:T) -1 s ~ cf> ~ ~- 1-fR 1l +ve Q)l ~ ~ ~PTT. ~ '34c'fi.:S:: "ijxJql\~
~ ~ ~ ~ (Net Wh) ~ t. ~ -ve ~ f5111T ~ ~ ~l
-q=q 3ITTITTf t I~ '34<.6~ rHF-llx'i ~- WhNArh ~l ~ cf& Wh ~TT
VArh ~ ~ '<-1'l1cnftla (~) ~fGliR~- 3~ "'q""<:Z111, ~ 3WlIB '6 (!l
qg fcrq~a -~ lf ~ I
(g) ~ -rPiR-irtla•- ~\!Pft~~ (llPT ~ ~-~ 1ft ~m~ I
(i) -~ cfft ~-Gt5il11 "&-«TT (~-~~~r~ ;fo)
(ii) ~
(iii) ~
(iv) xhnfl Wh -~~«'-~ ~~T
(v) ~ 15 fi'l~ ~en" cn'l 311~,a ~ I
(vi) f11uR 1 s f?f-;:rc ~ -ii • /- fclp1 nf~,_:i ·it(~ \V h , : i ~d 11 ,~ <:--1
..
(vii) ~ SIRi~ld 4\lcie.GI
(viii) S1RwuRt ~ ~ +/ -~ ~
(ix) q\(cie.GI-~ V Arb xRif-R-x ~
(x) 416eut-~ V Arb xftt~x ~
(Gt) aR ~-~-~~<'! q~<.>eGI "qj) Pl~d~ ~-~~Rld fcmn Gt1q111 ~ ~ ~
~ ~ 1ft" 700/o ~ ~ amfi i ij)- ~ ~ ~ ~ ~ ~ G~lhH
\1mp11 wm R<t>1J ~ . u11~111 1 ~ ~ ai1fivt<-1~ ~ ~ ctft ·
3JlcPtllcf>dl ~~VT flc6.s~ ~ W ~ ~ ~ ~ -GRiH61-1
~ , S4~<t> ~ 1) 30 -~ ma lfm qff-~ ~ ~ qR~cad1 ~
~-~ ~-~ ~c-1"\S~ om~ m1fi I .
(~) . ~ ~ ~c-1'1 ~ lR -Rt qf~ ~ cfft_ ~ 1f 'ffl_flt d ~ ~. ~ ftRfi
fl'-ll~1Gt1 (~.suttcfie) ~ ~~ ~ ~ ~ ~ ~ ~ ~-~
N1l1 ·Wh~ VAr~ VArh Tfll@ ~ -~. (t6-5t~ecl RP<M~) ~
51-<'flrl<M <ffi' ~6e'{ ~ Gtl~'II -~ -$rc;f q;;g1ifccl fm~~ qft
~Jt cm- 1WTI/4R<t>R-la fcpm Gt1,p11 I
(ur) lR ~ crm ~ ~ -CT er.ITT VT c5 -~ 1ft ~ -w ~ ~ 1
(cf>)
(~)
.. ~ lftc(' ~ ~ '34lll 11 ~ ~ ~ ~-tj4)· ~~l( ~
en) 1lPR ct ~ ~ "ITT1TT I
~ ~ c5 ~3IT <$ ~ ffitp 3Hq~llcf>dl31T tff
a,1~1Ra ;aqini:Rir 1ftcx it P1"'1~~a ~.-<14le-<1 "if -~ ~ ~
~ <ffi" ~. Rcf>I~ ~elm~ qfi 'tl~'tW~ M I dl~fulch .
~ 1fFfT cffl" t§l~ch~. ~ ~-<i41e-< ~ ~ ~ ~ 1ft ~ ~
~ I .
(i) ~:sifat11a1 ~~
(ii) -~ qJcR ~cfc.'<
(iii) ~ -~cf>~ qjT ~
(iv) ~q~;;e ~
(v) '3 i:;q d 'l lTTTT
(vi) ~ ch~'J' om ~ ~
23
24 THE GAZETTE OFINDJA: EXTRAORDINARY · [PART lll-:-Ssc. 4]
(2) . ~ ~ "tf>Gf ~ ~ ~ ~-m&lel~C'i ~ "# cf)lf ~ qi"-q 35 ~
cf>T~~~qft~m-ifi- 1 -
(cf>) ~ ~ tfi\if m ~ 3TI1IB" -# ~ 1fr· \Jfffi i m ~ -~ ~
~f1ftijj<1~mTIT I
(~) ~ ~ -~ ~ ~ ~ cpl" ·q1q~ ~ ~ ~ "CR ~
~i-111.d-~ 6Tffi ~ill~~-~~ q)l -<Rilitc< cfRlJT_am-~
~ it ~f4>c. ~ <'6:Gffi ~ ID1IT I .ste~q, iil~GI _<ff ~ "# 3m
d1i~ct cITTf ~ ~ Picf1'6U Gil(PII ~ ~ <$ ~ m"ll ~ <:'l'fl.!11
\JllC:•11 I
(7T) ~- • cf> $i{ R=lct4ti cf> ~ ~ q;rq ~ ~ 1flcift
~cfi ~) l
(u) 3 llwr, 3 cIT<R1frcx~~-#. ~~qrf (Y) ~~ "Gf@"f
t cIT ~ <Pnl cfRcfT ~ I 3 ~. ·4 ~ Sl 0 11~ cfi 1lr@ if, ~
-ey ~ ~ '34~ Rl it '4t lftcx cffi1t cfflfil ~ ~ -~ ~
~-~~m~cft~qft31:!q~R) if~ I
(~ ~~~~ LVCT qR=rH~d ~~1lll@"Jl, ~~
-am ~1'3c~c. e.~1cl ~ ~ .\JJIB t cff ~ lficx -~ ~ qj)
'<ic)<f>ctl ~ Rct,1~ cfR'l. 1)-~ 1?t-m t
('if) ~ ~ <Pl ~Rit~~,1 ~ ~ ~ =q1ft~. ~ ~~~c'. .m,r ~
~ cfnR ~ ~ ~ ~ t ~ ~ ~-19,c c:~-1<:>1 ~ ~ -q
~~ll'ttl
(u) +ftcx ~cfc~ ~f~M~E'5 (3l~lif41e1) ~ ~ ~ ~ ~ ~ "ffi ~
~~§3UWTTI
(\if) +fie{~ 4~el11_2fo1 ctft ~ (~ vr·3,4=q1~a ~ c5 ~) am
~ ~ m:-TT qft ~ ~ ~ q1' ~ '3't!i:f>l :ff:~i11cl'1
~ffl~~H) -~ ri ~ cfi ~ _6Q4cft1_ ~ ~ ~-~ ~arr
<fiT ~ ~ am wmi ~ 3ITTllr :{-l:~-qfoM iffi" RCP.1& ffl' if
~ir1llt
(~) x3qg,cffi ~ ~ f4Pl_lFil _c{W Pt~~~ ·g1 ~j~l'< 3l'WTT_ -'3q~cffi ,~H<fil'< -
(fj -~ <fil~w'i * 3tjf1'<01 l'f ~RtRcfd ~-e~R,1 m~tta1~ ~ -it.
am qRq~ cf>1" '3ctc'il. 'clRT ~ mt ~ 3TT1Pf 3l'Tx 31'{11J.t1.:.a
1~c6l~ ~ "$1 ~ ~ ~~ <61 ~3IT cf>1" ~ ~
t1fulfc.ia 6T, '3Gcl&.{ ~ ull ~ -g- I
(1) ~ '7icfjt\JR:•r ~ ~ ~ ~ ~ -~ ~ ~ ~ffh.Q
~ ~ q'i lfllR. Ri:h1tl•1 om ~ ~ ~ tlq~tffi mTt 1
(2) ~ 31ct>MR•1 ~ ~ cJft 31rq~<tg,c1131T 1R frr4x ~ ~ -~
aicfiMR•, ~ ~ ~ it f.1i:.-ift9 ftm ~'<i4k:{i ii ~ cmt ~ ~
~ ~-<i4'le\li Q'>t lffCR; Rcbl~ ~ elm ~ qft- p mlfi I
t11~f1)1q, ~ 1lFfT cffl ·t§l~qj'< ~ ll-<141C{ ~ ~ ~ ~ ~ ~
~~I .
(<v) Q~~;e ~ .
(~) fiRR ('lftcp) cfi "d1 ~ l:lx l6iJMl~I.J1 f&;e1\lqlc
(~) firm <'5 <ft ~ lR l6Gtql~GI cf> ~ ~ (5-1RIEll<l1)
(ti) ~I~"< <fi cfi ~ lR l6Glql$GI ql<R\il
(~ WR~~-
(=cr) ~ tfT<R ~<fc':<
(u) ~~
(vr) $it <n~ui
(~) ~~~
(ur) ~ ~e-11~
3. ~ 31ct,1'3R~, ~ ~ ~ it .JA-q)C'lcl~t-t ~ ~ q;i, ~ ~
35~7.f>T'5lcf~_~qft!Wfffimrfi I
-~ 31ct5MR•1 ~ ~ ~ ~ ·~ ~ ~~ifc• ~ ~ ~
-Gl,:M('ll..s ~ ~ '{1f4etl ~ ~-~. th:U-<01 ~cqc:6· lff ~ ~
~~lff~~qft'~fcl\:11 ~ I
a77c;; 2 /06 --- <;
~~.-~
[ ~-IU/IV/186-10/2005/amf_]
25
(Published in the Gazette of India, Extraordinary, Part III, section iv)
Central Electricity Authority
New Delhi, dated the 17th March, 2006
NOTIFICATION
No. 502/70/CEA/DP&D In exercise of the powers conferred by sub-section (1) of
section 55 and clause (e) of section 73 read with sub-section (2) of section 177 of
Electricity Act, 2003, the Central Electricity Authority hereby makes the following
regulations for regulating the installation and operation of meters, namely :-
1. Short title and commencement. -
(1) These regulations may be called the Central Electricity Authority (Installation and
Operation of Meters) Regulations, 2006.
(2) These Regulations shall come into force on the date of their publication in the
Gazette of India.
2. Definitions. -
(1) In these regulations, unless the context other wise requires, -
(a) ‘Act’ means the Electricity Act, 2003;
(b) ‘Accredited Test Laboratory’ means a test laboratory accredited by National
Accreditation Board for Testing and Calibration Laboratories (NABL);
(c) ‘Active Energy’ means the electricity supplied or consumed during a time
interval, being the integral of Active Power with respect to time, measured in
the units of ‘Watt – hours’ or standard multiples thereof. One ‘kilowatt –
hour’ (kWh) is one unit;
(d) ‘Active Power’ means the electrical power, being the product of root mean
square (rms) voltage, root mean square (rms) current and cosine of the
phase angle between the voltage and current vectors and measured in units
of ‘Watt’ (W) or in standard multiples thereof;
(e) ‘Appropriate Load Despatch Centre’ means ‘National Load Despatch
Centre’ (NLDC) or ‘Regional Load Despatch Centre’ (RLDC) or the ‘State
Load Despatch Centre’ (SLDC) as the case may be;
(f) ‘Appropriate Transmission Utility’ means the ‘Central Transmission Utility’
(CTU) or the ‘State Transmission Utility’ (STU), as the case may be;
(g) ‘Availability Based Tariff (ABT)’ means a tariff structure based on availability
of generating units and having components, viz, Capacity Charges (CC),
1
Energy Charges (EC) or Variable Charges (VC) and charges for
Unscheduled Interchange (UI);
(h) ‘Buyer’ means any generating company or licensee or consumer whose
system receives electricity from the system of generating company or
licensee;
(i) ‘Check Meter’ means a meter, which shall be connected to the same core of
the Current Transformer (CT) and Voltage Transformer (VT) to which main
meter is connected and shall be used for accounting and billing of electricity
in case of failure of main meter;
(j) ‘Consumer Meter’ means a meter used for accounting and billing of
electricity supplied to the consumer but excluding those consumers covered
under Interface Meters;
(k) ‘Correct Meter’ means a meter, which shall at least have, features, Accuracy
Class and specifications as per the Standards on Installation and Operation
of Meters given in Schedule of these Regulations;
(l) ‘Energy Accounting and Audit Meters’ means meters used for accounting of
the electricity to various segments of electrical system so as to carry out
further analysis to determine the consumption and loss of energy therein
over a specified time period;
(m) ‘Instrument Transformer’ means the ‘Current Transformer’ (CT), ‘Voltage
Transformer’ (VT) and ‘Capacitor Voltage Transformer’ (CVT);
(n) ‘Interface Meter’ means a meter used for accounting and billing of electricity,
connected at the point of interconnection between electrical systems of
generating company, licensee and consumers, directly connected to the
Inter-State Transmission System or Intra-State Transmission System who
have to be covered under ABT and have been permitted open access by the
Appropriate Commission;
(o) ‘Main Meter’ means a meter, which would primarily be used for accounting
and billing of electricity;
(p) ‘Meter’ means a device suitable for measuring, indicating and recording
consumption of electricity or any other quantity related with electrical system
and shall include, wherever applicable, other equipment such as Current
Transformer (CT), Voltage Transformer (VT) or Capacitor Voltage
Transformer (CVT) necessary for such purpose;
(q) ‘Power Factor’ means the cosine of the electrical angle between the voltage
and current vectors in an AC electrical circuit;
(r) ‘Prepaid Meter’ means a meter which facilitates use of electricity only after
advance payment;
(s) ‘Reactive Energy’ means, the integral of Reactive Power with respect to time
and measured in the units of ‘Volt-Ampere hours reactive (VARh) or in
standard multiples thereof;
(t) ‘Reactive Power’ means the product of root mean square (rms) voltage, root
mean square (rms) current and the sine of the electrical phase angle
between the voltage complexor and current complexor, measured in ‘Volt –
ampere reactive’ (VAr) and in standard multiples thereof;
(u) ‘Standards’ means ‘Standards on Installation and Operation of Meters’ given
in the Schedule of these Regulations unless otherwise any other standard
specifically referred;
2
(v) ‘Standby Meter’ means a meter connected to CT and VT, other than those
used for main meter and check meter and shall be used for accounting and
billing of electricity in case of failure of both main meter and check meter;
(w) ‘Supplier’ means any generating company or licensee from whose system
electricity flows into the system of another generating company or licensee
or consumer;
(x) ‘Time of the Day (TOD) Meter’ means a meter suitable for recording and
indicating consumption of electricity during specified time periods of the day.
(2) The words and expressions used and not defined in these Regulations but defined
in the Act shall have the meaning assigned to them in the Act.
3. Applicability of regulations. -
(1) These Regulations shall be applicable to meters installed and to be installed by all
the generating companies and licensees who are engaged in the business of
generation, transmission, trading, distribution, supply of electricity and to all
categories of consumers.
(2) After coming into force of these regulations, the provisions of the Indian Electricity
Rules, 1956 relating to installation and operation of meters in this regard shall not
be applicable.
(3) These regulations provide for type, standards, ownership, location, accuracy class,
installation, operation, testing and maintenance, access, sealing, safety, meter
reading and recording, meter failure or discrepancies, anti tampering features,
quality assurance, calibration and periodical testing of meters, additional meters
and adoption of new technologies in respect of following meters for correct
accounting, billing and audit of electricity:
(i) Interface meter
(ii) Consumer meter
(iii) Energy accounting and audit Meter
4. Type of meters. -
(1) All interface meters, consumer meters and energy accounting and audit meters shall
be of static type.
(2) The meters not complying with these regulations shall be replaced by the licensee
on his own or on request of the consumer. The meters may also be replaced as per
the regulations or directions of the Appropriate Commission or pursuant to the
reforms programme of the Appropriate Government.
3
5. Standards. -
All interface meters, consumer meters and energy accounting and audit meters
shall –
(a) comply with the relevant standards of Bureau of Indian Standards (BIS). If
BIS Standards are not available for a particular equipment or material, the
relevant British Standards (BS), International Electro-technical Commission
(IEC) Standards, or any other equivalent Standard shall be followed:
Provided that whenever an international Standard or IEC Standard is
followed, necessary corrections or modifications shall be made for nominal
system frequency, nominal system voltage, ambient temperature, humidity
and other conditions prevailing in India before actual adoption of the said
Standard;
(b) conform to the standards on ‘Installation and Operation of Meters’ as
specified in Schedule annexed to these regulations and as amended from
time to time.
.
6. Ownership of meters. -
(1) Interface meters
(a) All interface meters installed at the points of interconnection with Inter-State
Transmission System (ISTS) for the purpose of electricity accounting and
billing shall be owned by CTU.
(b) All interface meters installed at the points of interconnection with Intra-State
Transmission System excluding the system covered under sub-clause (a)
above for the purpose of electricity accounting and billing shall be owned by
STU.
(c) All interface meters installed at the points of inter connection between the
two licensees excluding those covered under sub-clauses (a) and (b) above
for the purpose of electricity accounting and billing shall be owned by
respective licensee of each end.
(d) All interface meters installed at the points of inter connection for the purpose
of electricity accounting and billing not covered under sub-clauses (a), (b)
and (c) above shall be owned by supplier of electricity.
(2) Consumer meters
(a) Consumer meters shall generally be owned by the licensee.
(b) If any consumer elects to purchase a meter, the same may be purchased by
him. Meter purchased by the consumer shall be tested, installed and sealed
4
by the licensee. The consumer shall claim the meter purchased by him as
his asset only after it is permanently removed from the system of the
licensee.
(c) All consumer meters shall bear BIS mark, meet the requirements of these
regulations and have additional features as approved by the Appropriate
Commission or pursuant to the reforms programme of the Appropriate
Government. To facilitate this, the licensee shall provide a list of makes and
models of the meters.
(3) Energy accounting and audit meters
Energy accounting and audit meters shall be owned by the generating company or
licensee, as the case may be.
7. Locations of meters.-
(1) The location of interface meters, consumer meters and energy accounting and
audit meters shall be as per the Table given below :
Provided that the generating companies or licensees may install meters at
additional locations in their systems depending upon the requirement.
Table
Sl.
No
Stages Main meter Check meter Standby meter
A. Generating
Station
On all outgoing
feeders.
On all outgoing
feeders.
(i) High Voltage
(HV) side of
Generator
Transformers
(ii) High Voltage
(HV) side of all
Station Auxiliary
Transformers
Explanation: The location of main, check and standby meters installed at the existing
generating stations shall not be changed unless permitted by the Authority.
B. Transmission
and Distribution
System
At one end of the line
between the sub-
stations of the same
licensee, and at both
ends of the line
between sub-stations
of two different
licensees. Meters at
both ends shall be
considered as main
meters for respective
- There shall be no
separate standby
meter. Meter
installed at other
end of the line in
case of two
different licensees
shall work as
standby meter.
5
licensees.
C. Inter-Connecting
Transformer (ICT)
High Voltage (HV)
side of ICT.
- Low Voltage (LV)
side of ICT.
D. Consumer
directly
connected to the
Inter-State
Transmission
System or Intra-
State
Transmission
System who have
to be covered
under ABT and
have been
permitted open
access by the
Appropriate
Commission
or
Any other system
not covered
above
As decided by the Appropriate Commission.
(a) Interface Meters
(i) Consumers who have interconnection with the Inter-State Transmission System
or Intra-State Transmission System and have been permitted open access by
the Appropriate Commission shall be provided with interface meters.
(ii) For consumers connected to distribution system and permitted open acess,
provision of interface meters may be made as per the regulations or
directions of the Appropriate Commission.
(iii) The scheme for location of interface meters shall be submitted to the CTU or
the STU or the CTU or the STU or the licensee by owner of the meter in
advance, before the installation of the scheme.
(b) Consumer meters
6
(i) The consumer meter shall be installed by the licensee either at consumer
premises or outside the consumer premises:
Provided that where the licensee installs the meter outside the premises of
the consumer, then the licensee shall provide real time display unit at the
consumer premises for his information to indicate the electricity consumed
by the consumer:
Provided further that for the billing purpose, reading of consumer meter and
not the display unit shall be taken into account.
(ii) In the event the Appropriate Commission allows supply of electricity directly
from a generating company to consumer on a dedicated transmission
system, the location of the meter will be as per their mutual agreement.
(c) Energy accounting and audit meters
Energy accounting and audit meters shall be installed at such locations so
as to facilitate to account for the energy generated, transmitted, distributed
and consumed in the various segments of the power system and the energy
loss. The location of these meters shall be as under:
(i)Generating Stations
(1) at the stator terminal of the generator;
(2) on HV and LV sides of the station and the unit auxiliary transformers;
(3) on feeders to various auxiliaries.
(ii)Transmission System
All incoming and out going feeders (If the interface meters do not
exist).
(iii)Distribution System
(1) all incoming feeders (11 kV and above);
(2) all outgoing feeders (11 kV and above);
(3) Sub-Station Transformer including Distribution Transformer – Licensee
may provide the meter on primary or secondary side or both sides
depending upon the requirement for energy accounting and audit.
8. Accuracy Class of meters. -
Every meter shall meet the requirement of accuracy class as specified in the
standards given in the Schedule.
9. Installation of meters. -
7
(1) Generating company or licensee, as the case may be, shall examine, test and
regulate all meters before installation and only correct meters shall be installed.
(2) The meter shall be installed at locations, which are easily accessible for
installation, testing, commissioning, reading, recording and maintenance. The
place of installation of meter shall be such that minimum inconvenience and
disruptions are caused to the site owners and the concerned organizations.
(3) In case of single phase meters, the consumer shall ensure that there is no
common neutral or phase or looping of neutral or phase of two or more
consumers on consumers’ side wiring. If such common neutral or phase or
looping of neutral or phase comes to the notice of the licensee, it shall suitably
inform the consumer through installation report or regular electricity bills or
meter test report as applicable.
(4) Consumer shall install the Earth Leakage Protective Device (ELPD) in
accordance with the provisions of the rules or regulations in this regard.
(5) If the earth leakage indication is displayed in the meter the licensees shall
suitably inform the consumer through installation report or regular electricity bills
or meter test report as applicable.
(6) In case CTs and VTs form part of the meters, the meter shall be installed as
near the instrument transformers as possible to reduce the potential drop in the
secondary leads.
10. Operation, Testing and Maintenance of meters. -
The operation, testing and maintenance of all types of meters shall be carried out
by the generating company or the licensee, as the case may be.
11. Access to meter. -
The owner of the premises where, the meter is installed shall provide access to the
authorized representative(s) of the licensee for installation, testing, commissioning,
reading and recording and maintenance of meters.
12. Sealing of meters. -
(1) Sealing Arrangements
(a) All meters shall be sealed by the manufacturer at its works. In addition to
the seal provided by the manufacturer at its works, the sealing of all
meters shall be done as follows at various sealing points as per the
standards given in the Schedule:
8
(i) Sealing of interface meters, shall also be done by both the supplier
and the buyer.
(ii) Sealing of consumer meters shall be done by the licensee.
(iii) Sealing of energy accounting and audit meters shall be done by the
licensee or generating company as the case may be.
(b) A tracking and recording software for all new seals shall be provided by
the manufacturer of the meter so as to track total movement of seals
starting from manufacturing, procurement, storage, record keeping,
installation, series of inspections, removal and disposal.
(c) Seal shall be unique for each utility and name or logo of the utility shall be
clearly visible on the seals.
(d) Only the patented seals (seal from the manufacturer who has official right
to manufacture the seal) shall be used.
(e) Polycarbonate or acrylic seals or plastic seals or holographic seals or any
other superior seal shall be used.
(f) Lead seals shall not be used in the new meters. Old lead seals shall be
replaced by new seals in a phased manner and the time frame of the same
shall be submitted by the licensee to the Appropriate Commission for
approval.
(2) Removal of seals from meters
(a) Interface meters
Whenever seals of the interface meters have to be removed for any reason,
advance notice shall be given to other party for witnessing the removal of seals
and resealing of the interface meter. The breaking and re-sealing of the meters
shall be recorded by the party, who carried out the work, in the meter register,
mentioning the date of removal and resealing, serial numbers of the broken and
new seals and the reason for removal of seals.
(b) Consumer meters
Seal of the consumer meter shall be removed only by the licensee. No
consumer shall tamper with, break or remove the seal under any
circumstances. Any tampering, breaking or removing the seal from the meter
shall be dealt with as per relevant provisions of the Act.
(c) Energy accounting and audit meters
Seal of the energy accounting and audit meter shall be removed only by
the generating company or the licensee who owns the meter.
9
13. Safety of meters. -
(1) The supplier or buyer in whose premises the interface meters are installed shall be
responsible for their safety.
(2) The consumer shall, as far as circumstances permit, take precautions for the safety
of the consumer meter installed in his premises belonging to the licensee.
(3) Licensee shall be responsible for the safety of the consumer meter located outside
the premises of the consumer and the consumer shall be responsible for the safety
of the real time display unit installed by the licensee in consumer premises.
(4) The generating company or the licensee who owns the energy accounting and audit
meters shall be responsible for its safety.
14. Meter reading and recording. -
(1) Interface meters
It shall be the responsibility of the Appropriate Transmission Utility or the licensee to
take down the meter reading and record the metered data, maintain database of all
the information associated with the interface meters and verify the correctness of
metered data and furnish the same to various agencies as per the procedure laid
down by the Appropriate Commission.
(2) Consumer meters
(a) It shall be the responsibility of the licensee to record the metered data, maintain
database of all the information associated with the consumer meters and verify
the correctness of metered data.
(b) The licensee shall maintain accounts for the electricity consumption and other
electrical quantities of its consumers.
(c) Brief history, date of installation and details of testing, calibration and
replacement of meters shall be maintained by the licensee.
(3) Energy accounting and audit meters
It shall be the responsibility of the generating company or licensee to record the
metered data, maintain database of all the information associated with the energy
accounting and audit meters and verify the correctness of metered data. Each
generating company or licensee shall prepare quarterly, half-yearly and yearly energy
account for its system for taking appropriate action for efficient operation and system
development.
10
15. Meter failure or discrepancies. -
(1) Interface meters
(a) Whenever difference between the readings of the Main meter and the
Check meter for any month is more than 0.5%, the following steps shall be
taken:
(i) checking of CT and VT connections;
(ii) testing of accuracy of interface meter at site with reference standard
meter of accuracy class higher than the meter under test.
If the difference exists even after such checking or testing, then the defective
meter shall be replaced with a correct meter.
(b) In case of conspicuous failures like burning of meter and erratic display of
metered parameters and when the error found in testing of meter is beyond the
permissible limit of error provided in the relevant standard, the meter shall be
immediately replaced with a correct meter.
(c) In case where both the Main meter and Check meter fail, at least one of the
meters shall be immediately replaced by a correct meter.
(d) Billing for the Failure period:
(i) The billing for the failure period of the meter shall be done as per the
procedure laid down by the Appropriate Commission.
(ii) Readings recorded by Main, Check and Standby meters for every
time slot shall be analysed, crosschecked and validated by the
Appropriate Load Despatch Centre (LDC). The discrepancies, if any,
noticed in the readings shall be informed by the LDC in writing to the
energy accounting agency for proper accounting of energy. LDC shall
also intimate the discrepancies to the Appropriate Transmission Utility
or the licensee, who shall take further necessary action regarding
testing, calibration or replacement of the faulty meters in accordance
with the provisions laid down.
(e) The defective meter shall be immediately tested and calibrated
(2) Consumer meters
In case the consumer reports to the licensee about consumer meter readings not
commensurate with his consumption of electricity, stoppage of meter, damage to
the seal, burning or damage of the meter, the licensee shall take necessary steps
as per the procedures given in the Electricity Supply Code of the Appropriate
Commission read with the notified conditions of supply of electricity.
11
(3) Energy accounting and audit meters
Energy accounting and audit meters shall be rectified or replaced by the generating
company or licensee immediately after notice of any of the following abnormalities:
(a) the errors in the meter readings are outside the limits prescribed for the
specified Accuracy Class;
(b) meter readings are not in accordance with the normal pattern of the load
demand;
(c) meter tampering, or erratic display or damage.
16. Anti-tampering features of meters. -
The meters shall be provided with such anti-tampering features as per the
Standards on Installation and Operation of Meters given in the Schedule.
17. Quality assurance of meters. -
(1) The distribution licensee shall put in place a system of quality assurance and
testing of meters with the approval of Appropriate Commission.
(2) The licensee shall set up appropriate number of accredited testing laboratories or
utilize the services of other accredited testing laboratories. The licensee shall take
immediate action to get the accreditations of their existing meter testing
laboratories from NABL, if not already done.
(3) The generating company or licensee shall ensure that all type, routine and
acceptance tests are carried out by the manufacturer complying with the
requirement of the relevant IS or BS or IEC as the case may be.
18. Calibration and periodical testing of meters. –
(1) Interface meter
(a) At the time of commissioning, each interface meter shall be tested by the owner at site
for accuracy using standard reference meter of better accuracy class than the meter
under test.
(b)All interface meters shall be tested at least once in five years. These meters shall also
be tested whenever the energy and other quantities recorded by the meter are
abnormal or inconsistent with electrically adjacent meters. Whenever there is
unreasonable difference between the quantity recorded by interface meter and the
corresponding value monitored at the billing center via communication network, the
communication system and terminal equipment shall be tested and rectified. The
meters may be tested using NABL accredited mobile laboratory or at any accredited
laboratory and recalibrated if required at manufacturer’s works.
12
(c) Testing and calibration of interface meters may be carried out in the presence of the
representatives of the supplier and buyer. The owner of the meter shall send
advance notice to the other party regarding the date of testing.
(2) Consumer meters
The testing of consumer meters shall be done at site at least once in five years. The
licensee may instead of testing the meter at site can remove the meter and replace
the same by a tested meter duly tested in an accredited test laboratory. In addition,
meters installed in the circuit shall be tested if study of consumption pattern changes
drastically from the similar months or season of the previous years or if there is
consumer’s complaint pertaining to a meter. The standard reference meter of better
accuracy class than the meter under test shall be used for site testing of consumer
meters up to 650 volts. The testing for consumers meters above 650 volts should
cover the entire metering system including CTs, VTs. Testing may be carried out
through NABL accredited mobile laboratory using secondary injection kit, measuring
unit and phantom loading or at any accredited test laboratory and recalibrated if
required at manufacturer’s works.
(3) Energy accounting and audit meters
Energy accounting and audit meters shall be tested at site at least once in five years or
whenever the accuracy is suspected or whenever the readings are inconsistent with
the readings of other meters, e.g., check meters, standby meters. The testing must be
carried out without removing the CTs and VTs connection. Testing may be carried out
through NABL accredited mobile laboratory using secondary injection kit, measuring
unit and phantom loading or at any accredited test laboratory and recalibrated if
required at manufacturer’s works.
19. Additional meters. -
In addition to any meter which may be placed for recording the electricity consumed by
the consumer, the licensee may connect additional meters, maximum demand
indicator or other apparatus as he may think fit for the purposes of ascertaining or
regulating either the quantity of electricity supplied to the consumer, or the number of
hours during which the supply is given, or the rate per unit of time at which energy is
supplied to the consumer, or any other quantity or time connected with the supply to
consumer:
Provided that the meter, indicator or apparatus shall not, in the absence of an
agreement to the contrary, be placed otherwise than between the distributing mains of
the licensee and any meter:
Provided further that, where the charges for the supply of energy depend wholly or
partly upon the reading or indication of any such meter, indicator or apparatus as
aforesaid, the licensee shall, in the absence of an agreement to the contrary, keep the
meter, indicator or apparatus correct.
13
Previous and next
Questions people ask
Is regulation 19 of Central Electricity Authority (Installation & Operation of Meters) Regulations, 2006 still in force?
No repeal of Central Electricity Authority (Installation & Operation of Meters) Regulations, 2006 is recorded.