Rule 37, Atomic Energy (Factories) Rules, 1996: WATER-SEALED GASHOLDER
Atomic Energy (Factories) Rules, 1996 - Rule 37
Text of rule 37
WATER-SEALED GASHOLDER
37. WATER-SEALED GASHOLDER.-
(1) The expression "gasholder" means a water-sealed gasholder which has a storage capacity
of not less than 140 cu.m.
(2) Every gasholder shall be of adequate material and strength, sound construction and
properly maintained.
(3) No gasholder shall be taken into use in any factory for the first time unless,
(a) information giving details of gasholder is recorded in Form 6 ;
Atomic Energy Factory Rules, 1996
45
Rule 37
(b) certificate of its internal and external examination in Form 6 is obtained either
from the manufacturer or from any person competent to conduct such
examination; and
(c) such certificate is in possession of the occupier.
(4) Where there is more than one gasholder in a factory, every gasholder shall be marked in a
conspicuous position with a distinguishing number or letter.
(5) Every gasholder shall be thoroughly examined externally by a competent person at least
once in a period of 12 months.
(6) In the case of gasholder of which any lift has been in use for more than 10 years, the
internal state of the sheeting shall, within one year of the coming into operation of these
rules and thereafter at least once in every period of four years, be examined by a
competent person by means of electronic or other accurate devices:
Provided that if the Competent Authority is satisfied that such electronic or other accurate
devices are not available, it may permit the cutting of samples from the crown and the
sides of the holder:
Provided further that if the above examination raises a doubt, an internal visual
examination shall be made.
(7) All possible steps shall be taken to prevent or minimise ingress of impurities in the
gasholder.
(8) No gasholder shall be repaired or demolished except under the direct supervision of a
person who, by his training, experience and knowledge of the necessary precautions
against risks of explosion and of persons being overcome by gas, is competent to
supervise such work.
(9) (a) All sample discs cut under sub-rule (6) above shall be kept readily available for
inspection.
(b) A permanent register in Form 6 duly signed by the occupier or manager shall be
maintained.
(c) The results of examinations by the competent person carried out as required under
sub-rules (5). and (6). above shall be recorded in Form 6.
(d) A copy of the report shall be kept in the register in Form 6 and both the register
and the report shall be readily available for inspection.
Atomic Energy Factory Rules, 1996
46
Rules 37-39
(10) The Inspector shall inspect the gasholder at least once in a period of 12 months.
Previous and next
Questions people ask
Is rule 37 of Atomic Energy (Factories) Rules, 1996 still in force?
No repeal of Atomic Energy (Factories) Rules, 1996 is recorded.