LawGrids logoLAWGRIDS.ORG

Rule 15, Tripura Fire Safety Rules 2026: RESIDUARY PROVISIONS

Tripura Fire Safety Rules 2026 - Rule 15

Text of rule 15

RESIDUARY PROVISIONS

15. RESIDUARY PROVISIONS:- In regard to such aspects of building or premise as are not covered by these rules, the respec tive provisions of the “Tripura Building Rules, 2017” for the time being in force shall be followed. Tripura Fire Safety Rules, 2026 Page 10 of 169 Fire Prevention: 1) Based on the experience in the use of the provisions of the Rule in relation to various occupancies and subdivision classification under various building occupancy types, the same has been reviewed and updated. Also, mixed occupancy and minor occupancy have been further clarified. 2) Table 1 on fire resistance ratings of structural and non-structural elements has been updated. 3) The provisions relating to fire separating walls, fire separating floors and fire partitions have been detailed. 4) Provisions of fire safety requirements of services shafts have been rationalized and updated. 5) A separate comprehensive clause on electrical power supply distribution for fire and life safety systems has been included. 6) Detailed clauses on air conditioning systems towards safety and smoke control integration have been provided. 7) Glass facade requirements have been detailed towards fire protection and smoke exhaust aspects. 8) A separate comprehensive clause on Fire Command Centre (FCC) has been introduced covering various requirements. Life Safety: 1) The components of means of egress have been comprehensively brought out covering specific aspects relating to exit access, exit and exit discharge. The relationship of occupant load, exit width requirements and travel distances have also been duly detailed enabling efficient planning for enhanced life safety provisions. The table on capacity factors has been modified based on aspect of width per person approach used globally. 2) Requirement for displaying the occupancy load for assembly buildings and call centres, has been included. 3) The concept of firefighting shaft for safe and efficient use by the fire fighters to access the floor on fire and also allow egress/evacuation of the occupants with simultaneous use of refuge area used as staging of the occupants, have been well integrated, including in the annex for high rise buildings. 4) Aspects of compartmentation with fire barrier and its passive fire safety requirements have been detailed for respective occupancies. 5) Pressurization of exits and smoke extraction requirements for respective areas including car parking have been updated with an approach towards selecting alternative means there for. 6) The clause on gas supply has been comprehensively updated. 7) The clause on fire detection and alarm system has been completely reviewed and updated as per the latest practices. Fire Protection: 1) The table on minimum requirements for firefighting installations (erstwhile Table 23 and now Table 7 specified) has been comprehensively updated. 2) Detailed provisions have been included on fire water storage, fire pump room, sprinkler system and various alternative fire suppression systems. FIRE PREVENTION, LIFE SAFETY AND FIRE PROTECTION Schedule- I [See rule 3] Tripura Fire Safety Rules, 2026 Page 11 of 169 1. FIRE PREVENTION 1. 1. Classification of Buildings Based on Occupancy 1.1.1 General Classification All buildings, whether existing or hereafter erected shall be classified according to use or the character of occupancy in one of the following groups: 1) Group A Residential 6) Group F Mercantile 2) Group B Educational 7) Group G Industrial 3) Group C Institutional 8) Group H Storage 4) Group D Assembly 9) Group J Hazardous 5) Group E Business 10) Group K Mixed use The details of each occupancy and example of buildings in each group are given in 1.1.2 to 1.1.10. 1.1.1.1 Minor occupancy This is purely incidental to operations in a main occupancy, which shall be considered as part of the main occupancy and shall be classified under the relevant group for the main occupancy. 1.1.1.2 Mixed occupancy Where two or more types of occupancies intermingle in the same building, the entire building shall be treated as mixed occupancy and the same shall comply with 1.1.12. 1.1.2 Group A Residential Buildings: These shall include any building in which sleeping accommodation is provided for normal residential purposes with or without cooking or dining or both facilities, except any building classified under Group C. Buildings and structures under Group A shall be further subdivided as follows: Subdivision A-1 Lodging and rooming houses Subdivision A-2 One or two family private dwellings Subdivision A-3 Dormitories Subdivision A-4 Apartment houses Subdivision A-5 Hotels Subdivision A-6 Starred hotels a) Subdivision A -1 Lodging and rooming houses — These shall include any building or group of buildings under the same management, in which separate sleeping accommodation on transient or permanent basis, with or without dining facilities but without cooking facilities for individuals is provided. This includes inns, clubs, motels and guest houses. Explanation — A lodging or rooming house shall be classified as a dwelling in Subdivision A-2, if no room in any of its private dwelling units is rented to more than three persons. b) Subdivision A-2 One or two family private dwellings — These shall include any private dwelling, which is occupied by members of one or two families and has a total sleeping accommodation for not more than 20 persons. If rooms in a private dwelling are rented to outsiders, these shall be for accommodating not more than three persons per room. If sleeping accommodation for more than 20 persons is provided in any one residential building, it shall be classified as a building in Subdivision A-1 or Subdivision A-4 as the case may be. Tripura Fire Safety Rules, 2026 Page 12 of 169 c) Subdivision A-3 Dormitories — These shall include any building in which group sleeping accommodation is provided, with or without dining facilities for persons who are not members of the same family, in one room or a series of closely associated rooms under joint occupancy and single management, for example, school and college dormitories, students, and other hostels and military barracks. d) Subdivision A-4 Apartment houses — These shall include any building or structure in which living quarters are provided for three or more families, living independently of each other and with independent cooking facilities, for example, apartment houses, mansions and Chawls. e) Subdivision A-5 Hotels — These shall include any building or group of buildings under single management , n which sleeping accommodation is provided, with or without dining facilities for hotels classified up to Four Star Category. f) Subdivision A-6 Starred hotels — These shall include the hotels duly approved by the concerned authorities as Five Star and above hotels. 1.1.3 Group B Educational Buildings: These shall include any building used for school, college, other training institutions involving assembly for instruction, education or recreation for not less than 20 students. Buildings and structures under Group B shall be further subdivided as follows: Subdivision B-1 Schools up to senior secondary level and Coaching Center including dance, painting, etc. Subdivision B-2 All others/training institutions a) Sub division B-1 : Schools up to senior secondary level and Coaching Center including dance, painting, etc. Schools— This subdivision shall include any building or a group of buildings under single management which is used for students not less than 20 in number. b) Subdivision B-2 All others/training institutions - This subdivision shall include any building or a group of buildings under single management which is used for students not less than 100 in number. In the case of temporary buildings/structures which are utilized for educational purposes, the provisions of 1.2.5.3 shall apply. If residential accommodation is provided in the schools/ institutions that portion of occupancy shall be classified as a building in Subdivision A-3. 1.1.4 Group C Institutional Buildings: These shall include any building or part thereof, which is used for purposes, such as medical or other treatment or care of persons suffering from physical or mental illness, disease or infirmity; care of infants, convalescents or aged persons and for penal or correctional detention in which the liberty of the inmates is restricted. Institutional buildings ordinarily provide sleeping accommodation for the occupants. Buildings and structures under Group C shall be further subdivided as follows: Subdivision C-1 Hospitals and sanatoria Subdivision C-2 Custodial institutions Subdivision C-3 Penal and mental institutions a) Subdivision C-1 Hospitals and sanatoria - This subdivision shall include any building or a group of buildings under single management, which is used for housing persons suffering from physical limitations because of health or age and those incapable of self-preservation, for example, hospitals, infirmaries, sanatoria and nursing homes. b) Subdivision C-2 Custodial institutions - This subdivision shall include any building or a group of buildings under single management, which is used for the custody and care of persons, such as children, convalescents and the aged who are incapable of self-preservation, for example, homes for the aged and infirm, convalescent homes and orphanages. c) Subdivision C-3 Penal and mental institutions - This subdivision shall include any building or a group of buildings under single management, which is used for housing persons under restraint, or who are detained for penal or corrective purposes, in which the liberty of the inmates is restricted, for example, jails, prisons, mental hospitals, mental sanatoria and reformatories. Tripura Fire Safety Rules, 2026 Page 13 of 169 1.1.5 Group D Assembly Buildings These shall include any building or part of a building, where not less than 50 persons congregate or gather for amusement, recreation, social, religious, patriotic, civil, travel and similar purposes, for example, theatres; motion picture houses; assembly halls; auditoria; exhibition halls; museums; skating rinks; gymnasiums; restaurants; places of worship; dance halls; club rooms; passenger stations and terminals of air, surface and marine public transportation services; and stadia. Buildings under Group D shall be further subdivided as follows: Subdivision D-1 Buildings having a theatrical or motion picture or any other stage and fixed seats for over 1000 persons Subdivision D-2 Buildings having a theatrical or motion picture or any other stage and fixed seats up to 1000 persons Subdivision D-3 Buildings without a permanent stage having accommodation for 300 or more persons but no permanent seating arrangement Subdivision D-4 Buildings without a permanent stage having accommodation for less than 300 persons with no permanent seating arrangement Subdivision D-5 All other structures including temporary structures designed for assembly of people not covered by Subdivisions D-1 to D-4, at ground level Subdivision D-6 Buildings having mixed occupancies of assembly and mercantile (for example, shopping malls providing facilities such as shopping, cinema theatres, multiplexes and restaurants/food courts) Subdivision D-7 Underground and elevated mass rapid transit system a) Subdivision D-1 - This subdivision shall include any building primarily meant for theatrical or operatic performances and which has a stage, proscenium curtain, fixed or portable scenery or scenery loft, lights, mechanical appliances or other theatrical accessories and equipment for example, theatres, motion picture houses, auditoria, concert halls, television and radio studios admitting an audience and which are provided with fixed seats for over 1 000 persons. b) Subdivision D-2 - This subdivision shall include any building primarily meant for use as described for Subdivision D-1, but with fixed seats up to 1000 persons. c) Subdivision D-3 - This subdivision shall include any building, its lobbies, rooms and other spaces connected thereto, primarily intended for assembly of people, but which has no theatrical stage or permanent theatrical and/or cinematographic accessories and has accommodation for 300 persons or more, for example, dance halls, night clubs, halls for incidental picture shows, dramatic, theatrical or educational presentation, lectures or other similar purposes having no theatrical stage except a raised platform and used without permanent seating arrangement; art galleries, community halls, marriage halls, places of worship, museums, lecture halls, passenger terminals and heritage and archaeological monuments, pool and billiard parlours, bowling alleys, community halls, courtrooms, gymnasiums (without spectator seating), indoor swimming pools (without spectator seating), indoor tennis courts (without spectator seating). d) Subdivision D-4 - This subdivision shall include any building primarily intended for use as described in Subdivision D-3, but with accommodation for less than 300 persons with no permanent seating arrangements. e) Subdivision D-5 - This subdivision shall include any building or structure, permanent or temporary meant for assembly of people not covered by Subdivisions D-1 to D-4, for example, grandstands, stadia, amusement park structures, reviewing stands and circus tents, arenas, external swimming pools, tennis and similar type of courts. f) Subdivision D-6 - This subdivision shall include any building for assembly of people provided with multiple services/facilities like shopping, cinema theatres, multiplexes, restaurants/food court. g) Subdivision D-7 - This subdivision shall include any building or structure like example, underground or elevated railways. 1.1.6 Group E Business Buildings These shall include any building or part thereof which is used for transaction of business for keeping of accounts and records and similar purposes, professional establishments, service facilities, etc. City halls, town halls, Tripura Fire Safety Rules, 2026 Page 14 of 169 courthouses and libraries shall be classified in this group so far as the principal function of these is transaction of public business and keeping of books and records. Buildings under Group E shall be further subdivided as follows: Subdivision E-1 Offices, banks, professional establishments, like offices of architects, engineers, doctors, lawyers, post offices and police stations Subdivision E-2 Laboratories, outpatient clinics, research establishments, libraries and test houses Subdivision E-3 Electronic data processing centres, computer installations, information technology parks and call centres Subdivision E-4 Telephone exchanges Subdivision E-5 Broadcasting stations, T.V. stations and air traffic control towers 1.1.7 Group F Mercantile Buildings These shall include any building or part thereof, which is used as shops, stores, market, for display and sale of merchandise, either wholesale or retail. Mercantile buildings shall be further subdivided as follows: Subdivision F-1 Shops, stores, departmental stores, markets (any with covered area up to 500 m2) Subdivision F-2 Shops, stores, departmental stores, markets (any with covered area more than 500 m2) Subdivision F-3 Underground shopping centres Storage and service facilities incidental to the sale of merchandise and located in the same building shall also be included under this group. 1.1.8 Group G Industrial Buildings These shall include any building or part of a building or structure, in which products or materials of all kinds and properties are fabricated, assembled, manufactured or processed, for example, assembly plants, industrial laboratories, dry cleaning plants, power plants, generating units, pumping stations, fumigation chambers, laundries, buildings or structures in gas plants, refineries, dairies and saw-mills, etc. Buildings under Group G shall be further subdivided as follows: Subdivision G-1 Buildings used for low hazard industries Subdivision G-2 Buildings used for moderate hazard industries Subdivision G-3 Buildings used for high hazard industries The hazard of occupancy, for the purpose of the NOTIFICATION, shall be the relative danger of the start and spread of fire, the danger of smoke or gases generated, the danger of explosion or other occurrences potentially endangering the lives and safety of the occupants of the buildings. Hazard of occupancy shall be determined by the Authority on the basis of the fire loads of the contents, and the processes or operations conducted in the building, provided, however, that where the combustibility of the material, the flame spread rating of the interior finish or other features of the building or structure are such as to involve a hazard greater than the occupancy hazard, the greater degree of hazard shall govern the classification. For determination of fire loads and fire load density for arriving at the classification of occupancy hazard, guidance on calorific values of some common materials is given at Annex A. A broad classification of industrial occupancies into low, moderate and high hazard classes is given at Annex B, for guidance. Any occupancy not covered in Annex B, shall be classified in the most appropriate class depending on the degree of hazard. Where different degrees of hazard of occupancy exist in different parts of a building, the most hazardous of those shall govern the classification for the purpose of this rule, except in cases where hazardous areas are segregated or protected as specified in the rule. Tripura Fire Safety Rules, 2026 Page 15 of 169 a) Subdivision G-1 - This subdivision shall include any building in which the contents are of such comparative low combustibility and the industrial processes or operations conducted therein are of such a nature that there is hardly any possibility for any self-propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source. b) Subdivision G-2 - This subdivision shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity or result in other hazardous situation and may give off a considerable volume of smoke, but from which neither toxic fumes nor explosions are to be feared in the event of fire. c) Subdivision G-3 - This subdivision shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with extreme rapidity or result in other hazardous situation or from which poisonous fumes or explosions are to be feared in the event of a fire. 1.1.9 Group H Storage Buildings These shall include any building or part of a building used primarily for the storage or sheltering (including servicing, processing or repairs incidental to storage) of goods, ware or merchandise (except those that involve highly combustible or explosive products or materials), vehicles or animals, for example, warehouses, cold storages, freight depots, transit sheds, storehouses, truck and marine terminals, garages, hangars, grain elevators, barns and stables. Storage properties are characterized by the presence of relatively small number of persons in proportion to the area. Any new use which increases the number of occupants to a figure comparable with other classes of occupancy shall change the classification of the building to that of the new use, for example, hangars used for assembly purposes, warehouses used for office purposes, garage buildings used for manufacturing. 1.1.10 Group J Hazardous Buildings These shall include any building or part thereof which is used for the storage, handling, manufacture or processing of highly combustible or explosive materials or products which are liable to burn with extreme rapidity and/or which may produce poisonous fumes or explosions for storage, handling, manufacturing or processing which involve highly corrosive, toxic or noxious alkalis, acids or other liquids or chemicals producing flame, fumes and explosive, poisonous, irritant or corrosive gases; and for the storage, handling or processing of any material producing explosive mixtures of dust which result in the division of matter into fine particles subject to spontaneous ignition. Examples of buildings in this class are those buildings which are used for, a) storage, under pressure of more than 0.1 N/mm2 and in quantities exceeding 70 m3 of acetylene, hydrogen, illuminating and natural gases, ammonia, chlorine, phosgene, sulphur dioxide, carbon dioxide, methyloxide and all gases subject to explosion, fume or toxic hazard, cryogenic gases, etc; b) storage and handling of hazardous and highly flammable liquids, liquefiable gases like LPG, rocket propellants, etc; c) storage and handling of hazardous and highly flammable or explosive materials (other than liquids); and d) manufacture of artificial flowers, synthetic leather, ammunition, explosives and fireworks. Explanation — A list of hazardous substances giving quantities, for which or exceeding which owners handling such substances are required to be covered under The Public Liability Insurance Act, 1991, has been notified under the ‘Rules on Emergency Planning, Preparedness and Response for Chemical Accidents’ by the Govt. of India, Ministry of Environment and Forests Notification No. G.S.R. 347(E) dated 01 August 1996. 1.1.11 Group K Mixed Use In case of mixed use, in so far as fire protection is concerned, all the occupancies/the entire building shall be governed by the most restrictive provisions of the NOTIFICATION among those applicable for individual occupancies. The provisions for life safety given in the NOTIFICATION for individual occupancy shall, however, apply to the respective occupancies. Exits in such mixed occupancy shall be arranged so as to ensure that means of egress is not decreased in the direction of egress travel. Tripura Fire Safety Rules, 2026 Page 16 of 169 Further, in such mixed occupancies, the occupancies are also required to be separated (horizontally and/or vertically as the case may be) by a 240 min fire resistance rating. 1.1.12 Where change in the occupancy of any building places it in a different group or in a different subdivision of the same group, such building shall be made to comply with the requirements of the NOTIFICATION for the new group or its subdivision. 1.1.13 Where the new occupancy of a building is less hazardous, based on life and fire risk, than its existing occupancy, it shall not be necessary to conform to the requirements of the NOTIFICATION for the new group or its subdivision. 1.1.14 A certificate of occupancy shall be necessary, before any change is effected in the character of occupancy of any building. 1.2 Types of Construction 1.2.1. The design of any building and the type of materials used in its construction are important factors in making the building resistant to a complete burn-out and in preventing the rapid spread of fire, smoke or fumes, which may otherwise contribute to the loss of lives and property. The fire resistance of a building or its structural and non-structural elements is expressed in minutes against a specified fire load which is expressed in kcal/m2, and against a certain intensity of fipre. The fire-resistance test for structural element shall be done in accordance with the list of standards as specified in Schedule V (2). For the purpose of the NOTIFICATION, the types of construction according to fire resistance shall be classified into four categories, namely, Type 1 Construction, Type 2 Construction, Type 3 Construction and Type 4 Construction. The minimum fire resistance ratings of structural and nonstructural members for various types of construction shall be as given in Table 1. Non-combustible materials should be used for construction of buildings, and the internal walls of staircase enclosures should be of brick work or reinforced concrete or any other material of construction with minimum of 120 min rating. The walls for the chimney shall be of Type 1 or Type 2 Construction depending on whether the flue gas temperature is above 200°C or less, respectively. 1.2.2 It is required that a structural and/or non-structural element/component shall have the requisite fire resistance rating as per Table 1. The fire resistance rating for the structural and non-structural elements shall be based on guidelines as per approved and accepted standards. The fire rating shall be validated and certified with a view to meeting the requirements of Table 1. In the absence of any validated/certified rating, guidance may be obtained from the information available in Annex C. 1.2.3 Load bearing steel beams and columns of buildings having total covered area of 500 m2 and above shall be protected against failure/collapse of structure in case of fire. This could be achieved by use of appropriate methodology using suitable fire resistance rated materials along with suppression system (see Annex C, Table 25 and Table 26). 1.2.4 The false ceiling, including all fixtures used for its suspension, shall be of non-combustible material and shall provide adequate fire resistance to the ceiling in order to prevent spread of fire across ceiling. 1.3. General Requirements of All Individual Occupancies 1.3. 1 General All buildings shall satisfy certain requirements, which contribute, individually and collectively, to the safety of life from fire, smoke, fumes and panic arising from these or similar causes. There are, however, certain general principles and common requirements, which are applicable to all or most of the occupancies. 1.3. 2 Exceptions and Deviations Exceptions and deviations to the general provisions of requirements of individual occupancies are given as applicable to each type of occupancy in 6.1 to 6.9. In case of practical difficulty or to avoid unnecessary Tripura Fire Safety Rules, 2026 Page 17 of 169 hardship, without sacrificing reasonable safety, local head, fire services may consider exemptions from the NOTIFICATION. 1.3. 3 Occupation of Buildings under Construction 1.3. 3.1 A building or portion of the building may be occupied during construction, repairs, alterations or additions only if all means of exit and fire protection measures are in place and continuously maintained for the occupied part of the building. 1.3. 3.2 A high rise building during construction shall be provided with the following fire protection measures, which shall be maintained in good working condition at all the times: a) Dry riser of minimum 100 mm diameter pipe with hydrant outlets on the floors constructed with a fire service inlet to boost the water in the dry riser and maintenance should be in accordance with the list of standards as specified in Schedule E (5). b) Drums of 2 000 litre capacity filled with water with two fire buckets on each floor; c) A water storage tank of minimum 20 000 litre capacity, which may be used for other construction purposes also. Tripura Fire Safety Rules, 2026 Page 18 of 169 1.4.4 Maximum Height, Floor Area Ratio and Open Spaces will be as per Tripura Building Rules, 2017. 1.4.4.1 Every building shall be restricted in its height above the ground level and the number of storeys, depending upon its occupancy and the type of construction. The maximum permissible height for any Tripura Fire Safety Rules, 2026 Page 19 of 169 combination of occupancy and types of construction should necessarily be related to the width of street fronting the building, or floor area ratios and the local firefighting facilities available. The building Height restriction shall be as per the “Tripura Building Rules, 2017”. Explanation — Set-back distances (according to the permissible height for each type of building as per the occupancy), width of streets providing approach to the building, permitted floor area ratio (FAR), permitted open space around or inside buildings, provision of adequate passageway and clearances required for firefighting vehicles, etc shall be strictly governed by the provisions of the Tripura Building Rules, 2017. 1.4.4.2. Floor area ratio The comparative floor area ratios for different occupancies and types of construction are given in Table 2. 1.4.4.3.The requirements of open space around the building(s) shall be in accordance with Tripura Building Rules, 2017. 1.4.5 Openings in Fire Resistant Walls and Floors 1.4.5.1 At the time of designing openings in fire resistant walls and floors, particular attention shall be paid to all such factors which limit fire spread through these openings and maintain fire rating of the structural members. 1.4.5.2 For Types 1 to 3 constructions, a doorway or opening in a fire resistant wall on any floor shall be limited to 5.6 m2 in area with a maximum height/width of 2.75 m. Every wall opening shall be protected with fire- resisting doors, having the fire rating of not less than 120 min. The openings in the floors shall be protected by vertical enclosures extending above and below such openings, such enclosures having a fire resistance of not less than 120 min and all openings therein being protected with a fire-resisting assembly as specified in 1.4.5.6. For escalator openings, the smoke spill shall be avoided by provision of smoke barrier (of 450-600 mm) thereby creating smoke compartment. Further, the protection shall be ensured through installation of sprinklers on all sides of the cut out opening on each floor (see Fig. 3 for details). 1.4.5.3 For Type 4 construction, openings in the fire separating walls or floors shall be fitted with 120 min fire- resistance rated assemblies. Tripura Fire Safety Rules, 2026 Page 20 of 169 1.4.5.4 Service ducts and shafts Openings in walls or floors which are necessary to be provided to allow passages of all building services like cables, electrical wirings, telephone cables, plumbing pipes, etc, shall be protected by enclosure in the form of ducts/shafts having a fire resistance not less than 120 min. The inspection door for electrical shafts/ducts shall be not less than 120 min. Further, medium and low voltage wiring running in shafts/ducts, shall either be armoured type or run through metal conduits. The space between the electrical cables/conduits and the walls/slabs shall be filled in by a fire stop material having fire resistance rating of not less than 120 min. This shall exclude requirement of fire stop sealing for low voltage services shaft. For plumbing shafts in the core of the building, with shaft door opening inside the building, the shafts shall have inspection doors having fire resistance rating not less than 30 min. Tripura Fire Safety Rules, 2026 Page 21 of 169 For plumbing shafts doors which open in wet areas or in naturally ventilated areas or on external wall of the building, the shafts may not require doors having any specified fire rating. Explanation — In the case of buildings where it is necessary to lower or lift heavy machinery or goods from one floor to the other, it may be necessary to provide larger openings in the floor. Such openings shall be provided with removable covers which shall have the same strength and fire resistance as the floor. 1.4.5.5 Refuse chutes Refuse chutes, if any provided in a building, shall have opening at least 1 m above roof level for venting purpose and they shall have an enclosure wall of non-combustible material with fire resistance of not less than 120 min. They shall not be located within the staircase enclosure or service shafts, or air conditioning shafts. Refuse chutes inspection panel and doors shall be tight fitting with 60 min fire resistance. Sprinkler protection system shall be provided for the refuse chutes. Refuse chutes shall be at least 6 m away from exits. 1.4.5.6 Vertical opening Every vertical opening between the floors of a building shall be suitably enclosed or protected, as necessary, to provide the following: a) Reasonable safety to the occupants while using the means of egress by preventing spread of fire, smoke, or fumes through vertical openings from floor to floor to allow occupants to complete their use of the means of egress. Further it shall be ensured to provide a clear height of 2 100 mm in the exit access. b) Limitation of damage to the building and its contents. 1.4.6 Electrical Installation 1.4.6.1 For requirements regarding electrical installations from the point of view of fire safety, reference may be made to good practice in accordance with the list of standards as specified in Schedule V (6) and Section 2 Electrical and Allied Installations’ of the NOTIFICATION. In general, it is desirable that the wiring and cabling are with flame retardant property. Medium and low voltage wiring running in shafts, and within false ceiling shall run in metal conduit. Any 230 V wiring for lighting or other services, above false ceiling, shall have 660 V grade insulation. The electric distribution cables/wiring shall be laid in a separate shaft. The shaft shall be sealed at every floor with fire stop materials having the same fire resistance as that of the floor. High, medium and low voltage wiring running in shaft and in false ceiling shall run in separate shaft/conduits. Water mains, gas pipes, telephone lines, intercom lines or any other service line shall not be laid in the duct for electrical cables; use of bus ducts/solid rising mains instead of cables is preferred. All metallic items like steel structural members, etc, shall be bonded properly to the earthing system. 1.4.6.2 Emergency power for fire and life safety systems Emergency power supplying distribution system for critical requirement for functioning of fire and life safety system and equipment shall be planned for efficient and reliable power and control supply to the following systems and equipment where provided: a) Fire pumps. Tripura Fire Safety Rules, 2026 Page 22 of 169 b) Pressurization and smoke venting; including its ancillary systems such as dampers and actuators. c) Fireman’s lifts (including all lifts). d) Exit signage lighting. e) Emergency lighting. f) Fire alarm system. g) Public address (PA) system (relating to emergency voice evacuation and annunciation). h) Magnetic door hold open devices. j) Lighting in fire command centre and security room. Power supply to these systems and equipment shall be from normal and emergency (standby generator) power sources with changeover facility. If power supply, is from HV source and HV generation, the transformer should be planned in standby capacity to ensure continuity of power to such systems. Wherever transformers are installed at higher levels in buildings and backup DG sets are of higher voltage rating, then dual redundant cables shall be taken to all transformers. The generator shall be capable of taking starting current of all the fire and life safety systems and equipment as above. Where parallel HV/LV supply from a separate substation fed from different grid is provided with appropriate transformer for emergency, the provision of generator may be waived in consultation with the Authority. The power supply to the panel/distribution board of these fire and life safety systems shall be through fire proof enclosures or circuit integrity cables or through alternate route in the adjoining fire compartment to ensure supply of power is reliable to these systems and equipment. It shall be ensured that the cabling from the adjoining fire compartment is protected within the compartment of vulnerability. The location of the panel/ distribution board feeding the fire and life safety system shall be in fire safe zone ensuring supply of power to these systems. Circuits of such emergency system shall be protected at origin by an automatic circuit breaker with its no-volt coil removed. Master switches controlling essential service circuits shall be clearly labelled. Cables for fire alarm and PA system shall be laid in metal conduits or armoured to provide physical segregation from the power cables. 1.4.6.3 Substation/Transformers Areas in substation shall not be used as storage/dump areas or for other utility purposes other than those required for the functioning of the substation. The substation area should be adequately ventilated. An independent, ventilated or air conditioned MV panel room shall be provided on the ground level or first basement. This room shall be provided with access from outside (or through exit passageway accessible from outside). The MV panel room shall be provided with fire resistant walls and doors of fire resistance of not less than 120 min. If the licensees agree to provide meters on upper floors, the licensees’ cables shall be segregated from consumers’ cables by providing a partition in the shaft. Meter rooms on upper floors shall not open into staircase enclosures and should be ventilated directly to open air outside or in electrical room of 120 min fire resistant walls. Electrical MV main distribution panel and lift panels shall be provided with CO2/inert gas flooding system for all panel compartments with a cylinder located beside the panel. 1.4.6.3.1 Oil filled substation Tripura Fire Safety Rules, 2026 Page 23 of 169 A substation or a switch-station with oil filled equipment shall be limited to be installed in utility building or in outdoor location. Such substation/utility building shall be at least 7 m away from the adjoining building(s). Substation equipment (exceeding oil capacity of 2000 litre) in utility building shall have fire rated baffle walls of 240 min rating constructed between such equipment, raised to at least 600 mm above the height of the equipment (including height of oil conservators) and exceeding 300 mm on each side of the equipment. All transformers where capacity exceeds 10 MVA shall be protected by high velocity water spray systems or nitrogen injection system. 1.4.6.3.2 Dry type substation Transformers located inside a building shall be of dry type and all substation/switch room walls, ceiling, floor, opening including doors shall have a fire resistance rating of 120 min. Access to the substation shall be provided from the nearest fire exit/exit staircase for the purpose of electrical isolation. 1.4.6.4 Standby supply Diesel generator set(s) shall not be installed at any floor other than ground/first basement. If the same are installed indoors, proper ventilation and exhaust shall be planned. The DG set room shall be separated by 120 min fire resistance rated walls and doors. The oil tank for the DG sets (if not in the base of the DG) shall be provided with a dyked enclosure having a volumetric capacity of at least 10 percent more than the volume of the oil tank. The enclosure shall be filled with sand for a height of 300 mm. For detailed information regarding fire safety requirements for hazardous petroleum products, reference may be made to The Petroleum Act, 1934 and the Rules framed the reunder. 1.4.6.5 Lightning protection o buildings Routing of down conductors (insulated or un insulated) of lightning protection through electrical or other service shafts are not allowed as it can create fire and explosion during lightning.. 1.4.7 Escape Lighting and Exit Signage Exit access, exits and exit discharge shall be properly identified, with adequate lighting maintained in the elements of the egress systems so that all occupants shall be able to leave the facility safely. 1.4.7.1 Lighting a) The exit, exit access and exit discharge systems shall be illuminated continuously. The floors of the means of egress shall be illuminated at all points, including angles and intersections, in corridors and passageways, stairwells, landings of stairwells and exit. b) Emergency lighting shall be powered from a source independent of that supplying the normal lighting. c) Escape lighting shall be capable of, 1) indicating clearly and unambiguously the escape routes; 2) providing adequate illumination along such routes to allow safe movement of persons towards and through the exits; and 3) ensuring that fire alarm call points and firefighting equipment provided along the escape routes can be readily located. d) The horizontal luminance at floor level on the centre line of an escape route shall not be less than 10 lumen/m2. In addition, for escape routes up to 2 m wide, 50 percent of the route width shall be lit to a minimum Tripura Fire Safety Rules, 2026 Page 24 of 169 of 5 lumen/m2. In auditoriums, theatres, concert halls and such other places of assembly, the illumination of floor exit/access may be reduced during period of performances to values not less than 2 lux. e) Required illumination shall be arranged such that the failure of any single lighting unit, such as the burning out of one luminaire, will not leave any area in darkness and does not impede the functioning of the system further. f) The emergency lighting shall be provided to be put on within 5 s of the failure of the normal lighting supply. Also, emergency lighting shall be able to maintain the required illumination level for a period of not less than 90 min in the event of failure of the normal lighting even for smaller premises. g) Battery pack emergency lighting, because of its limited duration and reliability, shall not be allowed to be used in lieu of a diesel engine driven emergency power supply. h) Escape lighting luminaires should be sited to cover the following locations: 1) Near each intersection of corridors, 2) At exits and at each exit door, 3) Near each change of direction in the escape route, 4) Near each staircase so that each flight of stairs receives direct light, 5) Near any other change of floor level, 6) Outside each final exit and close to it, 7) Near each fire alarm call point, 8) Near firefighting equipment, and 9) To illuminate exit and safety signs as required by the enforcing authority. Note — For the purpose of this clause ‘near’ is normally considered to be within 2 m measured horizontally. j) The luminaires shall be mounted as low as possible, but at least 2 m above the floor level. k) Signs are required at all exits, emergency exits and escape routes, which should comply with the graphic requirements of the relevant Indian Standards. 1.4.7.2 Exit passageway (at ground) and staircase lighting shall also be connected to alternative supply. The alternative source of supply may be provided by battery continuously trickle charged from the electric mains. 1.4.7.3 Suitable arrangements shall be made by installing double throw switches to ensure that the lighting installed in the staircase and the corridor does not get connected to two sources of supply simultaneously. Double throw switch shall be installed in the service room for terminating the stand-by supply. The emergency lighting system shall be well maintained by periodical inspections and tests so as to ensure their perfect serviceability at all times. 1.4.7.4 Exit signage Where exit access is provided through corridors/paths, the occupants shall be able to easily identify the way to exits. Exit signs shall be provided such that no point in an exit access is more than 30 m from a visible exit directional sign. An exit sign indicating the direction to an exit shall be provided at all changes in direction. Exits shall be clearly visible and the route to reach the exits shall be clearly marked and signs posted to guide the occupants of the floor concerned. Signs shall be illuminated and wired to an independent electrical circuit on an alternative source of supply. The sizes and colours of the exit signs shall be in accordance with good practice in accordance with the list of standards as specified in Schedule E (7). The colour of the exit signs shall be green. Note — This provision shall not apply to A-2 and A-4 occupancies less than 15 m in height. The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be so installed that no mechanical damage shall occur to them due to moving of furniture or other Tripura Fire Safety Rules, 2026 Page 25 of 169 heavy equipment. Further, all landings of floor shall have floor indicating boards prominently indicating the number of the floor. Photo luminescent markings shall be pasted at internal hydrant boxes. 1.4.8 Air Conditioning, Ventilation and Smoke Control 1.4.8.1 Air conditioning and mechanical ventilation requirements of different rooms or areas in any occupancy shall be as given in Part 8 ‘Building Services, Section 1 Lighting and Natural Ventilation’ and ‘Section 3 Air conditioning, Heating and Mechanical Ventilation’ of the Notification. Air conditioning and ventilating systems shall be so installed and maintained as to minimise the danger of spread of fire, smoke or fumes from one floor to other or from outside to any occupied building or structure. Many high-rise buildings integrate smoke management systems into their conventional HVAC systems. In such installation, it requires special design considerations, including safe and adequate controls, acceptable and documented testing and regular maintenance systems. Wherever batteries are provided, the same shall be segregated by 120 min fire rated construction. Ventilation to the room shall be provided as per manufacturer’s instructions. 1.4.8.2 Air handling unit 1.4.8.2.1 From fire safety point of view, separate air handling units (AHU) for each floor shall be provided so as to avoid the hazards arising from spread of fire and smoke through the air conditioning ducts. The air ducts shall be separate from each AHU to its floor and in no way shall interconnect with the duct of any other floor. Within a floor it would be desirable to have separate air handling unit provided for each compartment. Air handling unit shall be provided with effective means for preventing circulation of smoke through the system in the case of a fire in air filters or from other sources drawn into the system, and shall have smoke sensitive devices for actuation in accordance with the accepted standard [4(8)] and control. 1.4.8.2.2 Shafts or ducts, if penetrating multiple floors, shall be of masonry construction with fire damper in connecting ductwork or shall have fire rated ductwork with fire dampers at floor crossing. Alternatively, the duct and equipment may be installed in room having walls, doors and fire damper in duct exiting/entering the room of 120 min fire resistance rating. Such shafts and ducts shall have all passive fire control meeting 120 min fire resistance rating requirement to meet the objective of isolation of the floor from spread of fire to upper and lower floors through shaft/duct work. Explanation — Zoned and compartmented HVAC systems are encouraged with an approach to avoid common exhaust shafts and fresh air intake shafts which will limit the requirement of such passive measure and fire rated duct work and dampers. 1.4.8.2.3 The air filters of the air handling units shall be made of non-combustible materials. 1.4.8.2.4 The air handling unit room shall not be used for storage of any combustible materials. 1.4.8.3 Duct work 1.4.8.3.1 Air ducts serving main floor areas, corridors, etc, shall not pass through the exits/exit passageway/ exit enclosure. Exits and lift lobbies, etc, shall not be used as return air passage. 1.4.8.3.2 As far as possible, metallic ducts shall be used even for the return air instead of space above the false ceiling. Tripura Fire Safety Rules, 2026 Page 26 of 169 1.4.8.3.3 Wherever the ducts pass through fire walls or floors, the opening around the ducts shall be sealed with materials having fire resistance rating of the compartment. Such duct shall also be provided with fire dampers at all fire walls and floors unless such ducts are required to perform for fire safety operation; and in such case fire damper may be avoided at fire wall and floor while integrity of the duct shall be maintained with 120 min fire resistance rating to allow the emergency operations for fire safety requirements. 1.4.8.3.4 The ducting within compartment would require minimum fire resistance rating of 30 min. Such ducting material in substantial gauge shall be in accordance with good practice in accordance with the list of standards as specified in Schedule E (9). If such duct crosses adjacent compartment/floor and not having fire dampers in such compartment/floor, it would require fire resistance duct work rating of 120 min. The requirements of support of the duct shall meet its functional time requirement as above. 1.4.8.3.5 The materials used for insulating the duct system (inside or outside) shall be of non-combustible type. Any such insulating material shall not be wrapped or secured by any material of combustible nature. 1.4.8.3.6 Inspection panels shall be provided in the ductwork to facilitate the cleaning accumulated dust in ducts and to obtain access for maintenance of fire dampers. 1.4.8.4 Fire or fire/smoke dampers 1.4.8.4.1 These dampers shall be evaluated to be located in supply air ducts, fresh air and return air ducts/ passages at the following points: a) At the fire separation wall, b) Where ducts/passages enter the vertical shaft, c) Where the ducts pass through floors, and d) At the inlet of supply air duct and the return air duct of each compartment on every floor. 1.4.8.4.2 Damper shall be of motorized type/fusible link. Damper shall be so installed to provide complete integrity of the compartment with all passive fire protection sealing. Damper should be accessible to maintain, test and also replace, if so required. Damper shall be integrated with Fire Alarm Panel and shall be sequenced to operate as per requirement and have interlocking arrangement for fire safety of the building. Manual operation facilities for damper operation shall also be provided. 1.4.9 Heating 1.4.9.1 Installation of chimney and heating apparatus shall be in accordance with good practice in accordance with the list of standards as specified in Schedule E (10). 1.4.9.2 Boiler rooms 1.4.9.2.1 Provisions of boiler and boiler rooms shall conform to The Boilers Act, 1923. 1.4.9.2.2 Further, the following additional aspects may be taken into account in the location of boiler room: a) The boilers shall be installed in a fire resisting room of 180 min fire resistance rating. b) Entry to this room shall be provided with a composite door of 120 min fire resistance rating. c) The boiler room shall be provided with its dedicated natural or mechanical ventilation system. Mechanical ventilation system for the boiler room would be accepted with 120 min fire resistance rating ductwork, if it has interface with other mechanical areas. Ventilation system should not be allowed to be routed through electrical room area or through exit corridor/exits. Tripura Fire Safety Rules, 2026 Page 27 of 169 d) The oil tank for the boiler shall be provided with a dyked enclosure having a volumetric capacity of at least 10 percent more than the volume of the oil tank. The enclosure shall be filled with sand for a height of 300 mm. 1.4.10 Glazing 1.4.10.1 The glazing shall be in accordance with Part 6 ‘Structural Design, Section 8 Glass and Glazing’ of the NOTIFICATION. The entire glazing assembly shall be rated to that type of construction as given in Table 1. This shall be applicable along with other provisions of this Part related to respective uses as specified therein. The use of glass shall not be permitted for enclosures of exits and exit passageway. 1.4.10.2 Glass facade shall be in accordance with the following: a) For fully sprinklered buildings having fire separation of 9 m or more, tempered glass in a non-combustible assembly, with ability to hold the glass in place, shall be provided. It shall be ensured that sprinklers are located within 600 mm of the glass facade providing full coverage to the glass. Explanation — In case of all other buildings, fire resistance rating of glass facade shall be in accordance with Table 1. b) All gaps between floor-slabs and facade assembly shall be sealed at all levels by approved fire resistant sealant material of equal fire rating as that of floor slab to prevent fire and smoke propagation from one floor to another. c) Openable panels shall be provided on each floor and shall be spaced not more than 10 m apart measured along the external wall from centre-to-centre of the access openings. Such openings shall be operable at a height between 1.2 m and 1.5 m from the floor, and shall be in the form of openable panels (fire access panels) of size not less than 1 000 mm x 1 000 mm opening outwards. The wordings, ‘FIRE OPENABLE PANEL — OPEN IN CASE OF FIRE, DO NOT OBSTRUCT’ of at least 25 mm letter height shall be marked on the internal side. Such panels shall be suitably distributed on each floor based on occupant concentration. These shall not be limited to cubicle areas and shall be also located in common areas/corridors to facilitate access by the building occupants and fire personnel for smoke exhaust in times of distress. 1.4.11 Surface Interior Finishes 1.4.11.1 The use of combustible surface finishes on walls (including facade of the building) and ceilings affects the safety of the occupants of a building. Such finishes tend to spread the fire and even though the structural elements may be adequately fire resistant, serious danger to life may result. It is, therefore, essential to have adequate precautions to minimise spread of flame on wall, facade of building and ceiling surfaces. The finishing materials used for various surfaces and decor shall be such that it shall not generate toxic smoke/fumes. 1.4.11.2 The susceptibility of various types of wall surfaces to fire is determined in terms of the rate of spread of flame. Based on the rate of spread of flame, surfacing material shall be considered as divided into four classes as follows {see also good practice in accordance with the list of standards as specified in Schedule E (11)}: a) Class 1 Surfaces of very low flame spread. b) Class 2 Surfaces of low flame spread. c) Class 3 Surfaces of medium flame spread. d) Class 4 Surfaces of rapid flame spread. 1.4.11.3 The uses for which surface materials falling into various classes shall be adopted in building construction are given below: Tripura Fire Safety Rules, 2026 Page 28 of 169 Class 1 Class 2 Class 3 May be used in any situation May be used in any situation, except on walls, facade of the building, staircase and corridors May be used only in living rooms and bed rooms (but not in rooms on the roof) and only as a lining to solid walls and partitions; not on staircases or corridors or facade of the building. Explanation — Panelling (lining) shall be permitted in a limited area. It shall not be permitted in a vestibule. 1.4.11.4 Materials of Class 4 which include untreated wood fiberboards may be used with due fire retardant treatment as ceiling lining, provided the ceiling is at least, 2.4 m from the top surface of the floor below, and the wall surfaces conform to requirements of class [see Note under 1.4.11.3]. Class 4 materials shall not be used in kitchens, corridors and staircases. Some materials contain bitumen and, in addition to risk from spread of fire, emit dense smoke on burning; such materials shall be excluded from use under these conditions and shall also not be used for construction of ceiling where the plenum is used for return air in air conditioned buildings. 1.4.11.5. When frames, walls, partitions or floors are lined with combustible materials, the surfaces on both sides of the materials shall conform to the appropriate class, because there is considerable danger from fire starting and rapidly spreading within the concealed cavity unknown to the occupants whose escape may be hampered thereby. For detailed information on materials and details of construction with their fire resistance rating, reference may be made to good practice in accordance with the list of standards as specified in Schedule E (12). 1.4.12 Fire Command Centre (FCC) a) Fire command centre shall be on the entrance floor of the building having direct access. The control room shall have the main fire alarm panel with communication system (suitable public address system) to aid floors and facilities for receiving the message from different floors. b) Fire command centre shall be constructed with 120 min rating walls with a fire door and shall be provided with emergency lighting. Interior finishes shall not use any flammable materials. All controls and monitoring of fire alarm systems, pressurization systems, smoke management systems shall happen from this room. Monitoring of integrated building management systems, CCTVs or any other critical parameters in building may also be from the same room. c) Details of all floor plans along with the details of firefighting equipment and installations (2 sets laminated and bound) shall be maintained in fire command centre. d) The fire staff in charge of the fire command centre shall be responsible for the maintenance of the various services and firefighting equipment and installations in coordination with security, electrical and civil staff of the building Tripura Fire Safety Rules, 2026 Page 29 of 169 2. LIFE SAFETY 2.1 General Every building shall be so designed, constructed, equipped, maintained and operated as to provide adequate means of egress to avoid undue danger to the life and safety of the occupants from fire, smoke, fumes or panic during the time period necessary for escape. For high occupancy areas, it may be required to have annunciation, announcements and voice guided/aided system to direct the occupants towards safe egress routes, areas of comparative safety or exits, and to avoid situation of panic during distress. Every main occupancy may have certain occupancies which may be incidental to the main occupancy. The exit requirements pertaining to such incidental occupancies from the floor of the occupancy to the level of exit discharge shall be calculated to meet the requirement of the actual occupancy of such type, to ensure adequate means of egress of the occupants. 2.1.1. REQUIREMENTS FOR ACCESSIBILITY IN BUILT ENVIRONMENT FOR ELDERS AND PERSONS WITH DISABILITIES 2.1.1.1 These requirements deal with barrier free access to, movement within and around buildings, by the elderly persons and persons with disabilities who may have non-ambulatory disabilities, ambulatory disabilities, sight disabilities, hearing disabilities, disabilities of in coordination, ageing, allergies, heart and lung diseases, epilepsy, haemophilia, incontinence, enterostomy, etc. It is intended to make all buildings and facilities used by the public accessible to, and usable by all people including those living with disabilities and may include those with inability to walk or difficulty in walking, reliance on walking/mobility aids, blindness and visual impairments, speech and hearing impairments, in coordination of motor movements, reaching and manipulation, lack of stamina, difficulty in interpretation and reacting to sensory information and extremes in physical sizes. It supplements the general requirements of this Part of the Rule, and reflects greater concern for safety of life and limb of every resident irrespective of age, gender or abilities. 2.1.1.2 These requirements apply to all buildings and facilities open to and used by the public. These shall also apply to all forms of public housing by the government/civic bodies or private developers. It does not apply to private residences. For extent of application of requirements covered under 2.1.1. to different building occupancy types, reference shall be made to 2.1.5. 2.1.1.3 The reference to the accessibility needs of persons with disabilities, made in this Part shall also mean a reference to such needs of the elderly persons, children and persons of too short stature in so far as the concerned provision is applicable to the type of disabilities that may be associated therewith. 2.1.2 For the purpose of this clause, the following definitions shall apply. 2.1.2.1 Ability identifiable human attribute, including but not exclusively, to walk, to speak, to hear, to see, to feel by touch, to taste, to understand, and to recognize. 2.1.2.2 Access Aisle An accessible pedestrian space between elements, such as parking spaces, seating and desks, that provides clearances appropriate for use of the elements 2.1.2.3 Accessible Site, Building, Facility or Portions A site, building, facility, or portions thereof that complies with the requirements given in this clause to which people, regardless of their disability, age or gender are able to gain access to, in to them, to use them and exit from them with dignity. Explanation - Accessibility includes ease of independent approach, entry, evacuation and/or use of a building and its services and facilities, by all of the building’s potential users with an assurance of individual health, safety and welfare during the course of those activities. Tripura Fire Safety Rules, 2026 Page 30 of 169 2.1.2.4 Accessible Route A continuous unobstructed path connecting all accessible elements and spaces in a building or facility that may be negotiated by a person with disability using a wheelchair and that is also safe for and usable by persons with other disabilities. Interior accessible routes may include corridors, ramps, elevators, lifts, and clear floor space at fixtures. Exterior accessible routes may include parking, access aisles, kerb ramps, walkways, pathways, footpaths/sidewalks, and ramps. 2.1.2.5 Accessible Toilet A compartment having the basic requirements of minimum clear spaces, water closet, washbasin and other essential washroom accessories as required by people with non-ambulatory disabilities. There are also toilets for ambulant disabled which provide accessibility for convenient use by persons with ambulatory disabilities. 2.1.2.6 Ageing Those manifestations of the ageing processes that significantly reduce mobility, flexibility, coordination, and perceptiveness but are not accounted for in disability categories mentioned elsewhere in this Part. 2.1.2.7 Area of Rescue Assistance Building space directly adjoining, and visible from, a main vertical evacuation route, robustly and reliably protected from heat, smoke and flame during and after a fire, where people can temporarily wait with confidence for further information, instructions, and/or rescue assistance, without obstructing or interfering with the evacuation travel of other building users. Explanation - ‘Robust’ means structurally hardened and resistant to mechanical damage during the fire and for a period of time afterwards, that is, the cooling phase. 2.1.2.8 Assistive Product/Device Product/device especially produced or generally available, for preventing, compensating for, monitoring, relieving or neutralizing impairments, activity limitations and participation restrictions. 2.1.2.9 Assisted Evacuation Strategy that exists during which a designated person or persons provide assistance, during an emergency, to another person to leave a building or a specific part of the built environment and to reach a final place of safety. 2.1.2.10 Automatic Door A door equipped with a power operated mechanism and controls that open and close the door automatically upon receipt of a momentary signal. The switch that begins the automatic cycle may be photoelectrical device, floor mat, sensing device, or manual switch mounted on or near the door itself. 2.1.2.11 Circulation Path An exterior or interior way of passage from one place to another for pedestrians, including walkways, pathways, hallways, courtyards, stairways and stair landings. 2.1.2.12 Circulation Space Unobstructed space necessary for access to, into and within and egress from any part of the built environment. 2.1.2.13 Clear Unobstructed. 2.1.2.14 Colour Contrast The difference in colour that makes an object (or its representation in an image or display) distinguishable. It is determined by the difference in the colour of the object and other objects within the same field of view. Distinguishing one form/object from another by hue is the most basic and easily understood contrast. Explanation- The basic guidelines for making effective colour choices are based on the hue value of the colours. The most commonly used methods of achieving colour contrast incorporate either harmonizing or contrasting colour combinations. Contrast of hue is what relates most directly to the colour wheel combinations. The further away from each other two colours are, the higher the contrast. This means that the complementary colour combination has the highest contrast, while the analogous combination has the lowest. 2.1.2.15 Disability An umbrella term for impairments, activity limitations, and participation restrictions, denoting the negative aspects of the interaction between an individual (with a health condition) and that individual ’s contextual factors(environmental and personal factors). Disability is neither simply a biological nor a social phenomenon but arises from the relationship between health condition and context. 2.1.2.16 Grab Bars A bar used to give a steadying or stabilizing assistance to a person engaged in a particular function. 2.1.2.17 Handrails A rail used in circulation areas such as corridors, passageways, ramps and stairways to assist in continuous movement. Tripura Fire Safety Rules, 2026 Page 31 of 169 2.1.2.18 Hue Attribute of visual sensation which has given rise to colour names, such as, blue, green, yellow, red and purple. Explanation- People with normal colour vision report that hues follow a natural sequence based on their similarity to one another. With most colour deficits, the ability to discriminate between colours on the basis of hue is diminished. 2.1.2.19 Impairment Limitation in body function or structure such as a significant deviation or loss which can be temporary due, for example to injury, or permanent, slight or severe and can fluctuate over time, in particular, deterioration due to ageing. Explanation- Body function can be a physiological or psychological function of a body system; body structure refers to an anatomic part of the body such as organs, limbs and their components. 2.1.2.20 International Symbol of Accessibility (Pic. 1) consisting of a square overlaid with a stylized image of a person using a wheelchair. The symbol is often provided where access has been improved, particularly for wheelchair users and other mobility impaired persons. The symbol denotes a barrier free environment, to help older people, parents with prams and travellers with luggage besides persons with disabilities. The wheelchair symbol is always facing to the right. The international symbol of accessibility shall be replicated consistently in all wheelchair signage. The preferred colour is navy blue with white lettering. Graphical symbols should be used in conjunction with building signage system, wherever possible. Graphical symbols shall be highly contrasted with a minimum difference in Light Reflectance Value (LRV) of 70 points and properly illuminated. They shall be used on guides and directional signage. Graphical symbols on directional and door signs should be tactile, and should be accompanied by raised lettering and Braille. Signs above a height of 1600 mm do not need to be tactile, nor to include raised lettering or Braille information. The size of graphical symbols is dependent on the viewing distance (D). The minimum size of the inner outline of the frame of graphical symbols (s) can be derived from formula s = 0.09 D, applicable for a viewing distance of 1000 mm to 10000 mm. 2.1.2.21 Kerb A side barrier to a trafficable surface or the edge where a raised sidewalk/footpath, road median, or road shoulder meets an unraised street or other roadway. 2.1.2.22 Kerb Ramp A short ramp cutting through a kerb or built up to it. 2.1.2.23 Knurled Surface Roughened area, often in a crisscross pattern; used on grab bars to improve grasp and to prevent slipping. 2.1.2.24 Landing A platform or part of a floor structure at the end of a flight of stairs or a ramp or at the entrance to a lift car. https://www.google.com/search?q=Light+Reflectance+Value&oq=LRV&gs_lcrp=EgZjaHJvbWUqDQgAEAAYgwEYsQMYgAQyDQgAEAAYgwEYsQMYgAQyBwgBEAAYgAQyBwgCEAAYgAQyBwgDEAAYgAQyBwgEEAAYgAQyBwgFEAAYgAQyDwgGEC4YChjHARjRAxiABDIHCAcQABiABDIHCAgQABiABDIHCAkQABiABNIBCDE1MzZqMGo3qAIIsAIB8QVIKjdjBOdlog&sourceid=chrome&ie=UTF-8&ved=2ahUKEwj4ntDdz6KTAxVYTWwGHZRgDJMQgK4QegQIARAD https://www.google.com/search?q=Light+Reflectance+Value&oq=LRV&gs_lcrp=EgZjaHJvbWUqDQgAEAAYgwEYsQMYgAQyDQgAEAAYgwEYsQMYgAQyBwgBEAAYgAQyBwgCEAAYgAQyBwgDEAAYgAQyBwgEEAAYgAQyBwgFEAAYgAQyDwgGEC4YChjHARjRAxiABDIHCAcQABiABDIHCAgQABiABDIHCAkQABiABNIBCDE1MzZqMGo3qAIIsAIB8QVIKjdjBOdlog&sourceid=chrome&ie=UTF-8&ved=2ahUKEwj4ntDdz6KTAxVYTWwGHZRgDJMQgK4QegQIARAD Tripura Fire Safety Rules, 2026 Page 32 of 169 2.1.2..25 Light Reflectance Value (LRV) The total quantity of visible light reflected by a surface at all wavelengths and directions when illuminated by a light source. 2.1.2.26 Manoeuvring Zone The minimum three dimensional space within which it is feasible to complete a manoeuvre needed to gain access to a specific facility, component or fitting, in particular while using a wheelchair or a walking aid. 2.1.2.27 Ramp: The construction, in the form of an inclined plane that is steeper than or equal to 1:20 (5 percent) from the horizontal, together with any intermediate landing, that makes it possible to pass from one level to another more easily and safely. A ramp is a sloping pathway leading from one level to another. Ramps of an appropriate design shall be provided at all changes in level other than those served by an accessible lift or accessible lifting mechanism accommodating the specific requirements of persons with disabilities. 2.1.2.28 Operable Parts: A part of a piece of equipment or appliance used to insert or withdraw objects, or to activate, deactivate, or adjust the equipment or appliance (for example coin slot, push button, handle, etc). 2.1.2.29 Persons with Disabilities: A person with any physical, mental, intellectual or sensory impairment which in interaction with various barriers may hinder full and effective participation in society on an equal basis with others. 2.1.2., Room alcove, courtyard, or lobby). 2.1.2.31 Tactile: That relating to perception using the sense of touch. Explanation- It relates to information and interpretations derived from the sense of touch. This involves sensory transfer through physical contact of the hands or feet with other surfaces, as well as sensory transfers received by contact with non-physical elements such as pressure, wind and temperature. 2.1.2.32 Tactile Ground Surface Indicators Indicators profiled paving surface with visual contrast criteria to enable a person with impaired sight using a long cane, underfoot or visual identification to detect a specific route (guiding pattern) or the presence of a hazard (attention pattern). These are also called tactile tiles or tactile walking surface indicators. Explanation- These indicators which provide a distinctive surface pattern of strips and truncated domes or cones (small domes or cones that have had their tops cut off, or truncated) are used to guide/alert persons with vision impairments of their approach to facilities, streets and hazardous drop-offs. People who are blind or visually impaired are alerted of impending danger from vehicle impact or a grade change. 2.1.2.33 Tactile Guiding Blocks Tiles of size 300 mm × 300 mm that incorporate flat topped bars 5 mm (± 0.5 mm) high, 20 mm wide and spaced 50 mm from the centre of one bar to the centre of the next, and are easily detectable underfoot by persons with visual impairments. They are used externally to guide people with visual impairments along the circulation path. They may also be used internally in large busy areas such as railway stations and airports. 2.1.2.34 Tactile Warning Blocks Tiles of size 300 mm × 300 mm that incorporate rows of 5 mm (± 0.5 mm) high flat topped blister like domes that are easily detectable underfoot by persons with visual impairments, recognized as a sign of approaching hazards. These are placed along the approach path to unavoidable obstacles and hazards to warn persons with visual impairments of the approaching danger or level change. 2.1.2.35 Tactile Signs Tactile signage incorporates raised text or symbols to enable touch reading by people who are blind, and touch enhancement of visual perception for people who are vision impaired. 2.1.2.36 Unobstructed Width Free unobstructed space necessary for passage through a doorway, along a passageway, or other route element (for example stairway). 2.1.2.37 Unobstructed Width, Door Available width for passage through a door opening, clear of all obstructions, measured when the door is opened 90°, or when a sliding or folding door is opened to its fullest extent 2.1.2.38 Unisex Accessible Toilet Accessible toilets that can be used by both sexes. Explanation- Unisex accessible toilets allow the greatest flexibility for people who require assistance. 2.1.2.39 Universal Design The design of products and environments to be usable by all people, to the greatest extent possible, without the need for adaptation or specialized design. 2.1.2.40 Visual Contrast Visual perception between one element of a building and another. This can be produced by a difference in light reflectance value (LRV) or luminance, also called luminance contrast. Tripura Fire Safety Rules, 2026 Page 33 of 169 Explanation- Light reflectance value is measured on a scale of 0 to 100 where 0 equals black meaning total light absorption and 100 equals white meaning total light reflection. A simple formula for visual contrast is given below for guidance: Visual contrast = [(B1 B2)/B1] × 100, in percent where B1 = LRV of the lighter area; and B2 = LRV of the darker area. In most circumstances, a difference in these values of 30 percent is considered adequate. However, research suggests that signs are more legible for the visually impaired when characters contrast with their background by at least 70 percent. 2.1.2.41 Walks (Walkways) A predetermined prepared surface, exterior pathway leading to or from a building or facility, or from one exterior area to another, placed on the existing ground level and not deviating from the level of the existing ground immediately adjacent. 2.1.2.42 Way Finding Descriptive of a system whereby appropriate information is provided to assist a person to pass through the built environment towards a specific destination. Explanation- Way finding includes orienting oneself, knowing one’s destination, following the best route, recognizing one’s destination and finding one’s way back out. People who are blind or who have a vision impairment benefit from tactile information to facilitate way finding. 2.1.2.43 Wheelchair User A person who relies on a wheelchair for mobility. 2.1.2.44 Water-Closet Compartment/Toilet Cubicle A compartment having a water-closet with grab bars installed to assist persons with physical disabilities/ mobility impairments. 2.1.2.45 White Cane A long rod-like device used by blind or visually impaired travellers to give them information about the environment they are travelling through. 2.1.3. General Design Considerations 2.1.3.1 These requirements relate to the principal human abilities that should be considered when designing, constructing and managing the built environment. 2.1.3.2 Design Aspects According to Human Abilities Understanding of the human abilities or limitation thereof as described below, and design aspects according to the same, when fully implemented, are expected to benefit all people: a) Non-ambulatory disabilities Impairments that, regardless of cause or manifestation, for all practical purposes, make an individual a wheelchair user for his mobility. The requirement of non-ambulatory disabilities relates primarily to the design of buildings, so as to meet their independent mobility needs while sitting in the wheelchair with or without assistance, minimum widths and heights, level changes and signage, etc. b) Ambulatory disabilities Impairments that cause individuals to walk with difficulty or insecurity of balance. Such persons are able to walk on level, either with or without personal assistance, and may depend on prostheses (artificial limbs), orthoses (calipers), sticks, crutches or walking aids or may negotiate suitably graded steps provided that convenient handrails are available. For example elders using walking sticks, ladies in advance stage of pregnancy, temporary disabilities, such as, fracture, individuals using braces or crutches, amputees, persons having arthritis, those with spasticity and those with pulmonary and cardiac ills, etc, may be ambulatory disabled. c) Sight disabilities Total blindness or impairments affecting sight to the extent that the individual may have to use his other sensory organs such as sense of touch and hearing, use assistive devices for orientation in the environment, such as white cane. Accordingly, building design needs to take in to account means, such as, tactile, Braille and audio-visual, and colour contrasting signage. d) Hearing disabilities Deafness or hearing impairment may affect an individual’s verbal communication or ability to hear warning signals in the environment. The buildings needs to be designed to provide more visual signage, induction loops for hearing enhancement, emergency audio-visual sirens, etc. e) Disabilities of incoordination of motor movements due to cerebral palsy, spinal injury or peripheral nerve injury. f) People with allergies People with allergies may be sensitive to dust, mildew, pollen, animal hair, formalin, turpentine, etc. Some are sensitive to contact with substances and materials such as nickel, chromium and rubber. g) People with heart and lung diseases People with heart and lung diseases may only be able to walk short distances and may be unable to climb stairs. The requirements of these people are similar to those with impaired mobility. h) People with epilepsy, haemophilia, etc The requirements of those with epilepsy, heamophilia, etc, are related primarily to the design of buildings and the need to minimize the risk of injury Tripura Fire Safety Rules, 2026 Page 34 of 169 caused by falling or encountering obstacles. j) People with incontinence, enterostomy operations, etc The requirements of people with incontinence, enterostomy operations, etc, (colostomies, ileostomies and urostomies) are mainly related to bathroom provision. In certain circumstances, for example in public water- closet compartments, it may be desirable to provide a special sink for emptying urine bags. k) People with hidden (such as strength, stamina, dexterity and allergy) impairments, and m) People with diversities in age and stature (including frail persons). 2.1.3.3 Key Accessibility Issues Entering, using and evacuating buildings should be safe and easy for individuals, families and groups which include persons with disabilities. The main considerations are as follows: 1) Pedestrian access into site; 2) Designated vehicular parking near the main entrance; 3) Accessible path to the entrance; 4) Appropriate external lighting; 5) Accessible external furniture (seats, bins, etc); 6) Accessible information at the entrance to the site; 7) Suitable drop-off point near main entrance; 8) Reduced travelling distances; 9) Level entrances and exits; 10) Simple and logical layouts; 11) Unobstructed level circulation; 12) Easy access to information desks, lifts and toilet compartments for disabled persons; 13) Intuitive, obvious and accessible means of egress; 14) Spacious lifts; 15) Safe stairs that are easy to use, and facilitate safe assisted evacuation/rescue in emergencies; 16) Slip-resistant walking surfaces; 17) Wide door openings and easy door operation, sufficient space around doors that makes it possible to open and close them when seated in a wheelchair; 18) Adequate manoeuvring space; 19) Adequate height, location and easy operation of controls and switches; 20) Good lighting; 21) Good visual contrast of walls, floors, doors and signage; 22) Good signage; 23) Important information communicated via two senses or more (tactile, audible and visual); 24) Good acoustics; 25) Hearing enhancement systems; and 26) Management and maintenance of the built environment. The key accessibility issues are highlighted in Pic. 2. 2.1.4 Various key accessibility issues shall be taken into account for ensuring accessibility in built and specific requirements on site planning and development, designated accessible parking space, approach to the buildings, access at entrance and within the buildings, controls and operating mechanisms, seating spaces, other facilities, level changes, toilet and sanitary facilities, emergency evacuation in buildings, signages, etc. 2.1.5 Various accessibility requirements for persons with disabilities and the elderly shall be at least one entrance preferably the main entrance per building shall be accessible. All efforts should be made to make as many/all entrances accessible. Other requirements shall be in accordance with the Tripura building Rules, 2017 or any other rules for the time being in force. Tripura Fire Safety Rules, 2026 Page 35 of 169 Tripura Fire Safety Rules, 2026 Page 36 of 169 Tripura Fire Safety Rules, 2026 Page 37 of 169 2. 2 General Exit Requirements 2. 2.1 An exit may be a fire exit doorway; an internal staircase, exit passageway, external doorway, external staircase and these having access to the street or to a Veranda or to a refuge area or to the terrace or roof of a building. An exit may also include a horizontal exit leading to an adjoining building/fire compartment having its further access to unlocked/public exit at the same level. 2. 2.2 Unless otherwise specified, lifts, escalators, moving walks and revolving doors shall not be considered as exits and shall not constitute any part of the required exit. 2 2.3 Every exit, exit passageway and exit discharge shall be continuously maintained free of all obstructions or impediments to full use in the case of fire or other emergency. 2. 2.4 Every building having human occupancy shall be provided with exits sufficient to permit safe egress of occupants, in case of fire or other emergency. 2. 2.5 In every building or structure, exits shall comply with the minimum requirements of this Part, except those not accessible for general public use. 2. 2.6 No building shall be so altered as to reduce the number, width or protection of exits to less than that required. 2. 2.7 For non-naturally ventilated areas, fire doors with 120 min fire resistance rating shall be provided and particularly at the entrance to lift lobby and stair well where a ‘funnel or flue effect’ may be created, induc ing an upward spread of fire, to prevent spread of fire and smoke. 2. 2.8 Exits shall be so arranged that they may be reached without passing through another occupied unit/passage in others control, if they pose challenge or restriction in means of egress. 2.2. 9 Doors in exits shall open in the direction of exit. In case of assembly buildings (Group D) and institutional buildings (Group C-1), exit door shall not open immediately upon a flight of stair and all such entries to the stair shall be through a landing, so that such doors do not impede movement of people descending from a higher floor when fully opened (see Fig. 4A). While for other occupancies, such doors shall not reduce the pathway in the landing by more than half the width of such staircase (see Fig. 4B). Over-head or sliding doors shall not be installed. 2. 2.10 At least half of the required exit stairs from upper floors (rounded to the next higher number) shall discharge directly to the exterior or through exit passageways. 2. 2.11 Unless otherwise specified, all the exits and exit passageways to exit discharge shall have a clear ceiling height of at least 2.4 m. However, the height of exit door shall be at least 2.0 m (see Fig. 5). 2. 2.12 Where changes in elevation of more than 300 mm are encountered in the exits, ramps or sloped surfaces shall be used with handrails and floor finish materials that contrast with the adjacent finish materials. 2. 2.13 The capacity of the means of egress required from any storey of the building shall not be reduced along the path of egress travel until arrival to the exit discharge. Tripura Fire Safety Rules, 2026 Page 38 of 169 2. 2.14 The lifts, escalators, moving walks, turnstiles and revolving doors shall not be considered in determining the required capacity of means of egress for the individual floor(s) or the building. 2. 2.15 Turnstiles or similar devices that restrict travel to one direction or that are used to restrict unauthorized entry shall not be so placed as to obstruct any required means of egress. Alternative door openings of required exit width shall be available within 3 m of such devices, if installed. 2. 2.16 Suitable means shall be provided so that all access controlled exit doors, turnstiles, boom barriers and other such exits shall automatically operate to open mode during emergencies like fire, smoke, acts of terrorism, etc, so that people can safely and quickly egress into safe areas outside. If required, a master controlling device may be installed at a strategic location to achieve this. 2. 2.17 Penetrations into and openings through an exit are prohibited except those necessary like for the fire protection piping, ducts for pressurization and similar life safety services. Such openings as well as vertical passage of shaft through floors shall be protected by passive systems. 2. 2.18 Walking surfaces in exit access shall comply with the following requirements for smooth exit: a) Walking surfaces shall be nominally level. b) The slope of walking surface in the direction of travel shall not exceed 1 in 20 unless the ramp requirements are met (see 2.4.2.4.3.5). c) Slope perpendicular to the direction of travel shall not exceed 1 in 48. d) Walking surfaces shall be slip-resistant along the entire path of travel. 2. 2.19 Basement a) Basement exits shall be sufficient to provide for the capacity of the basement as determined in accordance with 2.4.2.1. In no case shall there be less than two independent basement exits. b) Basements having incidental occupancies to main occupancy shall be planned with exit requirements of the basements for the actual occupancy within the basement. c) Where basement is used for car parking and also there is direct approach from any occupancy above to the basement, door openings leading to the basement shall need to be protected with fire doors with 120 min fire rating, except for exit discharge doors from the basements. Tripura Fire Safety Rules, 2026 Page 39 of 169 Tripura Fire Safety Rules, 2026 Page 40 of 169 2.3 Occupant Load For determining the exits required, the number of persons within any floor area or the occupant load shall be based on the actual number of occupants declared, but in no case less than that specified in Table 3. The occupant load of a mezzanine floor discharging to a floor below shall be added to that floor occupancy and the capacity of the exits shall be designed for the total occupancy load thus established. Tripura Fire Safety Rules, 2026 Page 41 of 169 The occupant load of each story considered individually shall be required to be used in computing the number of means of egress at each story, provided that the required number of means of egress is not decreased in the direction of egress travel. The assembly occupancies and call centres shall be required to display, limiting occupant load details positioned in a conspicuous place near the entrance of each of such respective occupancy to avoid possible overcrowding and overloading. The display shall preferably be engraved on a metal plate of not less than 300 mm x 200 mm, with letters of height and width not less than 50 mm, with detail of occupancy, area and occupancy load (see figure below). The capacity of any open mezzanine/balcony shall be added to the capacity of the floor below for the purpose of determining exit capacity. 2.4 Egress Components Egress components to be considered are the number of exits to which access is provided, capacity of exit access, travel distance to an exit, the obviousness of the direction to an exit, and any hindrance including due to security issues involved. 2.4.1 Exit Access a) A common path of travel is desirable in exit access which leads to two independent directions to separate exits. b) Capacity of exit access — The width of corridors, aisles or ramps required for exit access shall be sufficient to ensure a smooth flow of occupants to the exit. Where a corridor is the only way of access to an exit, the corridor width shall not be less than the calculated exit width. c) Objects like tables, chairs or any other temporary/permanent structures in exit access corridors shall be avoided as this may result in congestion and also impeding smooth flow of personnel during emergencies. d) In order to ensure that each element of the means of egress can be effectively utilized, they shall all be properly lit and marked. Lighting shall be provided with emergency power back-up in case of power failures. Also, exit signs of adequate size, marking, location, and lighting shall be provided so that all those unfamiliar with the location of the exits may safely find their way. e) Exit access to fireman’s lift and refuge area on the floor shall be step free and clearly signposted with the international symbol of accessibility. f) Exit access shall not pass through storage rooms, closets or spaces used for similar purpose. g) The calculation of capacity of exit access shall be in accordance with 2.4.2.4. MAXIMUM OCCUPANCY PERSONS PERMITTED WITHIN THIS SPACE/ROOM It is confirmed that the fire exits are planned for egress of the occupancy as mentioned above and occupancy more than the above is not permitted in the space/room as follows: SPACE/ROOM DETAIL: FLOOR NO. : _________________ Signature with Date (Manager/Authorized Signatory) Tripura Fire Safety Rules, 2026 Page 42 of 169 2.4.2 Exits 2.4.2.1 Number of exits The minimum required number of exits in a building shall be determined based on occupant load (see Table 3) and width required per person (see Table 4) as appropriate to the type of exit for respective occupancies, subject to complying with maximum travel distance requirement (see Table 5). 2.4.2.2 Arrangement of exits a) Exits shall be so located that the travel distance on the floor shall not exceed the distance given in Table 5. b) Travel distance shall be measured from the most remote point within a storey or a mezzanine floor along the natural and un-obstructed path of horizontal or vertical egress travel to the door to an exit. c) The dead end corridor length in exit access shall not exceed 6 m for educational, institutional and assembly occupancies. For other occupancies, the same shall be 15 m (see Fig. 6) d) Exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any point in the area served. 2.4.2.3 Capacities of means of egress a) Exit capacity is the number of people that can pass through a stairway, and level components (door and corridor) and ramps. The total capacity of all the respective means of egress serving a floor shall be sufficient to allow egress of the entire population of the floor. b) The unit of exit width, used to measure the capacity of any exit, shall be 500 mm. A clear width of 250 mm shall be counted as an additional half unit. Clear widths less than 250 mm shall not be counted for exit width. c) Width per person for stairways, and level components and ramps shall be determined using the capacity factors in accordance with Table-4. For example, if an exit doorway measures 1000 mm in clear width, it would be defined as providing exit capacity for 1000/6.5 occupants, that is, 153 persons (say 150 persons) and number of such exit doorways can then be calculated depending on the occupant load. d) When calculating stairways, level components and ramps and other exit means, the capacity of the entire system shall have to be based upon the minimum capacity available from any part of the system. The corridor, if so provided shall also to be planned with consideration of exit access adequacy for the number of occupants. Further, consider the situation of doors opening to an exit stairway. Tripura Fire Safety Rules, 2026 Page 43 of 169 If the stairway provides an exit capacity of 150 persons, and the doors leading into the stairway provide an exit capacity of 153 persons, the overall exit system would be considered to provide the minimum exit capacity of only 150 persons afforded by the stairway. The exit planning will be limited by the most restrictive exit calculation under the means of egress. e) In the procedures for determining required egress capacity, the number of required means of egress is based on a floor-by-floor consideration, rather than the accumulation of the occupant loads of all the floors. However, the number of means of egress cannot decrease as an occupant proceeds along the egress path. 2.4.2.4 Types of exit access and exits Various types of exit access and exits are doorways, corridors and passageways, horizontal exits, internal staircases, exit passageways, external staircases and ramps. Requirements for each are as detailed below. 2.4.2.4.1 Doorways a) Every exit doorway shall open into an enclosed stairway or a horizontal exit of a corridor or passageway providing continuous and protected means of egress (see Fig. 7 on unaccepted arrangement of doors in a stair). b) No exit doorway shall be less than 1 000 mm in width except assembly buildings, where door width shall be not less than 2 000 mm (see Fig. 8). Doorways shall be not less than 2 000 mm in height. c) Exit doorways shall be operable from the side which they serve, without the use of a key. d) Mirrors shall not be placed on exit doors and in exits to avoid confusion regarding the direction of exit. e) Revolving doors can be accepted as a component in a means of egress where the following requirements are fully complied with: 1) Doors shall be capable of collapsing to a book fold position with parallel egress paths, of width not less than 1 000 mm. 2) Doors shall not be located within 3 m of the foot or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the doors. 3) Each revolving door shall be provided with a hinged door in the same wall within 3 m thereof, with same exiting capacity. 4) Each revolving door shall be considered as capable of exiting only 50 persons. f) All fire rated doors and assembly shall be provided with certificate and labels prominently indicating the manufacturer’s identification, door details covering door type, serial/batch number, month and year of manufacture, fire resistance rating, etc. The doors and assembly shall be certified with all prescribed hardware such as hinges, locks, panic bars, door closer, and door viewers. g) Access controlled doors — Access controlled doors and electromagnetic doors shall fall under this category. These shall meet the following requirements: 1) Doors shall have fire rating as per the requirements at the location of installation. 2) Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors in the direction of egress, and the doors shall remain unlocked until the automatic sprinkler system or fire-alarm system has been manually reset. 3) Loss of power to the part of the access control system that locks the doors shall automatically unlock the doors in the direction of egress. 4) A manual release device shall be provided in the readily accessible vicinity of the egress door with a signage ‘PUSH TO EXIT’ and when the same is operated, it shall result in direct interruption of power to the lock, independent of the access control system electronics. h) Turnstiles — Turnstiles or similar devices that restrict travel to one direction or are used to collect fares or admission charges shall not be placed so as to obstruct any required means of egress unless door openings of required width are available within 3 m thereof. Tripura Fire Safety Rules, 2026 Page 44 of 169 Turnstiles or such similar devices shall also be disengaged through automatic or manual intervention to allow egress in the direction of exit. j) Doors in folding partition shall not be treated as approved means of egress. 2.4.2.4.2 Corridors and passageways of means of egress a) Corridors and passageways shall be of width not less than the calculated aggregate width of exit doorways leading from them in the direction of travel to the exit (see Table 4 and Table 5). b) In the case of buildings where there is a central corridor, which is part of exit access, the doors of rooms (except for rooms having assembly occupancy) shall open inwards to permit smooth flow of traffic in the corridor. 2.4.2.4.3 Staircases 2.4.2.4.3.1 General The requirements of number of staircases shall supplement the requirement of different occupancies in 6.1 to 6.9. All buildings, as mentioned in 1.2, shall have a minimum of two staircases. The actual number of staircases shal l comply with the requirement of 2.4.2.1. All exit staircases shall discharge, at the level of exit discharge, to the exit discharge, either, a) directly, or b) through an exit passageway, or c) through a large lobby. At least 50 percent of the staircases shall discharge as per (a) and/or (b) above. The minimum width of tread without nosing shall be 250 mm for staircase of residential buildings. This shall be minimum 300 mm for assembly, hotels, educational, institutional, business and other buildings. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 190 mm for staircase of residential buildings (A-2) and 150 mm for other buildings. The number of risers shall be limited to 12 per flight. The staircases may be internal staircases or external staircases. Table 4 Capacity Factors [Clauses 2.4.2.1, 2.4.2.3(c) and 2.4.2.4.2(a)] Sl. No. Occupancy Group Width per Person in mm Stairways Level Components and Ramps 1) Residential (Group A) 10 6.5 2) Educational (Group B) 3) Institutional (Group C) 15 13 4) Assembly (Group D) 10 6.5 5) Business (Group E) 6) Mercantile ( Group F) 7) Industrial (Group G) 8) Storage (Group H) 9) Hazardous (Group J) 18 10 Tripura Fire Safety Rules, 2026 Page 45 of 169 Table 5 Travel Distance (Based on Occupancy and Construction Type) (Clauses 2.4.2.1 and 2.4.2.2) Sl. No. Occupancy Group Maximum Travel Distance (in Mtr) Types 1 and 2 (Heat & Smoke Un-Detectored and un-sprinklered) Types 1 and 2 (Heat & Smoke Detectored and and sprinklered) Types 3 and 4 (1) (2) (3) (4) (5) 1) Residential (Group A) 30.00 60.00 22.5 2) Educational (Group B) 30.00 45.00 22.5 3) Institutional (Group C) 30.00 45.00 22.5 4) Assembly (Group D) 30.00 45.00 30.00 5) Business (Group E) Businesses (including admin area of Data centre building) 30.00 60.00 30.00 Data centre building NA 60.00 NA 6) Mercantile (Group F) 30.00 45.00 30.00 7) Industrial (Group G) G-1,G-2 45.00 60.00 See Note 3 G-3 22.50 45.00 8) Storage (Group H) 30.00 90.00 9) Hazardous (Group J) 22.50 30.00 NOTES 1) The common path of travel should be not more than 50 percent of the above distances. 2) Ramps are not to be counted as an exit in case of basements below the first basement in car parking. 3) Construction of Type 3 or Type 4 is not permitted. 4) Utility service areas and equipment areas may be exempt from the measurement of travel distance from within the room. 5) For ceiling height 10 m or above at ground floor in buildings such as airports, exhibition halls, convention centres, atrium in shopping-malls, entrance lobbies and the like and provided with sprinkler system, the travel distance in such areas may be increased by 100 percent of the values specified. This is not to be applied to the values given in col 4) above. 6) In such buildings having ceiling heights 17 m or more and would have sprinkler exemption, the travel distance of such areas may be allowed to be increased by 100 percent of the values specified. This is not to be applied to the values given in col 4) above. In such cases, to prevent heat build-up at ceiling level, suitable smoke/heat venting systems are recommended. Tripura Fire Safety Rules, 2026 Page 46 of 169 2.4.2.4.3.2 Internal staircases The internal staircases may be constructed with an external wall, or otherwise, and shall comply with the following: a) Internal stairs shall be constructed of non-combustible materials throughout, and shall have fire resistant rating of minimum 120 min. b) A staircase shall not be arranged round a lift shaft. c) Exits shall not be used as a portion of a supply, return or exhaust air system serving adjoining areas. Any opening(s) shall not be permitted in walls or in doors, separating exits from adjoining areas. d) No flue chimney, electromechanical equipment, air conditioning units, gas piping or electrical panels shall be allowed in the stairway. e) Notwithstanding the detailed provision for exits in accordance with 2.2 and 2.3, the following minimum width shall be provided for staircases for respective occupancies: Tripura Fire Safety Rules, 2026 Page 47 of 169 Sl. No. Occupancy & Group Sub Group Width in M 1) Residential (Group A) (A-2) 1 M NOTE — For row housing with 2 storeys, the minimum width shall be 0.75 m. (A-1, 3 & 4) 1.25 M (A-5 & 6) 1.5 M 2) Educational (Group B) 1.5 M 3) Institutional (Group C) 2 M 4) Assembly (Group D) 2 M NOTE — The width of stairs may be accepted to be 1.50 m in case of assembly occupancy having less than 150 persons. 5) Business (Group E) 1.5 M 6) Mercantile (Group F) 1.5 M 7) Industrial (Group G) 1.5 M 8) Storage (Group H) 1.5 M 9) Hazardous (Group J) 1.5 M f) A handrail shall be provided on one side of the staircase of width less than 1500 mm, and on both sides of the staircase of width 1500 mm and more. The projection of handrail(s) in the staircase width shall not be more than 115 mm. All other requirements of handrail shall be in accordance with Part 3 ‘Development Control Rules and General Building Requirements’ of the Notification. g) Handrails may project inside the measured width by not more than 90 mm. h) The design of staircase shall also take into account the following: 1) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m 2) Access to exit staircase shall be through a fire door of a minimum 120 min fire resistance rating. 3) No living space, store or other fire risk shall open directly into staircases. 4) The exit (including staircases) shall be continuous from refuge floors or terrace level, as applicable, to the level of exit discharge. 5) No electrical shafts/air conditioning ducts or gas pipes, etc, shall pass through or open in the staircases. 6) Lifts shall not open in staircase. 7) No combustible material shall be used for decoration/wall panelling in the staircase. 8) Beams/columns and other building features shall not reduce the head room/ width of the staircase. 9) The floor indication board, indicating the location/designated number of staircase, respective floor number and direction to exit discharge shall be placed inside the staircase, on the wall nearest to the fire door. It shall be of size not less than 300 mm x 200 mm (see Fig. 9). 10) Individual floors shall be prominently indicated on the wall outside the staircase and facing it. 11) All staircase shall terminate at the level of exit discharge. The access to the basement shall be by a separate staircase. 12) Scissors type staircases shall not be treated as part of exit. 2.4.2.4.3.3 Curved stairs Curved stairs shall not be treated as part means of egress. However, these may be used as part of exit access provided the depth of tread is not less than 280 mm at a point 350 mm from the narrower end of the tread and the smallest radius is not less than twice the stair width. 2.4.2.4.3.4 External staircases Tripura Fire Safety Rules, 2026 Page 48 of 169 The external staircases are the staircases provided on the external wall/facade, and shall comply with the following: a) External stairs shall always be kept in sound and usable condition. b) All external stairs shall be directly connected to the ground. c) Entrance to the external stairs shall be separate and remote from the internal staircase. d) Where an external staircase is provided, it shall be ensured that the use of it at the time of fire is not prejudiced by smoke and flame from openings (for example, windows, doors) in the external face of the building. Care shall be taken to ensure that no external wall or window opening opens on to or close to an external stair. If such openings exists within 3 m from an external staircase, they shall be protected with fire rated doors/window assemblies with rating of at least 60 min (see Fig. 10). e) The external stairs shall be constructed of non-combustible materials, and any doorway leading to it shall have minimum 120 min fire resistance. f) No external staircase, shall be inclined at an angle greater than 45° from the horizontal. g) External stairs shall have straight flight not less than 1500 mm wide. h) Handrails, to be provided on both sides, shall be of a height not less than 1 000 mm and not exceeding 1200 mm. i)There shall be provisions of balusters with maximum gap of 150 mm. j) The use of spiral staircase shall be limited to low occupant load and to a building not exceeding 9 m in height. A spiral staircase shall be not less than 1500 mm in diameter and shall be designed to give adequate headroom. 2.4.2.4.3.5 Ramps Tripura Fire Safety Rules, 2026 Page 49 of 169 a) Ramps shall comply with all the applicable requirements for staircases regarding enclosure, capacity (see also Table 4) and limiting dimensions, except where specified in 6.1 to 6.9 for special uses and occupancies. b) The slope of a ramp shall not exceed 1 in 12 (8 percent). c) Ramp(s) shall be surfaced with approved slip resistant materials that are securely attached. No perforations are permissible on ramp floors. d) Any changes in travel direction in ramp shall be preceded by landings of 1.5 m x 1.5 m size. e) Ramps and intermediate landings shall continue with no decrease in width along the direction of egress travel. f) Outside ramps and landings shall be designed to minimise water accumulation on their surfaces. g) Ramps shall have landings located at the top, at the bottom, and at doors opening onto the ramp. h) Every landing shall be not less than 1 500 mm long in the direction of travel. i) Where the ramp is not part of an accessible route, the ramp landings shall not be required to exceed 1250 mm in the direction of travel, provided that the ramp has a straight run. j) Handrails shall be provided on all ramps on both sides (see 2.4.2.4.3.4). NOTE — Above requirements are not applicable to basement car parking ramps . Tripura Fire Safety Rules, 2026 Page 50 of 169 2.4.2.5 Smoke control of exits a) In building design, compartmentation plays a vital part in limiting the spread of fire and smoke. The design should ensure avoidance of spread of smoke to adjacent spaces through the various leakage openings in the compartment enclosure, such as cracks, openings around pipes ducts, airflow grills and doors. In the absence of proper sealing of all these openings, smoke and toxic gases will obstruct the free movement of occupants of the building through the exits. Pressurization of staircases is of great importance for the exclusion of smoke and toxic gases from the protected exit. b) Pressurization is a method adopted for protecting the exits from ingress of smoke, especially in high-rise buildings. In pressurization, air is injected into the staircases, lobbies, etc, as applicable, to raise their pressure slightly above the pressure in adjacent parts of the building. As a result, ingress of smoke or toxic gases into the exits will be prevented. The pressurization of staircases and lift lobbies shall be adopted as given in Table 6. The pressure difference for staircases shall be 50 Pa. Pressure differences for lobbies (or corridors) shall be between 25 Pa and 30 Pa. Further, the pressure differential for enclosed staircase adjacent to such lobby (or corridors) shall be 50 Pa. For enclosed staircases adjacent to non-pressurized lobby (or corridors), the pressure differential shall be 50 Pa. Tripura Fire Safety Rules, 2026 Page 51 of 169 c) Equipment and ductwork for staircase pressurization shall be in accordance with one of the following: 1) Directly connected to the stairway by ductwork enclosed in non-combustible construction. 2) If ducts used to pressurize the system are passed through shafts and grills are provided at each level, it shall be ensured that hot gases and smoke from the building cannot ingress into the staircases under any circumstances. d) The normal air conditioning system and the pressurization system shall be designed and interfaced to meet the requirements of emergency services. When the emergency pressurization is brought into action, the following changes in the normal air conditioning system shall be effected: 1) Any re-circulation of air shall be stopped and all exhaust air vented to atmosphere. 2) Any air supply to the spaces/areas other than exits shall be stopped. 3) The exhaust system may be continued provided, i) the positions of the extraction grills permit a general air flow away from the means of egress; ii) the construction of the ductwork and fans is such that, it will not be rendered inoperable by hot gases and smoke; and Tripura Fire Safety Rules, 2026 Page 52 of 169 iii) there is no danger of spread of smoke to other floors by the path of the extraction system which can be ensured by keeping the extraction fans running. e) For pressurized stair enclosure systems, the activation of the systems shall be initiated by signaling from fire alarm panel. f) Pressurization system shall be integrated and supervised with the automatic/manual fire alarm system for actuation. g) Wherever pressurized staircase is to be connected to unpressurized area, the two areas shall be segregated by 120 min fire resistant wall. h) Fresh air intake for pressurization shall be away (at least 4 m) from any of the exhaust outlets/grille. 2.5 Compartmentation 2.5.1 General a) It is important to limit the spread of a fire in any building. The usual method is to use fire bafflers. In some instances these barriers need to be penetrated for ductwork, plumbing and electrical systems, and in such cases, use of passive fire protection measures shall be done so that the integrity of these barriers is not compromised. b) Floor(s) shall be compartmented with area as given below. 2.5.2 All floors shall be compartmented / zoned with area of each compartment being not more than 750 m2. The maximum size of the compartment shall be as follows, in case of sprinklered basement/building: Sl. No. USE Compartmentation Area (m2) 1) Basement (car parking) 3000 2) Basements (other than car parking) 2000 3) Institutional buildings: Subdivision C-1 1800 4) Institutional buildings: Subdivision C-2 and C-3 1125 5) Mercantile and assembly buildings 2 000 6) Business buildings 3 000 7) All other buildings (Excluding low hazard and moderate hazard industrial buildings and storage buildings) 750 Compartmentation for low hazard and moderate hazard industrial buildings and storage buildings shall be done in consultation with local fire department. In addition, there shall be requirement of a minimum of two compartments if the floor plate size is equal or less than the areas mentioned above. However, such requirement of minimum two compartments shall not be required, if the floor plate is less than 750 m2. Compartmentation shall be achieved by means of fire barrier having fire resistance rating of 120 min. 2.6. Smoke Control 2.6.1 Smoke Exhaust and Pressurization of Areas Above Ground Corridors in exit access (exit access corridor) are created for meeting the requirement of use, privacy and layout in various occupancies. These are most often noted in hospitality, health care occupancies and sleeping accommodations. Tripura Fire Safety Rules, 2026 Page 53 of 169 Exit access corridors of guest rooms and indoor patient department/areas having patients lacking self preservation and for sleeping accommodations such as apartments, custodial, penal and mental institutions, etc, shall be provided with 60 min fire resistant wall and 20 min self-closing fire doors along with all fire stop sealing of penetrations. Smoke exhaust system having make-up air and exhaust air system or alternatively pressurization system with supply air system for these exit access corridors shall be required. Smoke exhaust system having make-up air and exhaust air system shall also be required for theatres/auditoria. Such smoke exhaust system shall also be required for large lobbies and which have exit through staircase leading to exit discharge. This would enable eased exit of people through smoke controlled area to exit discharge. All exit passageway (from exit to exit discharge) shall be pressurized or naturally ventilated. The mechanical pressurization system shall be automatic in action with manual controls in addition. All such exit passageway shall be maintained with integrity for safe means of egress and evacuation. Doors provided in such exit passageway shall be fire rated doors of 120 min rating. Smoke exhaust system where provided, for above areas and occupancies shall have a minimum of 12 air changes per hour smoke exhaust mechanism. Pressurization system where provided shall have a minimum pressure differential of 25-30 Pa in relationship to other areas. The smoke exhaust fans in the mechanical ventilation system shall be fire rated, that is, 250°C for 120 min. For naturally cross-ventilated corridors or corridors with operable windows, such smoke exhaust system or pressurization system will not be required. 2.6.2 Smoke Exhaust and Pressurization of Areas Below Ground Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 percent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills, or breakable stall board lights or pavement lights or by way of shafts. Alternatively, a system of mechanical ventilation system may be provided with following requirements: a) Mechanical ventilation system shall be designed to permit 12 air changes per hour in case of fire or distress call. b) In multi-level basements, independent air intake and smoke exhaust shafts (masonry or reinforced concrete) for respective basement levels and compartments therein shall be planned with its make-up air and exhaust air fans located on the respective level and in the respective compartment. Alternatively, in multi-level basements, common intake masonry (or reinforced cement concrete) shaft may serve respective compartments aligned at all basement levels. Similarly, common smoke exhaust/outlet masonry (or reinforced cement concrete) shafts may also be planned to serve such compartments at all basement levels. All supply air and exhaust air fans on respective levels shall be installed in fire resisting room of 120 min. Exhaust fans at the respective levels shall be provided with back draft damper connection to the common smoke exhaust shaft ensuring complete isolation and compartmentation of floor isolation to eliminate spread of fire and smoke to the other compartments/floors. c) Due consideration shall be taken for ensuring proper drainage of such shafts to avoid insanitation condition. Inlets and extracts may be terminated at ground level with stall board or pavement lights as before. Stall board and pavement lights should be in positions easily accessible to the fire brigade and clearly marked 'AIR INLET' or 'SMOKE OUTLET' with an indication of area served at or near the opening. Tripura Fire Safety Rules, 2026 Page 54 of 169 d) Smoke from any fire in the basement shall not obstruct any exit serving the ground and upper floors of the building. e) The smoke exhaust fans in the mechanical ventilation system shall be fire rated, that is, 250°C for 120 min. f) The smoke ventilation of the basement car parking areas shall be through provision of supply and exhaust air ducts duly installed with its supports and connected to supply air and exhaust fans. Alternatively, a system of impulse fans (jet fans) may be used for meeting the requirement of smoke ventilation complying with the following: 1) Structural aspects of beams and other down stands/services shall be taken care of in the planning and provision of the jet fans. 2) Fans shall be fire rated, that is, 250°C for 120 min. 3) Fans shall be adequately supported to enable operations for the duration as above. 4) Power supply panels for the fans shall be located in fire safe zone to ensure continuity o- power supply. 5) Power supply cabling shall meet circuit integrity requirement in accordance with accepted standard [4(13)]. The smoke extraction system shall operate on actuation o- flow switch actuation o- sprinkler system. In addition, a local and/or remote 'manual start-stop control/switch' shall be provided for operations by the fire fighters. Visual indication o- the operation status o- the fans shall also be provided with the remote control. No system relating to smoke ventilation shall be allowed to interface or cross the transformer area, electrical switchboard, electrical rooms or exits. Smoke exhaust system having make-up air and exhaust air system for areas other than car parking shall be required for common areas and exit access corridor in basements/underground structures and shall be completely separate and independent of car parking areas and other mechanical areas. Supply air shall not be less than 5 m from any exhaust discharge openings. 2.7 Gas Supply 2.7.1 Town Gas/LPG Supply Pipes Where gas pipes are run in buildings, the same shall be run in separate shafts exclusively for this purpose and these shall be on external walls, away from the staircases. Gas distribution pipes shall always be below the false ceiling. The length of these pipes shall be as short as possible. In the case o- kitchen cooking range area, hood should have grease filters using metallic grill to trap oil vapours escaping into the fume hood. 2.7.2 Thermal detectors These shall be installed into fume hoods of large kitchens for hotels, hospitals, and similar areas located in high rise buildings. Arrangements shall be made for automatic tripping of the exhaust fan in case of fire. If gas is used, the same shall be shut off. The voltage shall be 24 V or 100 V D.C. operated with external rectifier. The valve shall be of the hand re-set type and shall be located in an area segregated from cooking ranges. Valves shall be easily accessible. The hood shall have manual facility for steam or suitable hood extinguishing gas released depending on duty condition. 2.7.3 Gas cylinders and manifold shall need to be housed in a detached location with no other occupancy within distances prescribed in good practice in accordance with the list of standards as specified in Schedule V (14) thereof. There shall be an enclosure suitably ventilated. It is desirable to provide medium velocity spray nozzles which can be operated by quick opening valve situated away from the enclosure. Tripura Fire Safety Rules, 2026 Page 55 of 169 2.7.4 In the case of gas cylinders, if manifold has to be installed on podium/close to podium, the same shall be away from any air intakes/smoke exhaust openings/ any windows. 2.7.5 Pressure regulating stations shall be designed and installed at critical locations for excess flow shut off valves. Seismic shut off valve at the main distribution point shall be installed for buildings in D-6 occupancy and institutional occupancy above 15 m. 2.7.6 Gas meters shall be housed in a suitably constructed metal cupboard located in a well-ventilated space, keeping in view the fact that LPG is heavier than air and town gas is lighter than air. 2.7.7 Wherever LPG reticulation/cylinders are used in buildings above 100 m, gas leak detectors shall be provided at the usage points and monitored from fire command centre. The cables used for signaling shall be circuit integrity cables. 2.7.8 The gas lines shall not be installed through any electrical shafts, escape routes, refuge areas/refuge floors. 2.7.9 Kitchens working on LPG fuel shall not be permitted in basements. 4.8 Hazardous Areas, Gaseous, Oil Storage Yard, etc Rooms containing high pressure boilers, refrigerating machinery, transformers or other service equipment subject to possible explosion shall not be located directly under or adjacent to exits. All such rooms shall be effectively cut-off from other parts of the building and shall be provided with adequate vents to the outside air. All rooms or areas of high hazard in additions to those hereinbefore mentioned, shall be segregated or shall be protected with fire resistant walls having fire rating of 120 min as fire, explosion or smoke therefrom is likely to interfere with safe egress from the building. Further, a) each building shall be provided with an approved outside gas shut-off valve conspicuously marked; and b) all exterior openings in a boiler room or rooms contain central heating equipment, if located below opening in another storey or if less than 3 m from other doors or windows of the same building shall be protected by a fire assembly as in 1.4.5. Such assemblies shall be fixed, automatic or self-closing. 2.9 Fire Detection and Alarm a) The requirements of fire detection and alarm systems are covered for each occupancy in Table 7 and under 4.1 to 4.9 for annunciation to occupants in view of the ensuing vulnerability and to warn occupants early of the existence of fire, so as to facilitate orderly and safe egress. b) Fire detection and alarm systems in buildings shall be so planned and programmed so as to enable operations of various systems and equipment to facilitate requirements leading to life safety, compartmentation and fire protection. These systems and equipment may include electromechanical systems such as air handling units; pressurization systems; smoke management systems; creation of compartmentation through the release of fire barrier, hold-up fire doors, etc; and monitoring of fire water storage tanks and pumps, pressures in hydrant and sprinkler system, etc. These planning and requirements shall be based on building occupancy and other requirements on case to case basis. c) Voice evacuation systems shall employ Hindi, English and vernacular language using pre-recorded messages and integrate with fire alarm panels for alerting the zone of fire and surrounding zones/floors as required for annunciation (see also Table 7 and its Note 1). d) Appropriate visual warning arrangement through visual strobes/beacons may be considered in appropriate situations particularly in public buildings, at required locations to ensure visual as well as alarm for persons with hearing impairment. Tripura Fire Safety Rules, 2026 Page 56 of 169 e) For assembly buildings, institutional buildings and all buildings above 30 m in height where fire alarm system is provided in accordance to Table 7, detectors shall also be provided inside the electrical shafts, and lift machine rooms, etc, besides occupancy areas. f) Fire alarm panels shall be connected in peer to peer network or with redundant cables, run in different shafts. Each panel shall be able to work in standalone mode and master slave architecture may be used where required. g) The fire detection system shall be in accordance with accepted standards [4(15)]. Guidelines for selection of various types of fire detectors for different occupancies and their installation and maintenance shall be in accordance with good practice in accordance with the list of standards as specified in Schedule V (16) h) In buildings where automatic fire alarm system is provided, the following shall be monitored from fire alarm panel: 1) Water level in all tanks. 2) Hydrant and sprinkler pressures of respective zones as provided. 3) Pump ‘ON/OFF’ status. 4) All isolation valves, wherever provided with supervisory switch (non-padlock valves). 5) Other requirements to meet electro-mechanical services interface. 2.10 Fire Officer 2.10.1 A qualified Fire Officer with experience of not less than 3 years shall be appointed who will be available on the premises, for large educational complexes, business buildings with height 30 m and above, residential building with height 60 m and above, institutional buildings of 15 m and above, starred hotels and D-6 occupancy. 2.10.2 The Fire Officer shall, a) maintain the firefighting equipment in good working condition at all times. b) prepare fire orders and fire operational plans and get them promulgated. c) impart regular training to the occupants o~ the buildings in the use of firefighting equipment provided on the premises and keep them informed about the fire emergency evacuation plan. d) keep proper liaison with the city fire brigade. e) ensure that all fire precautionary measures are observed at the times. NOTE — Competent authority having jurisdiction may insist on compliance of the above rules in case of buildings having very large areas even if the height is less than 30 m. 2.11 Fire Drills and Fire Orders Fire notices/orders shall be prepared to fulfill the requirements of firefighting and evacuation from the buildings in the event of fire and other emergency. The occupants shall be made thoroughly conversant with their action in the event of emergency, by displaying fire notices at vantage points and also through regular training. Such notices should be displayed prominently in bold lettering. For guidelines for fire drills and evacuation procedures for high rise buildings, see Annex D. Tripura Fire Safety Rules, 2026 Page 57 of 169 TABLE- 7 (MINIMUM REQUIREMENTS FOR FIRE PREVENTION, PROTECTION AND LIFE SAFETY MEASURES INSTALLATIONS IN BUILDINGS OR PREMISES BASED ON OCCUPANCY) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under-ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) RESIDENTIAL BUILDINGS (A) (a) Lodging or Rooming Houses (A-1) (see Note3) 1) Less than 15m in height i) Up to 15 rooms R NR NR NR NR R (see Note-4) NR NR NR 5000 (see Note-5) NR NR ii) More than 15 and up to 30 rooms R R NR NR NR R (see Note-4) NR NR NR 5000 (5000) (see Note-6) NR 450 (450) (See Note- 6) iii) More than30 rooms R R NR NR NR R (see Note-4) R (see Note-7) NR NR 10000 (5000) (see Note-6) NR 450 (450) (See Note- 6) (b) One or two Family Private dwellings (A-2) (see Note 3) NR NR NR NR NR NR NR NR NR NR NR NR Tripura Fire Safety Rules, 2026 Page 58 of 169 SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note- 2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (C) Dormitories (A-3) and Apartment Houses (A-4) 1) Less than 15m in height R R NR NR NR R (see Note-4) NR NR NR 5000 (5000) (see Note-6) NR 450 (450) (see Note-6) 2) 15m and above but not exceeding 35m in height R R NR R NR R (see Note-4) R (see Note-4) NR NR 25000 NR 900 3) Above 35m but not exceeding 45m in height R R R NR NR R (see Note-4 and Note 9) R NR 75000 5000 (see Note-10) NR 4) Above 45m in height but not exceeding 60m in height R R R NR R R R NR 150000 10000 (see Note-11) NR 5) Above 60m in height R R R NR R R R R 200000 10000 (see Note- 12 and 13) NR Tripura Fire Safety Rules, 2026 Page 59 of 169 SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note- 2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (d) Hotel (A-5) 1) Less than 15m in height (i) Floor area not exceeding 300m2 on any of the floor R R NR NR NR R (see Note-4) R NR NR 5000 (5000) (see Note-6) NR 450 (450) (see Note-6) (ii) Floor area exceeding 300m2 but not more 1000m2 on any of the floor R R R (see Note-4) NR NR R (see Note-4) R R 10000 For every 500m2 floor area subject to minimum of 50000 (see note 7) 10000 (5000) (see Note-6) (see note 14 in case of prevision of wet riser) 450 (450) (see Note-6) (iii) Floor area exceeding 1000m2 on any of the floor R R R (see Note-15) NR R R R (see Note-1) R 100000 (see Note-15) 10000 (see Note-4) (see Note-14 and 15) NR 2) 15m and above but not exceeding 30m R R R NR R R R R 150000 20000 (see Note-11) NR 3) Above 30m in height R R R NR R R R R 200000 20000 (see Note-11 NR (e) Hotels (A-6) R R R NR R R R R 250000 20000 (see Note-12) NR Tripura Fire Safety Rules, 2026 Page 60 of 169 EDUCATION BUILDINGS (B) (see Note-16) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note- 2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) 1) Less than 15m in height Ground plus one or more storey R R NR NR NR R (see Note-4) NR NR NR 10000 (5000) (see Note 6) NR 450 (450) (see Note-6) 2) 15m and above but not exceeding 24m in height R R NR R NR R (see Note-4) R NR NR 25000 NR 900 3) Above 24m but not exceeding 30m in height R R R NR R R (see Note-4) R NR 50000 (5000) (see Note-6) (see note-14) NR Tripura Fire Safety Rules, 2026 Page 61 of 169 INSTITUTIONAL BUILDINGS (C) (see note 16) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (a) Hospitals, Sanatoria and Nursing Homes (C-1) 1) Less than 15m in height with plot area upto 1000m2 (i) Up to ground plus one storey, with no beds R NR NR NR NR R (see Note-4) R NR NR (5000) (see Note-6) NR (450) (see Note-6) (ii) Up to ground plus one storey with beds R R NR NR NR R (see Note-4) R NR NR 5000 (5000) (see Note-6) NR 450 (450) (see Note-6) (iii) Ground plus two or more storeys, with no beds R R NR R NR R (see Note-4) R R NR 10000 (5000) (see Note- 6) NR 900 (450) (see Note-6) (iv) Ground plus two or more storeys, with beds R R R NR NR R R (see Note-1) R 75000 10000 (see Note-14) NR 2) Less than 15m in height with plot area more than 1000m2 R R R NR R R R (see Note-1) R 100000 10000 (see Note-14) NR 3) 15m and above but not exceeding 24m in height R R R NR R R R R 150000 20000 (see Note-10) NR 4) Above 24m and not exceeding 45m in height R R R NR R R R R 200000 20000 (see Note-11) NR Tripura Fire Safety Rules, 2026 Page 62 of 169 SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note- 2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (b) Custodial (C-2) and Panel & Mental (C-3) 1) Less than 10m in height (i) Up to 300 persons R R NR NR NR R (see Note-4) R NR NR 10000 (5000) (see Note- 6) NR 450 (450) (see Note-6) (ii) More than 300 persons R R NR R NR R (see Note-4) R NR NR 15000 (5000) (see Note- 6) NR 900 (450) (see Note-6) 2) 10m and above but not exceeding 15m in height R R R NR R R (see Note-4) R R 100000 5,000 (5000) (see Note- 6) (see Note-10) NR 3) 15m and above but not exceeding 24m in height R R R NR R R R R 150000 10000 (see Note-11) NR 4) 24m and above but not exceeding 30m in height R R R NR R R R R 200000 20000 (see Note-11) NR Tripura Fire Safety Rules, 2026 Page 63 of 169 ASSEMBLY BUILDING (D) (see Note 16) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (a) Buildings (D-1 to D-5) 1) Less than 10m in height (i) Up to 300 persons R R NR R NR R (see Note-4) R NR NR 20000 (5000) (see Note-6) NR 450 (450) (see Note- 6) (ii) More than 300 persons R R NR R NR R (see Note-4) R NR NR 25000 (5000) (see Note-6) NR 900 (450) (see Note- 6) 2) Above 10m but not exceeding 15m in height R R R NR NR R (see Note-4) R (see Note-1) R 100000 5,000 (5000) (see Note-6) (see Note-10) 450 (450) (see Note-6) 3) Above 15m but not exceeding 24m in height R R R NR R R R R 150000 10000 (see Note-10) NR 4) Above 24m but not exceeding 30m in height R R R NR R R R R 200000 20000 (see Note-11) NR (b) D-6 R R R NR R R R R 200000 20000 (see Note-12) NR Tripura Fire Safety Rules, 2026 Page 64 of 169 BUSINESS BUILDINGS (E) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) 1) Less than 10m in height R R NR R NR R (see Note-4) R NR NR 10000 (5000) (see Note-6) NR 450 (450) (see Note-6) 2) Above 10m but not exceeding 15m in height R R R NR NR R (see Note-4) R R 50000 5000 (5000) (see Note-6) (see Note-14) 450 (450) (see Note-6) 3) Above 15m and up to 24m in height R R R NR R R R R 100000 10000 (see Note-10) NR 4) Above 24m and up to 30m in height R R R NR R R R R 150000 20000 (see Note-11) NR 5) Above 30m in height R R R NR R R R R 200000 20000 (see Note-12) NR Tripura Fire Safety Rules, 2026 Page 65 of 169 MERCANTILE BUILDINGS (F) (Notes- 3(b), 8 and 22) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (a) F-1 and F-2 (see Note 16) 1) Less than 15m in height (i)Ground plus one storey, with total of all floor area not exceeding 500m2. R R NR NR NR R (see Note-4) NR NR NR 5000 (5000) (see Note-6) NR 450 (450) (see Note-6) (ii)Ground plus one storey and total of all floor area exceeding 500m2. R R NR R NR R (see Note-4) R NR NR 20000 (5000) (see Note-6) NR 900 (450) (see Note-6) iii) More than ground plus one storey R R NR R NR R (see Note-4) R NR NR 25000 (5000) (see Note-6) NR 900 (450) (see Note-6) 2) Above 15m but not exceeding 24m in height R R R NR NR R R R 100000 10000 (see Note-10) NR 3) Above 24m but not exceeding 30m in height R R R NR R R R R 200000 20000 (see Note-11) NR (b) Underground shopping complex (F-3) R R R NR R R R R 150000 10000 (see Note-11) NR Tripura Fire Safety Rules, 2026 Page 66 of 169 INDUSTRIAL BUILDINGS (G) (see Note 17) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under- ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (a) LOW HAZARD (G-1) (see Note 18) (i) Covered area up to 100m2 R NR NR NR NR R (see Note-4) NR NR NR NR NR NR (ii) Covered area more than 100m2 and up to 500m2 R R NR R (see Note-8) NR R (see Note-4) NR NR NR 10000 (5000) (see Note-6 & 26) NR 450 (see Note- 26) (iii) Covered area more than 500m2 (for building height up to 15m) R R NR R NR R (see Note-4) R NR NR 10000 (5000) (see Note-6 & 26) NR 450 (see Note- 26) (iv) Covered area more than 500m2 (for building height above15m) R R R NR R R (see Note-4) R R 50000 (5000) (see Note- 26) (see Note-14) NR Tripura Fire Safety Rules, 2026 Page 67 of 169 Sr. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under-ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respecti ve Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (b) MODERATE HAZARD (G-2) (see Note 18) (i) Covered area up to 100m2 R R NR NR NR R NR NR NR NR NR NR (ii) Covered area more than 100m2 and up to 500m2 R R NR NR NR R NR NR NR 10000 (see Note- 27) NR 900 (see Note- 27) (iii) Covered area more than 500m2 and up to 1000m2 (for building height up to 15m) R R NR R NR R R R NR 30000 (see Note- 27) NR 900 (see Note- 27) (iv) Covered area more than 500m2 and up to 1000m2 (for building height above15m) R R R NR R R R R 75000 10000 (see Note- 28) (see Note-14) NR v) Covered area more than 1000m2 R R R NR R R R R 100000 10000 (see Note- 28) (see Note-11) NR (c) HIGH HAZARD (G-3) (see Note 19) (i) Covered area up to 50m2 R R NR NR NR R NR NR NR 10000 NR 900 (ii) Covered area more than 50m2 and up to 150m2 R R NR NR NR R R R NR 25000 NR 900 (iii) Covered area more than 150m2 and up to 300m2 R R R NR NR R R R 50000 10000 (see Note-14) NR (iv) Covered area more than 300m2 and up to 500m2 R R R NR R R R R 100000 20000 (see Note-10) NR (v) Covered area more than 500m2 R R R NR R R R R 150000 20000 (see Note-11) NR Tripura Fire Safety Rules, 2026 Page 68 of 169 STORAGE BUILDINGS (H) (see Note 20) SI. No. Type of Building Occupancy Type of Installations Water Supply (litres) Pump Capacity (litres/Min) Fire Extinguisher (see Note-25) First Aid Hose Reel Wet Riser Down Comer Yard Hydrant Automatic Sprinkler System Manually Operated Electronic Fire Alarm System (see note-1) Automatic Detection And Alarm System (see Note-2) Under-ground Static Water Storage, Tank Combined Capacity for Wet riser, Yard Hydrant and Sprinklers per Set of Pumps Terrace Tank Over Respective Tower Terrace Pump near Underground Static Water Storage Tank (Fire Pump) With Minimum Pressure of 3.5kg/cm2 at Remotest Location At the terrace Tank Level Minimum Pressure of 3.5kg/cm2 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) 1) Below 15m in height and covered area less than 250m2 R R NR NR NR R NR NR NR 25000 NR 900 2) Below 15m in height and covered area more than 250m2 (i) Ground floor only R R R NR R R R R 50000 10000 (see Note-14) 450 (ii) Ground plus one floor R R R NR R R R R 750000 10000 (see Note-10) 450 (iii) More than ground plus one floor R R R NR R R R R 100000 10000 (see Note-10) 450 3) Multi-Level Car Parking (MLCP) R R R NR R R R NR 150000 10000 (see Note-11) 900 HAZARDOUS BUILDING (J) (see Note 20) 1) Up to 15m in height i)Single storey Building R R R NR R R R R Minimum 240min fire fighting requirements NR (see Note-21) NR ii) More than one floor building but not exceeding 15m R R R R R R R R Minimum 240min fire fighting requirements 50000 (see Note-21) 900 RUBBER PLANTATION/GARDEN/SMOKE HOUSE 1) Rubber Plantation/Garden (see note 29) NR NR NR NR NR NR NR NR 5000 for every 500 m2 NR NR NR There must be fire lines in the entire garden area. 2) Smoke House R (Mechanical Foam - 10 ltrs and ABC (Dry Powder)- 10 kg for every 500 m2 NR NR NR NR NR NR NR 5000 for every 500 m2 NR NR NR Tripura Fire Safety Rules, 2026 Page 69 of 169 NOTES R- Required, NR- Not Required 1. Manually Operated Electronic Fire Alarm System shall also include talk-back system and public address system for the occupancies given in the table for (d) (1) (iii) under A-5, (a) (1) (iv) and (a) (2) under C-1, and (a) (2) under D-1 to D-5, in all buildings 15 m and above in height, except for A-3 and A-4 occupancies where these shall be provided for buildings of height 24 m and above. These shall also be provided in car parking areas more than 300 m2 and in multi -level car parking irrespective of their areas. 2. Automatic detection and alarm system is not required to be provided in car parking area. Such detection system shall however be required in other areas of car parking such as electrical rooms, cabins and other areas. 3. Buildings above 15 m in height are not to be permitted for occupancies A-1 and A-2. 4. Required to be installed in basement, if area of basement exceeds 200 m2. 5. Required to be provided if basement area exceeds 200 m2. 6. Additional value given in parenthesis shall be added if basement area exceeds 200 m2. 7. Required to be provided for buildings with more than two storeys (Ground + One). 8. Required to be provided for buildings with height above 15 m and above. 9. Sprinklers shall be fed water from both underground static water storage tank and terrace tank. 10. Provide required number of sets of pumps each consisting of one electric and one diesel pump (stand by) of capacity 2 280 litre/min and one electric pump of capacity 180 litre/min (see Fig. 11) (see also notes 22 and 23). 11. Provide required number of sets of pumps each consisting of two electric and one diesel pump (stand by) of capacity 2 280 litre/min and two electric pump of capacity 180 litre/min (see Fig. 12) (see also Notes 22 and 23). 12. Provide required number of sets of pumps each consisting of two electric and one diesel pump (stand by) of capacity 2 850 lit re/min and two electric pump of capacity 180 litre/min (see Fig. 12) (see also Notes 22 and 23). 13. Lower levels in high rise buildings 60 m or above in height are likely to experience high pressure and therefore, it is recommended to consider multi-stage, multi- outlet pumps (creating pressure zones) or variable frequency drive pumps or any other equivalent arrangement. 14. Provide required number of sets of pumps each consisting of one electric and one diesel pump (stand by) of capacity 1 620 lit re/min and one electric pump of capacity 180 litre/min (see Fig. 11) (see also Notes 22 and 23). 15. Required to be provided for buildings with more than one storey. 16. Buildings above 30 m in height not to be permitted for Group B, Group C, Group D and Group F occupancies. 17. The requirements given in this table for Group G Industrial Buildings are for small scale industry units. For other industries the requirements wi ll have to be worked out on the basis of relevant Indian Standards and also in consultation with the local fire authorities. 18. Buildings above 18 m in height not to be permitted for G-1 and G-2 occupancies. 19. Buildings above 15 m in height not to be permitted for G-3 occupancies. 20. Buildings above 15 m in height not to be permitted for Group H and Group J occupancies. However, buildings above 45 m in height shall not be permitted for multi- level car parking (MLCP) occupancy. Tripura Fire Safety Rules, 2026 Page 70 of 169 21. Pump capacity shall be based on the covered area of the building. 22. One set of pumps shall be provided for each 100 hydrants or part thereof, with a maximum of two sets. In case of more than one pump set installation, both pump sets shall be interconnected at their delivery headers. 23. Alternative to provisions of additional set of pumps, the objective can be met by providing additional diesel pump of the same capacity and doubling the water tank capacity as required for one set of pumps. 24. As per the requirement of local authority dry riser may be used in hilly areas, industrial areas or as required. 25. Selection & installation shall be in accordance with the standard specified in Schedule-V and as specified in OTHER TERMS. 26. If there is issue to provide terrace tank, the same capacity of under ground water tank must be available. Entire occupancy should be protected by one electric driven main pump of at least 450 LPM discharge capacity (with reliable back-up power supply like DG Set). The pressure 3.5 kgf/cm2 must be available at the remotest sprinkler of the top floor. 27. If there is issue to provide terrace tank, the same capacity of under ground water tank must be available. Entire occupancy should be protected by one electric driven main pump of 2850 LPM discharge capacity (with reliable back-up power supply like DG Set). The pressure 3.5 kgf/cm2 must be available at the remotest sprinkler of the top floor. Pressure control valve can be used. 28. If there is issue to provide terrace tank, the same capacity to be added with the capacity of under ground water tank. The pressure 3.5 kgf/cm2 must be available at the remotest sprinkler of the top floor. Note: The fire Safety measures for any occupancy if not covered/specified by the Table 7 or otherwise, the fire Safety recommendation as proposed by the authorized fire inspecting officer must be followed. No alterations shall be accepted. Tripura Fire Safety Rules, 2026 Page 71 of 169 OTHER TERMS APPLICABLE FOR BUILDINGS OR PREMISES FOR VARIOUS OCCUPANCIES : 1) Fixed fire fighting equipments standards references shall be standards specified in Schedule E. 2) a) i) Portable Fire Extinguishers: CO2 fire extinguisher(specially for electric panel boards), Water type fire extinguisher (specially for general fires), Dry Chemical Powder (ABC Type) (specially for flammable liquid, gases & general fires), Dry Chemical Powder (BC Type) (specially for flammable liquid & gases fires), Dry Chemical Powder (D Type) (specially for metal fires), Wet Chemical (specially for kitchen), Water Mist (specially for general fires) and CAF (specially flammable liquids manufacturing or handling small scale units). ii) Suppression/flooding systems: CO2 flooding system and Clean agent fire suppression system (specially for main electric panel /ACDB & DCDB room), Nitrogen injection system and Deluge system(specially for electric sub-station) and Foam fire suppression system (specially for Hanger and oil, paint storage room or the like where a blanketing effect is required). b) Mounting Heights and distance to be maintained: The carrying handle of a portable fire extinguisher with a total gross mass of 4kg and bottom of the extinguisher should be not less than 0.9 meter high from the floor. This height may be raised to 1.5 meters for extinguishers weighing less than 4kg. c) IS-2190 : 2010 (code of practice for the selection, installation, and maintenance of First-Aid Fire Extinguishers) – Spacing shall be a part depending on fire risk. Fire extinguisher spacing is determined by maximum travel distance to the unit, not just floor area. The distance may be allowed- i) Low Hazard : 30 m ii) Moderate Hazard : 22 m iii) High Hazard : 15 m Additional conditions: i) 1(one) no. CO2 - 4.5 kg capacity and 1(one) no. ABC - 6.8–10 kg capacity fire extinguishers must be available near staircase and lift landing areas in each floor. Additional 1(one) no. ABC - 10 kg capacity and 1(one) no. CO2 - 4.5 kg capacity fire extinguisher must be available at every 30 m intervals in the corridor of each floor. ii) If there is electric main/sub-panel board in any floor, 1(one) no. CO2 - 4.5 kg capacity fire extinguisher must be kept near electric main/sub-panel board. iii) 1(one) no. ABC- 6.8kg capacity fire extinguisher must be available in each normal kitchen. For professional/commercial kitchen, 1(one) no. Wet Chemical -9 ltr capacity and 1(one) no. ABC- 6.8kg capacity fire extinguishers must be available for every 400m2 area. iv) For car parking area, 1(one) no. ABC- 25kg (trolley mounted) capacity and 1(one) no. Foam type- 25 ltrs capacity (trolley mounted) fire extinguisher must be available for every 600m2 area. 3) Sprinkler spacing shall be as per IS 15105 (code of practice for the design and installation of Sprinkler), FM Global (FM) standards and NFPA13 or performance based designed. Increased spacing usually demands higher flow rates. Sprinkler spacing can be increased, but it must be done through specific, compliant methods, most notably using Extended Coverage (EC) sprinklers. Extended Coverage (EC) sprinklers are designed to protect larger areas per head compared to standard sprinklers, typically covering up to 400 ft² (37.2 sq. mt). EC sprinklers can be spaced up to 20 ft (6.1m) or more apart in Light and Moderate hazard environments, such as hotels, offices, and residential spaces. While High hazard with specific solid structural members may increase to 15 ft subject to maintain required higher flow rates. Other international standards may be adopted subject to maintaining the required high flow rates and other conditions. 4) Hydrant spacing shall be as per IS 13039:2014 (Code of Practice- External Hydrant Systems) In case of industries: The maximum distance between one hydrant to next one may be allowed 90 m. for high hazard [Gr.- G-3(industries), H, J and multiple hazards] buildings, if there is a monitor (60 m discharge range) in between two consecutive hydrant points and the hose box adjacent to the hydrant points should contain 2(two) delivery hoses, each 15 meters in length. https://www.google.com/search?q=Extended+Coverage+%28EC%29+sprinklers&sca_esv=5790ebd106505311&ei=i2jjacfWO9CwwcsPysOx6Ac&biw=1920&bih=945&ved=2ahUKEwiB8K2ipPeTAxWyTmwGHRe-OeQQgK4QegQIARAB&uact=5&oq=sprinkler+distance+can+be+increased++as+per+nepa+13&gs_lp=Egxnd3Mtd2l6LXNlcnAiM3Nwcmlua2xlciBkaXN0YW5jZSBjYW4gYmUgaW5jcmVhc2VkICBhcyBwZXIgbmVwYSAxMzIIEAAYgAQYogQyCBAAGIAEGKIEMggQABiABBiiBDIIEAAYgAQYogQyCBAAGIAEGKIESPw8UNIJWIQ1cAF4AZABAJgB6AGgAbgYqgEGMC4xNS4yuAEDyAEA-AEBmAIRoAKQF8ICChAAGEcY1gQYsAPCAgUQIRifBcICBRAhGKABwgIHECEYChigAZgDAIgGAZAGCJIHBjEuMTQuMqAH0juyBwYwLjE0LjK4B4sXwgcGMy4xMi4yyAcbgAgB&sclient=gws-wiz-serp&mstk=AUtExfDcO1mND_ntfcIpRZIJoLH4V1e-FhriJHdz6hrRRMCB_WTCSVxbeERcPWtpPWSwif5wzpwTLF3hKXArINc6xSDvIprrCj8fYmN6Cu-6iMB6ubFBpgi9tNubxUUq3_q5w4U&csui=3 Tripura Fire Safety Rules, 2026 Page 72 of 169 The maximum distance between one hydrant to next one may be allowed 45 m. for low and moderate hazard [Gr.- G-1 & 2(industries)] buildings, the hose box adjacent to the hydrant point should contain three (03) delivery hoses, each 15 meters in length. The maximum distance may be allowed, if i) the minimum hydraulically pressure of 3.5 kgf/cm2 must be available at the remote point in the premises of low & moderate hazard (Gr.- G-1 & 2) industries, and ii) the hydrant system should be so designed that when half the aggregate pumping capacity is being discharged at the hydraulically most remotest point and other half in the most vulnerable area enroute a minimum hydraulically pressure of 7 kgf/cm2 must be available at the remotest point in the premises of high hazard [Gr.- G-3(industries), H and J] buildings. 5) Single-staircase (single-exit) will be allowed for residential (apartment) buildings. The Requirements for such buildings: a) Maximum Height: Three (G+2) stories or up to 10 m. b) Maximum Area: 500m2 c) Units per Story: Limited to four tenements per floor. d) Occupants capacity: Maximum 70. e) Must be equipped with automatic fire detection system. f) The exit stair must discharge directly to the outside. g) Fire Escape Stair Width: Must be at least 3000 (1500+1500) mm (or 4000 (2000+2000)mm if the number of occupant is more than 50) wide with 250 mm treads and 190 mm risers. h) Dead-End Corridors: The distance from a dead end to the Escape Stair usually cannot exceed 15 m (half the allowed travel distance as specified hereinabove). The distance is not a "straight line". It is measured along the actual path of travel, including turns around furniture or walls, from the farthest "extreme side" of the floor to the door of the staircase. i) Position of Exit Stair: Location of the Exit Stair preferably at the center of the corridor of the building or shall be provided in such a manner, so that the distance from the extreme ends of the both sides of the building to the exit stairs can be reduced and people can safely evacuated from the building in case of emergency. The minimum travel distance is also of paramount importance in the context of firefighting and rescue operations. 6) Sharing of water storage tank may be permitted between the adjacent neighboring prope rties including industry clusters, without any loss of hydraulic effects (which is essential to fight the fire during an emergency). For buildings in the same complex, the entire fire fighting infrastructure to be managed/controlled by single management committee. The fire water shall be calculated for single largest building. Except industrial parks/estates, if neighboring properties are under different ownership, a Memorandum of Understanding (MoU) regarding the use of joint or common fire-fighting infrastructure— such as fire hydrants, water tanks, etc. must be signed between the owners in the presence of officials from the Fire Department. The owners have no right to cancel the said MoU without notifying the Fire Department. 7) Provision for shared/common fire fighting infrastructure such as fire hydrants, water tanks, etc. to be introduced in industrial parks/estates as an alternative to individual plot level mandates shall be as per the guidelines of the Tripura Industrial and Development Corporation ltd. 8) Provisions of side setbacks shall be in accordance with the Tripura Building Rules, 2017. 9) For industrial buildings (excluding high-risk structures), the required water tank capacity has been reduced; additionally, building owners are provided with the option to consolidate the total water storage capacity into a single underground water tank subject to the condition that the necessary pressure is maintained at the most remote sprinkler on the uppermost floor. 10) For Retail outlet (LPG) Gas:- Adequate “Brass wire Mesh” shall be provided. A fire-resistance door with a minimum fire rating of 120-minute shall be installed. Electrification shall not be permitted in the area/ room where LPG cylinders are kept. 11) Electrification shall be done outside the Gas Godown. Tripura Fire Safety Rules, 2026 Page 73 of 169 General Instruction: a) All exit/staircase/aisles/corridors/ramps existing in the building should always remain free from any obstruction for quick and safe evacuation of inmates in case of any emergency. b) Terrace / underground water reservoir exclusively for fire fighting system should always be kept full up to brim. c) Water reservoir of fire fighting purposes will be connected with water tank of other purposes in such a way that the Fire fighting water tank will be filled by water first, then water tank of other purposes will be filled by the overflow water. d) The owner/occupier has to arrange for annual building inspection and record be maintained. e) Electrical wiring of the all building shall have to be carefully checked periodically for any wear and tear in them, particularly lines above false ceiling & ducts. Electrical Safety Audit by the designated engineer of Electric Department to be conducted positively and record be maintained. f) Fire protection and life safety measures/arrangement shall have to be regularly checked, tested and maintenance of all the Fire Fighting installation in the Building is to be regularly done to keep in perfectly good working condition at all the times and record be maintained. g) Periodical flashing of water in the Hydrants, Pipe line shall be made to maintain the efficient working performance of above mentioned system and record be maintained. h) The employees and security staff shall be conversant with the installed Fire Fighting equipment of the building and to operate in the event of any Fire incident. i) Mock Fire Practice and evacuation drill shall be performed periodically involving all the occupants of the building and record be maintained. May seek help from local Fire station, if needed. j) Location of installed fire fighting equipment and plan of emergency evacuation from the building shall be prepared and displayed at all prominent places of the building/premises. k) Emergency Telephone No. like Fire Service, Police, Ambulance, etc. to be displayed in the premises. l) The department can make a surprise visit at any time. During the visit, if the fire fighting system already installed in the building / premises found dysfunctional, The NOC issued by the competent authority shall be treated automatically withdrawn / cancelled. m) In all matters of online services and allied issues, the decision of the Home (Fire & Emergency Services) Department, Government of Tripura would be final Tripura Fire Safety Rules, 2026 Page 74 of 169 3. FIRE PROTECTION 3.1 Fire Extinguishers/Fixed Firefighting Installations 3.1.1 All buildings depending upon the occupancy use and height shall be protected by fire extinguishers, hose reels, wet riser, down-comer, yard hydrants, automatic sprinkler installation, deluge system, high/medium velocity water spray, foam, water mist systems, gaseous or dry powder system, manual/automatic fire alarm system, etc, in accordance with the provisions of various clauses given below, as applicable: a) These fire extinguishing equipment and their installation shall be in accordance with accepted standards [4(17)]. The extinguishers shall be mounted at a convenient height to enable its quick access and efficient use by all in the event of a fire incidence. The requirements of fire extinguishers/yard hydrant systems/wet riser/down-comer installation and capacity of water storage tanks and fire pumps, etc, shall be as specified in Table 7. The requirements regarding size of mains/risers shall be as given in Table 8. The typical arrangements of down-comer and wet riser installations are shown in Fig. 13. The wet riser shall be designed for zonal distribution ensuring that unduly high pressures are not developed in risers and hose-pipes. b) First-aid firefighting appliances shall be provided and installed in accordance with good practice in accordance with the list of standards as specified in Schedule V (18). The firefighting equipment and accessories to be installed in buildings for use in firefighting shall also be in accordance with the list of standards as specified in Schedule V (17)] and shall be maintained periodically so as to ensure their perfect serviceability at all times. c) Valves in fixed firefighting installations shall have supervisory switch with its signalling to fire alarm panel or to have chain(s), pad lock(s), label and tamper-proof security tag(s) with serial number to prevent tampering/unauthorized operation. These valves shall be kept in their intended ‘open’ position. d) In addition to wet riser or down-comer, first-aid hose reels shall be installed in buildings (where required under Table 7) on all the floors, in accordance with accepted standard [4(19)]. The first-aid hose reel shall be connected directly to the riser/down-comer main and diameter of the hose reel shall not be less than 19 mm. e) Wet risers shall be interconnected at terrace level to form a ring and cut-off shall be provided for each connection to enable repair/ maintenance without affecting rest of the system. f) Pressure at the hydraulically remote hydrant and at the highest hydrant shall not be less than 3.5 bar. The pressure at the hydrants shall however not exceed 7.0 bar, considering the safety of operators. It may be planned to provide orifice plates for landing valves to control pressure to desired limit especially at lower levels; this could also be achieved through other suitable means of pressure reducing devices such as pressure controlled hydrant valves. g) Hydrants for firefighting and hose reels shall be located in the lobby in firefighting shaft. Those hydrants planned to be provided near fire exit staircase on the floor shall be within 5 m from exit door in exit access. Such hydrant cabinet may finish with doors to meet interior finishes with requirement of glass panel to provide visibility to the installations inside and inscribed with the word: ‘FIRE HOSE CABINET’ of letter size 75 mm in height and 12 mm in width. Such door of the fire hose cabinet need not be fire resistant rated. The location of such cabinets shall be shown on floor plan and duly displayed in the landing of the respective fire exit staircase. 3.1.2 Static Water Storage Tanks and Pump House 3.1.2.1 Static water storage tanks A satisfactory supply of water for the purpose of firefighting shall always be available in the form of underground/terrace level static storage tank with capacity specified for each building with arrangements or replenishment. Water for the hydrant services shall be stored in an easily accessible surface/underground lined reservoir or above ground tanks of steel, concrete or masonry. The effective capacity of the reservoir above the top of the pump casing (flooded suction) for various types of occupancies shall be as indicated in Table 7. Tripura Fire Safety Rules, 2026 Page 75 of 169 Water for firefighting shall be stored in two or more interconnected compartments of equal size to facilitate cleaning and maintenance of the tanks without interrupting the water availability for firefighting. To prevent stagnation of water in the static water storage tank, the suction tank of the domestic water supply shall be fed only through an overflow arrangement from the fire water storage tanks to maintain the level therein at the minimum specified capacity. Alternatively, domestic and fire water can be stored in two interconnected compartments as mentioned above. The suction inlet(s) for the domestic water pumps shall be so located at an elevation that minimum water requirements for firefighting as stated in Table 7 will be always available for fire pumps. The static storage water supply required for the above mentioned purpose shall entirely be accessible to the fire engines of the local fire service. Suitable number of manholes shall be provided for inspection, repairs, insertion of suction hose, etc. As an alternative to the arrangement of manholes to allow access from the top, suitable arrangement to enable efficient access to the tank by the firemen from the adjoining fire pump room having direct access from the ground level, shall be made. The underground fire water storage tank(s) shall not be more than 7 m in depth from the level having fire brigade draw-out connection, while the draw-out connection shall not be more than 5 m away from the tank wall. The covering slab shall be able to withstand a total vehicular load of 45 ton (or as applicable) equally divided as a four-point load when the slab forms a part of pathway/driveway. The static water storage tank shall be provided with a fire brigade collecting head with 4 number 63 mm diameter (2 number 63 mm diameter for pump with capacity 1400 litre/min) instantaneous male inlets arranged in a valve box at a suitable point at street level. The same shall be connected to the static tank by a suitable fixed galvanized iron pipe not less than 150 mm in diameter to discharge water into the tank when required at the rate of 2250 litre/min, if tank is in the basement or not approachable for the fire engines. Each of the static water storage tanks shall also be provided with a fire brigade draw out collecting head with 63 mm diameter instantaneous male draw out arranged in a valve box at a suitable point at street level. This draw out shall be connected to galvanized iron pipe of 100 mm diameter with foot valve arrangement in the tank. 3.1.2.2 Firefighting pump house The requirements shall be as given below: a) It is preferable to install the pump house at ground level. Pump house shall be situated so as to be directly accessible from the surrounding ground level. b) Pump house shall be installed not lower than the second basement. When installed in the basement, staircase with direct accessibility (or through enclosed passageway with 120 min fire rating) from the ground, shall be provided. Access to the pump room shall not require to negotiate through other occupancies within the basement. c) Pump house shall be separated by fire walls all around and doors shall be protected by fire doors (120 min rating). d) Pump house shall be well ventilated and due care shall be taken to avoid water stagnation. e) No other utility equipment shall be installed inside fire pump room. f) Insertions like flexible couplings, bellows, etc, in the suction and delivery piping shall be suitably planned and installed. g) Installation of negative suction arrangement and submersible pumps shall not be allowed. h) Pump house shall be sufficiently large to accommodate all pumps, and their accessories like PRVs, installation control valve, valves, diesel tank and electrical panel. j) Battery of diesel engine operated fire pump shall have separate charger from emergency power supply circuit. k) Exhaust pipe of diesel engine shall be insulated as per best engineering practice and taken to a safe location at ground level, considering the back pressure. m) Fire pumps shall be provided with soft starter or variable frequency drive starter. 3.1.3 Automatic Sprinkler Installation The requirements shall be as given below: a) Automatic sprinklers shall be installed wherever required in terms of Table 7 throughout the building in accordance with good practice in accordance with the list of standards as specified in Schedule V (20). Tripura Fire Safety Rules, 2026 Page 76 of 169 b) If selective sprinklering is adopted, there is a real danger of a fire starting in one of the unsprinklered area gathering momentum spreading to other areas and reaching the sprinklered areas as a fully developed fire. In such an event, the sprinklers can be rendered useless or ineffective. c) Automatic sprinklers shall be installed in false ceiling voids exceeding 800 mm in height. d) Installation of sprinklers may be excluded in any area to be used for substation and DG set. e) In areas having height 17 m or above such as in atria, sprinkler installations may be rendered ineffective and hence may be avoided. f) Pressure in sprinkler system shall not exceed 12 bar or else high pressure sprinkler to be installed for above 12 bar operations. g) The maximum floor area on any one floor to be protected by sprinklers supplied by any one sprinkler system riser from an installation control valve shall be based on system protection area limitations considering maximum floor area on any one floor to be 4 500 m2 for all occupancies except industrial and hazardous occupancies, where Authorities shall be consulted for advice based on type and nature of risk. h) Sprinkler installation control valves, shall be installed inside the fire pump room. i) For industrial buildings, such installation control valves may be installed outside the building and Authorities shall be consulted in situations where it is not possible to locate them inside the buildings. It is advisable to provide electrically operated siren for each valve outside the buildings in addition to water gongs in such case. j) The sprinkler flow switches provided shall be monitored by fire alarm panel. l) It is essential to make provisions for avoiding water from sprinkler/hydrant operation entering lifts and electrical rooms. m) Ramps at all levels shall be protected with sprinklers. 3.1.4 Automatic High Velocity and Medium Velocity Water Spray Systems Automatic high velocity water spray or emulsifying system shall be provided for protection o~ outdoor and/ or indoor oil-cooled transformers as applicable in accordance with good practice in accordance with the list of standards as specified in Schedule V (21) where applicable (see Annex E). Also, medium velocity water spray system shall be provided for tankage (where applicable), conveyors, cable galleries and other occupancies listed in good practice in accordance with the list of standards as specified in Schedule V (21). 3.1.5 Fixed Foam Installation Fixed foam generating system shall be provided for protection of oil storage area for boilers with its ancillary storage of furnace oils in basement. Fixed foam installations can be low, medium or high expansion types, which can be provided based on the type of fire hazards identified in the facility. High expansion foams are used for cable tunnels and other confined areas. Design and installation o~ foam systems shall be governed by good practice in accordance with the list of standards as specified in Schedule V (22). 3.1.6 Gas Based Suppression System Gas based fire extinguishing installation shall be provided in accordance with good practice on premises where water or foam cannot be used for fire extinguishing because of the special nature of the contents of the buildings/areas to be protected where either the building(s) have very limited manpower or unmanned. The protection design for fixed carbon dioxide fire extinguishing system shall conform to good practice in accordance with the list of standards as specified in Schedule V (23) in all respects. For some special fire risk/essential applications, carbon dioxide may not be suitable and alternate provisions shall be made as per relevant standards (see 3.1.9). 3.1.7 Firefighting equipment shall be suitably located and clearly marked by luminous signs. 3.1.8 Automatic Water Mist Systems These systems involve the use of fine water sprays for the efficient extinguishment of fires. These systems may be provided to protect areas in buildings for the uses as specified in good practice in accordance with the list of standards as specified in Schedule V (24). 3.1.9 Extinguishing Systems with Clean Agents Alternative systems for halon gas protection systems shall be provided where necessary as prescribed in this Part. These shall be in accordance with the accepted standards as specified in Schedule V (25). Tripura Fire Safety Rules, 2026 Page 77 of 169 3. 2 Fire Detection and Alarm System See 2.9. 3. 3 The fixed firefighting installations and systems shall be maintained in accordance with good practice in accordance with the list of standards as specified in Schedule V (26). 4. ADDITIONAL OCCUPANCY WISE REQUIREMENTS In addition to the general requirements on fire prevention given in 3, the life safety requirements given in 4, and the fire protection requirements given in 5, the following additional requirements shall also be complied with for each type of occupancy. For additional requirements for high rise buildings, the provisions as given in Annex E shall apply. Atriums in building occupancies shall comply with the provisions as given in Annex F. For fire protection requirements of commercial kitchen, cooking facilities with or without restaurants, the provisions of Annex G shall be referred. 4.1 Residential Buildings (Group A) 4.1.1 Life Safety 4.1.1.1 Subdivision A–1 a) All locking devices, which would impede or prohibit exit, such as chain type bolts, limited opening sliding type locks and burglar locks, which are not disengaged easily by quick releasing catches, shall be prohibited. b) All bathroom door locks or fasteners shall be designed to permit the opening of the locked or closed door from the outside in an emergency without the use of a special key. c) No lodging or rooming house shall have its sole means of egress pass through any non-residential occupancy in the same building. d) Rooming and lodging houses having floor area of 500 m2 on any one or more floors shall have access to minimum two separate means of exits, at least one o~ which shall be so arranged as to have direct exit discharge. 4.1.1.2 Subdivision A-3 a) Requirements of 4.1.1.1 shall be applicable. b) All sleeping rooms having occupancy of more than 10 persons shall have two separate and distinct exit access in different directions. 4.1.1.3 Subdivision A-4 In case of high rise apartments, of the minimum exits as specified in 2.4.2.4.3.1, the naturally ventilated exit staircases may not require the provision of fire door. However, fire door shall be provided for all other staircases and pressurized staircases. 4.1.1.4 Subdivision A-5 a) Panic bars shall be provided in the fire exits. Panic bars shall be located at a height between 865 mm and 1220 mm from the floor level. b) All guest rooms and suites shall be protected by extended throw, quick response type sprinklers only. Also these areas shall be provided with audio-based detectors, having a sound level of at least 75 dB. c) Horizontal-sliding doors shall not be used for door openings across corridors. 4.1.2 Additional Precautions a) Flammable liquids for household purposes shall be kept in tightly stoppered or sealed containers. For the limits of quantities of flammable liquids to be allowed in various occupancies, reference may be made to appropriate regulations. b) No stove or combustion heater shall be located directly under or immediately at the foot of stairs or otherwise so located as to block escape in case of malfunctioning of the stove or heater. c) All kitchen exhaust fans, where provided, shall be fixed to an outside wall or to a duct of non-combustible material, which leads directly to the outside. The ducts shall not pass through areas having combustible materials. However, in case of centralized ducting, the duct shall be provided with adequate protection to limit the spread of fire. d) Stores, engineering workshops, areas of high hazard, etc used for storage of substantial amount of flammable liquids shall be of 120 min fire resistance rating wall. Such areas shall be provided with fire doors, to be kept Tripura Fire Safety Rules, 2026 Page 78 of 169 closed and shall be posted with a sign on each side of the door in 25 mm high block letters stating — ‘FIREDOOR — KEEP CLOSED’. 4.2 Educational Buildings (Group B) 4.2.1 Fire Prevention a) Buildings intended for educational occupancy shall not be used for storage of any hazardous material. b) Gymnasiums, indoor stadiums and similar occupancies are permitted to have floors/ running tracks of wood, cinder, synthetic or the like. 4.2.2 Life Safety a) Every room with a capacity of over 45 persons in area shall have at least two doorways. Exit doors shall be operated by panic bars except that doors leading from classrooms directly to the outside may be equipped with the same type of lock as is used on classroom doors leading to corridor, with no provision whatsoever for locking against egress from the classroom. b) A building, which will have only the first floor and is accessible to not more than 20 pupils at any time, may be used for school purposes with the following exceptions: 1) Exterior walls or parts of walls which are less than 900 mm from adjacent property lines shall have no openings therein. 2) Classrooms may have only one exit not less than 900 mm wide. c) Rooms or areas for use by the preschool, kindergarten, Class/Grade 1 students shall be located on ground floor/level of exit discharge. Rooms or areas occupied by Class/Grade II students shall be located not above one floor higher than ground floor/level of exit discharge. d) Of the minimum exits as specified in 2.4.2.4.3.1, the naturally ventilated exit staircases, may not require provision of fire door. However, fire door shall be provided for all other staircases and pressurized staircases. 4.2.3 Additional Precautions a) Storage of volatile flammable liquids shall be prohibited and the handling of such liquids shall be restricted to science laboratories only. b) All exterior openings in a boiler room or rooms containing central heating equipment, if located below an opening in another storey or if less than 3 m from other doors or windows of the same building, shall be protected by a fire assembly as in 1.4.5. Such assemblies shall be of fixed, automatic or self-closing type. Tripura Fire Safety Rules, 2026 Page 79 of 169 Tripura Fire Safety Rules, 2026 Page 80 of 169 Tripura Fire Safety Rules, 2026 Page 81 of 169 Tripura Fire Safety Rules, 2026 Page 82 of 169 4.3 Institutional Buildings (Group C) 4.3.1 Fire Prevention No combustible material o~ any kind shall be stored or used in any building or section thereof used for institutional occupancy, except as necessary to normal occupancy and use of the building. 4.3.2 Life Safety a) The common path of travel shall be 30 m. The maximum dead end of corridor distance shall not exceed 6 m. b) Principle of progressive horizontal evacuation is of paramount consideration for hospital patients particularly those lacking self-preservation. This calls for moving occupants from a fire affected area to an adjoining area at the same level through a fire resistant wall, to protect them from the immediate dangers of fire and smoke (see Fig. 14). c) Progressive horizontal evacuation operates on the basis of evacuation from compartment to compartment and on use of adjacent compartments as temporary means of refuge. All compartments shall be divided with self- closing (door closers) fire doors with electromagnetic hold open. A coordinator shall be provided to sequence the closing of double leaf in case of emergency. d) Doors in fire resistant walls shall be so installed that these may normally be kept in open position, but will close automatically. Corridor door openings shall be not less than 2.0 m in width of double swing double leaf type door. A coordinator shall be provided as above, for closing of double leaf in case of emergency. e) Exits and other features for penal and mental institutions, and custodial institutions shall be the same as specified for hospitals [see 4.3.2 (g)], in so far as applicable. Reliable means shall be provided to permit the prompt release o~ inmates from any locked section in case of fire or other emergency. f) All buildings or sections of buildings in penal and mental institution used for manufacturing, storage or office purposes shall have exits in accordance with the provisions of the Notification for those occupancies. Tripura Fire Safety Rules, 2026 Page 83 of 169 g) For hospitals (Subdivision C-1), the following shall also be complied with: 1) Compartmentation shall meet the requirement as per 2.5.2. 2) Each compartment (see 2.5.2) shall be able to accommodate, in addition to its own, the patients from adjoining compartment also considering 3.5 m2 per person. If patients are not bed-ridden, a factor of 0.6 m2 per person is recommended. 3) All critical patients and those incapable of self-preservation and having physical impairment shall be housed within 30 m height. 4) Other types of patients and occupancies incidental to the hospitals such as consultation rooms, nurses’ stations, medical shops, canteens, etc may be housed at heights beyond 30 m but not more than 45 m. 5) Basement shall not be used to store flammables or for pathological or other laboratories particularly those involving usage of chemicals. 6) Operation theatres, delivery rooms, Intensive care units, recovery rooms, etc, that containing patients lacking self-preservation in case o~ emergencies shall be fire/smoke separated (120 min minimum rating) from all the adjoining areas. 7) Aisles, corridors, ramps, etc, through which patients are moved, shall have a minimum width of 2.4 m throughout. Aisles, corridors, and ramps in other areas not intended for the housing, treatment, or use of inpatients shall be not less than 1.5 m in width. 8) All exits from hospital or infirmary sections shall be not less than 2.0 m in width. 9) Minimum width of door of single or double occupancy patient room shall be 1.25 m while for the wards for 3 to 5 patient beds shall be 1.50 m, to permit movement of patients. The minimum width of door for wards for more than 5 patient beds and for areas necessarily requiring patient evacuation on bed (such as ICU, recovery units, delivery rooms, etc), shall have door width of 2.0 m. The width of 2.0 m may be reduced to minimum of 1.5 m where two such doors are provided in such areas. 10.)Any sleeping accommodation or suite exceeding 100 m2 in area shall have at least two doorways leading to the exit access corridors. 11) Floor surface of corridors shall not be inclined at a gradient steeper than 1 in 12 to the horizontal. 12) Exit access corridors from a compartment to another compartment shall be divided at the compartment intersection by a fire door of 120 min fire rating in the fire compartment wall. Tripura Fire Safety Rules, 2026 Page 84 of 169 13) Rooms designated for laboratory and the like shall not exceed 100 m2 in area and if additional space is required, fire separation of 120 min shall be provided. 14) Storage of flammable liquids in laboratories or in any other area shall be not more than 3 litre for every 10 m2 area. 15) Disposal of any equipment and other (particularly hazardous) materials shall be accomplished in the premises by a disposal specialist or at a safe location away from the health care facility by competent personnel using procedures established in concurrence with the safe practices. 16) A stretcher lift in a lift bank shall also act as fireman’s lift. h) Progressive evacuation strategy — See Fig. 15, in which, as an example, the exit calculations at two locations shall be based on requirements of total occupancy for area (A, B and C) divided by 2 considering progressive evacuation strategy. 4.3.3 Exception and Deviation It is recognized that in institutions or part of buildings housing various types of psychiatric patients, or used as mental institutions and penal institutions, it is necessary to maintain locked doors and barred windows; and to such extent the necessary provision in other sections of the notification requiring the keeping of exits unlocked may be waived. It is also recognized that certain type of psychiatric patients are not capable of seeking safety without adequate guidance. In buildings where this situation prevails, reliable means for the rapid release of occupants shall be provided, such as remote control of locks, or by keying all locks to keys commonly used by attendants. 4.4 Assembly Buildings (Group D) Tripura Fire Safety Rules, 2026 Page 85 of 169 4.4.1 Fire Prevention 4.4.1.1 The following shall be applicable: a) Decorations of places of assembly shall be of non-flammable materials. Fabrics and papers used for such purpose shall be treated with an effective flame-retardant material. Stage settings made of combustible materials shall likewise be treated with fire retardant materials of Class 1 flame spread. b) Gymnasiums, indoor stadiums and similar occupancies are permitted to have floors/ running tracks of wood, cinder, synthetic or the like. 4.4.1.2 Additional fire prevention requirements for D-6 occupancy Building having D-6 mixed use assembly/mercantile occupancy will limit the height of the assembly/ mercantile occupancy portion of the buildings to 30 m. Above this height the buildings may be used for business or residential occupancies with 240 min separation. Independent exits shall be provided for such occupancy above 30 m and shall not interface with exits of assembly/mercantile occupancy. 4.4.2 Life Safety 4.4.2.1 The following shall be applicable: a) Exit door width for assembly buildings shall not be less than 2.0 m. b) Every place of assembly of sub-division D-1 shall have at least four separate exits as remote from each other as practicable. c) Every place of assembly of sub-division D-2 shall have at least two separate exits as remote from each other as practicable and if of capacity over 600, at least three exits shall be provided with each exit not less than of 2.0 m width. d) Clear aisles not less than 1.2 m in width shall be formed at right angles to the line of seating in such number and manner that no seat shall be more than seven seats away from an aisle. Rows of seats opening on to an aisle at one end only shall have not more than seven seats. Under the conditions, where all these aisles do not directly meet the exit doors, cross-aisles shall be provided parallel to the line of seating so as to provide direct access to the exit, provided that not less than one cross aisle for every 10 rows shall be required. The width of cross-aisles shall be minimum of 1 m. Steps shall not be placed in aisles to overcome differences in levels, unless the gradient exceeds 1 in 10. e) The fascia of boxes, balconies and galleries shall have substantial railings not less than 1000 mm high above the floor. The railings at the end of aisles extending to the fascia shall be not less than 1100 mm high for the width of the aisle or 1.2 m high at the foot of steps. f) Cross-aisles, except where the backs of seats on the front of the aisle project 600 mm or more above the floor of the aisle, shall be provided with railings not less than 900 mm high. g) No turnstiles or other devices to restrict the movement of persons shall be installed in any place of assembly in such a manner as to interfere in any way with the required exit facilities. h) In theatres and similar places of public assembly where persons are admitted to the building at a time when seats are not available for them and are allowed to wait in a lobby or similar space until seats are available, such use of lobby or similar space shall not encroach upon the required clear width of exits. Such waiting shall be restricted to areas separated from the required exit ways by substantial permanent partitions or fixed rigid railing not less than 1050 mm high. Exits shall be provided for such waiting spaces on the basis of one person for each 0.3 m2 of waiting space area. Such exits shall be in addition to the exits specified for the main auditorium area and shall conform in construction and arrangement to the general rules of exits given above. i) No display or exhibit shall be so installed or operated as to interfere in any way with access to any required exit, or with any required exit sign. j) All displays or exhibits of combustible material or construction and all booths and temporary construction in connection therewith shall be so limited in combustibility or protected as to avoid any undue hazard of fire which might endanger occupants before they have opportunity to use the available exits, as determined by the authority. k) Places of assembly in buildings of other occupancy may use exits common to the place of assembly and the other occupancy, provided the assembly area and the other occupancy are considered separately, and each has exits sufficient to meet the requirements of the Notification. Tripura Fire Safety Rules, 2026 Page 86 of 169 l) Exits shall be sufficient for simultaneous occupancy of both the places of assembly and other parts of the building. m) For detailed information regarding cinema buildings, reference may be made to good practice in accordance with the list of standards as specified in Schedule V (27). n) Seats in places of public assembly, accommodating more than 300 persons, shall be securely fastened to the floor, except as permitted in below (o). All seats in balconies and galleries shall be securely fastened to the floor, except that in nailed-in enclosures, boxes with level floors and having not more than 14 seats, the seats need not be fastened. o) Chairs not secured to the floor may be permitted in restaurants, night clubs and other occupancies where the fastening of seats to the floor may not be practicable, provided that in the area used for seating, excluding dance floor, stage, etc, there shall be not more than one seat for each 1.4 m2 of floor area and adequate aisles to reach exits shall be maintained at all times. The arrangements shall be as follows in general: 1) Rows of seats between aisles shall have not more than 14 seats. 2) Rows of seats opening on to an aisle at one end only shall have not more than 7 seats. 3) Seats without dividing arms shall have their capacity determined by allowing 450 mm per person. p) The spacing of rows of seats from back to back shall be neither less than 850 mm nor less than 700 mm plus the sum of the thickness of the back and inclination of the back. There shall be a space of not less than 350 mm between the back of one seat and the front of the seat immediately behind it as measured between plumb lines. q) Lighting — No open flame lighting devices shall be used in any place of assembly, except in the following cases: 1) Where necessary for ceremonial purposes, the enforcing Authority may permit open flame lighting under such restrictions as are necessary to avoid danger of ignition of combustible materials or injury to occupants. 2) Candles may be used on restaurant tables if securely supported on non-combustible bases and so located as to avoid danger of ignition of combustible materials. 3) Open flame devices may be used on stages where they are a necessary part of the atrical performance, provided adequate precautions, satisfactory to the Authority aretaken to prevent ignition of combustible materials. 4.4.2.2 Life safety provisions for D-6 occupancy The following additional requirements shall be applicable: a) Assembly occupancies of theatres, cinema halls and multiplexes shall be so located in the mall building that their exits will be separate and lead the occupant directly to exit discharge. b) The common path of travel shall be 30 m. The maximum dead end of corridor distance shall not exceed 6 m. c) The minimum width of an exit passageway shall be 2.0 m. d) Where wheeled carts or buggies are used by customers, adequate provision shall be made for the transit and parking of such carts to minimize the possibility that they might obstruct means of egress. Any other storage or hindrances causing obstruction in exits shall be avoided. e) Car parking facilities shall comply with Annex H. Car parking areas at upper levels adjacent to shops, food courts or multiplex shall be separated by 120 min fire rated construction and building elements. f) 50 percent lifts in common areas in D-6 shall be with features and requirement of fireman’s lift. g) The manual call points shall be break glass and not pull stations. h) Photoluminescent markings shall be done along the width and length of treads in all enclosed exits staircases. Exit directional arrow on the wall (in the direction of egress) shall be 175 mm x 50 mm. i) Refuge area to be provided on the floor at or immediately above 18 m shall be not less than 10 percent of gross area of floor. Next refuge area to be at/on the floor immediately above 24 m. The refuge area shall be 10 percent of the respective floor, which may be divided into two or more separate refuge areas at each of the respective floors, with each being not less than 100 m2. Refuge area shall also meet all the requirements of life safety as per notification. 4.4.3 Fire Protection a) Every stage equipped with fly galleries, grid irons and rigging for movable theatre type scenery, shall have a system of automatic sprinklers over and under such stage areas or spaces and auxiliary spaces, such as Tripura Fire Safety Rules, 2026 Page 87 of 169 dressing rooms, store rooms and workshops, and the proscenium opening shall be provided with a fire resisting curtain, capable of withstanding a lateral pressure of 4 KN/m2 over the entire area. The curtain shall have an emergency closing device capable of causing the curtain to close without the use of power and when so closed, it shall be reasonably tight against the passage of smoke. b) The stage roof of every theatre using movable scenery or having a motion picture screen of highly combustible construction shall have a ventilator or ventilators in or above it, openable from the stage floor by hand and also opening by fusible links or some other approved automatic heat/smoke actuated device, to give a free opening equal to at least one-eighth the area of the floor of the stage. c) The proscenium wall of every theatre using movable scenery of decorations shall have, exclusive of the proscenium opening, not more than two openings entering the stage, each not to exceed 2 m2 and fitted with self-closing fire resistant doors. d) Every place of assembly in which projection of motion pictures by light is made shall have the projection apparatus enclosed in a fire resisting fixed booth in accordance with good practice in accordance with the list of standards as specified in Schedule V (27), except that such booth shall not be required where no nitrocellulose motion picture film is used. 4.5 Business Buildings (Group E) 4.5.1 Life Safety Not less than two exits shall be provided for every floor, including basements occupied for office purposes or uses incidental thereto. 4.5.2 Fire Protection a) For Subdivision E-2, the requirement shall be provision of automatic fire detection alarm system, while for fire protection, CO2 and/or foam based installation to be planned based on the requirements. b) For Subdivision E-3, E-4 and E-5, the requirement shall be provision of automatic fire detection alarm system, while for fire protection, any or combination of clean agents, mist technologies, hypoxic air technology, etc, may be planned for appropriate/special situations/locations. Electrical panels may be provided with CO2/inert gas flooding system based on the requirement and reliability of power for the functional requirement and performance. 4.6 Mercantile Buildings (Group F) 4.6.1 Life Safety 4.6.1.1 Open air mercantile operations, such as open air markets, petrol filling stations, roadside stands for the sale of a farm produce and other outdoor mercantile operations shall be so arranged and conducted as to maintain free and unobstructed ways of travel at all times to permit prompt escape from any point of danger in case of fire or other emergency, but no dead-ends in which persons might be trapped due to display stands, adjoining buildings, fences, vehicles or other obstructions. 4.6.1.2 If such mercantile operations are conducted in roofed-over areas, these shall be treated as mercantile buildings, provided canopies over individual small stands to protect merchandise from the weather shall not be construed to constitute buildings for the purpose of the Notification. 4.6.2 Exception and Deviation Any mercantile occupancy, where goods of a highly hazardous nature are predominant, shall be considered under Group J occupancy for the purpose of the Notification. 4.7 Industrial Buildings (Group G) 4.7.1 Fire Prevention 4.7.1.1 Fire separating walls, fire separating floors and fire partitions Fire separating walls shall be provided between two buildings or between two blocks inside a building, having different fire hazards in accordance with the provisions of this Part. The areas having storage, manufacturing, hazardous activities such as paint store, oil storage, spray booths, etc, shall be separated from non-hazardous Tripura Fire Safety Rules, 2026 Page 88 of 169 areas like administrative office, staff canteen, etc by fire rated walls/doors of 120 min fire resistance rating. The fire resistance rating of high hazardous areas like petrochemical, explosives shall be 240 min. The fire separating wall where provided shall comply with the following requirements: a) The separating wall shall be carried through the roof. This portion of the wall extending above the roof, known as ‘screen wall’ shall be of such a height (in no case less than 600 mm) that the horizontal distance at the level of the top of the screen wall between the roofs of the buildings/compartments being segregated is at least 6 m. b) The screen wall shall be of not less than 230 mm in thickness if it is an extension of a masonry wall, and not less than 150 mm in thickness if it is an extension of a reinforced concrete wall. c) The separating wall need not be extended as a screen wall if the roof of one or both of the buildings/blocks being segregated is of reinforced concrete construction (RCC). d) In the case of buildings of unequal height, windows or other openings in the wall of the higher building overlooking the roof of the lower building and within 6 m, thereof, shall be protected by fire resistant glass assembly or by approved type fire doors unless the roof of the lower building is of reinforced concrete. e) In case the eaves of the higher building fall within 6 m of the roof of the lower building such eaves should be cut-off and the screen wall raised as a parapet, 600 mm high over the roof of the higher building, unless the roof of the lower building is of RCC construction. f) Fire separating walls shall also be extended outwards on both sides by at least 450 mm. g) Doors and window openings in external walls within 3 m of the fire separating walls shall be protected by fire doors having a rating of at least 60 min and window openings may be protected by fire resistant glass assembly having same fire rating. h) In the case of buildings/compartments having north-light roofs when a separating wall runs parallel to the axis of the north-light opening, the screen wall shall be carried through and 600 mm above the ridge of the north light. If, however, the separating wall is at right angles to the axis of the north-light opening, the saw tooth gaps shall be bricked up and the screen wall extended 600 mm above the ridge of the north light as well as beyond the extreme north-light opening. i) Similarly, the thickness of the floor slabs in case of buildings having upper levels shall be designed to provide fire rating as mentioned above. j) Storage areas shall be separated from the remainder of the building/block by fire walls. k) Moderate and high hazard areas in industries to have two fire doors each having 180 min fire resistance rating. 4.7.2 Life Safety 4.7.2.1 In buildings used for aircraft assembly or other occupancy requiring undivided floor areas so large that the distances from points within the area to the nearest outside walls where exit doors could be provided are in excess of 45 m, requirements for distance to exits may be satisfied by providing stairs leading to exit tunnels or to overhead passageways. In cases where such arrangements are not practicable, the Authority may, by special ruling, permit other exit arrangements for single storeyed buildings with distances in excess of the maximum distances specified in 4, if completely automatic sprinkler protection is provided and if the heights of ceiling curtain boards and roof ventilation are such as to minimize the possibility that employees will be overtaken by the spread of fire or smoke within 1.8 m of the floor level before they have time to reach exits, provided, however, that in no case may the distance of travel to reach the nearest exit exceed 65 m where smoke venting is required as a condition for permitting distances of travel to exits in excess of the maximum otherwise allowed. 4.7.2.2 The following shall apply to special purpose industrial occupancies: a) Exits need be provided only for the persons actually employed; spaces not subject to human occupancy because of the presence of machinery or equipment may be excluded from consideration. b) Where unprotected vertical openings are necessary to manufacturing operations, these may be permitted beyond the limits specified for industrial occupancy, provided every floor level has direct access to one or more enclosed stairways or other exits protected against obstruction by any fire in the open areas connected by the unprotected vertical openings or smoke there from. Tripura Fire Safety Rules, 2026 Page 89 of 169 4.7.2.3 The following shall apply to high hazard industrial occupancies: a) From every point in every floor area, there shall be at least two exits accessible in different directions; where floor areas are divided into rooms, there shall be at least two ways of escape from every room, however small rooms, except toilet rooms, so located that the points of access thereto are out of or suitably shielded from areas of high hazard. b) In addition to types of exits for upper floors specified for Group G occupancies, slide doors accommodating aircraft may be used to escapes may be used as required exits for both new and existing buildings. NOTE — All high hazard industrial occupancies shall have automatic sprinkler protection or such other protection as may be appropriate to the particular hazard, including explosion venting for any area subject to explosion hazard, designed to minimize danger to occupants in case of fire or other emergency before they have time to utilize exits to escape. 4.7.3 Additional Precautions a) In any room in which volatile flammable substances are used or stored, no device generating a glow or flame capable of igniting flammable vapour shall be installed or used, such a room shall be provided with a suitably designed exhaust ventilation system (see Annex M). b) For detailed information on fire safety of certain individual (specific) industrial occupancies, reference may be made to good practice in accordance with the list of standards as specified in Schedule V (28). c) Fire protection considerations for venting industrial occupancies shall be as in Annex M. 4.8 Storage Buildings (Group H) 4.8.1 Life Safety 4.8.1.1 Every area used for the storage of hazardous commodities shall have an exit within 22.5 m of any point in the area where persons may be present or 35 m where automatic sprinkler protection is provided. 4.8.1.2 Every storage area or space exceeding 1400 m2 gross area, or where more than 10 persons may be normally present shall have at least two exit access doors leading to the corridors in exit access, which can be readily opened. This shall not be subject to locking so long as any persons are inside and shall not depend on power operation. Exits in such cases shall be as remote from each other as practicable. For warehouses, natural draft smoke venting shall utilize roof vents or vents in walls at or near the ceiling level; such vents shall be normally open, or, if closed, shall be designed for automatic opening in case of fire, by release of smoke sensitive devices. 4.8.1.3 The following special provisions shall apply to aircraft hangers: a) Exits from aircraft hangers (storage or servicing areas) shall be provided at intervals of not more than 45 m on all exterior walls of aircraft hangers. There shall be a minimum of two exits serving each aircraft storage or servicing areas. Horizontal exits through interior fire walls shall be provided at intervals of not more than 30 m. ‘Dwarf’ or ‘smash’ b) comply with these requirements. All doors designated as exits shall be kept unlocked in the direction of exit travel while the area is occupied. c) Exits from mezzanine floors in aircraft storage or servicing areas shall be so arranged that the maximum travel to reach the nearest exits from any point on the mezzanine shall not exceed 22.5 m. Such exits shall lead directly to a properly enclosed stairwell discharging directly to the exterior or to a suitably cut-off area or to outside fire escape stairs. 4.8.1.4 The following special provisions shall apply to grain elevators: a) There shall be at least one stair tower from basement to first floor and from the first floor to the top floor of workhouse which is enclosed in a dust tight non-combustible shaft. b) Non-combustible doors of self-closing type shall be provided at each floor landing. Tripura Fire Safety Rules, 2026 Page 90 of 169 c) An exterior fire escape of the stair or basket ladder type shall be provided from the roof of the workshop to ground level or the roof of an adjoining annexed with access from all floors above the first. d) An exterior fire escape of either the stair or basket ladder type shall be provided from the roof of each storage annexed to ground level. 4.8.1.5 For provisions relating to car parking facilities, see Annex H. 4.8.2 Additional Precautions Requirements specified in 4.7.3 (a) shall apply to Group H occupancies also. 4.9 Hazardous Uses (Group J) 4.9.1 Life Safety Requirements specified in 4.7.2.3 shall apply to Group J occupancies also. 4.9.2 Additional Precautions The following requirements shall apply to all Group J occupancies, as applicable: a) Hazardous buildings shall have vapour/flame/ember/spark detectors and explosion suppression systems depending on the type of fire hazard involved. b) Each building where gas is employed for any purpose shall be provided with an approved outside gas shut-off valve conspicuously marked.. c) Each boiler room or room containing a heating plant shall be separated from the rest of the building by a separating wall. d) In any room in which volatile flammable substances are used or stored, no device generating a spark, or glow flame capable of igniting flammable vapour shall be installed or permitted unless it is enclosed in a flameproof enclosure. e) The use, handling, storage and sale of gasoline, fuel oil and other flammable liquids shall not be permitted in Group J occupancies unless such use, handling, storage and sale is in accordance with appropriate legislation in force. f) All openings in exterior walls except wall vents shall be protected by a fire stop assembly as in 2 and they shall be fixed, automatic or self-closing. Wall vents having an area of not less than 100 cm2 each shall be placed in the exterior walls near the floor line, not more than 1800 mm apart horizontally. Each building shall be provided with a power driven fan exhaust system of ventilation which shall be arranged and operated so as to produce a complete change of air in each room every 3 min. g) Each machine in dry-cleaning establishments which uses flammable liquid shall have an adequate steam line or any other suitable extinguishing agent directly connected to it, so arranged as to have the agent automatically released to the inside of each machine should an explosion occur in the machine. h) Equipment or machinery which generates or emits combustible or explosive dust or fibres shall be provided with an adequate dust collecting and exhaust system. Tripura Fire Safety Rules, 2026 Page 91 of 169

Previous and next

All provisions of Tripura Fire Safety Rules 2026

Questions people ask

Is rule 15 of Tripura Fire Safety Rules 2026 still in force?

No repeal of Tripura Fire Safety Rules 2026 is recorded.