ANNEX M

ANNEX M (Clause 4.7.3) FIRE PROTECTION CONSIDERATIONS FOR VENTING IN INDUSTRIAL BUILDINGS M-1 APPLICATION M-1.1 The provisions given below are applicable only to single storey industrial buildings (factories and storage buildings) covering large floor areas without sub-dividing/separating walls which are usually designed to meet modern production methods. M-1.2 The requirements of fire and explosion venting of industrial buildings, as dealt with in this section, fall under two categories: a) Smoke and fire venting, and b) Explosion relief vents. M-2 SMOKE AND FIRE VENTING M-2.1 The basic considerations for formulating the design and other requirements for smoke and fire vents are as given in M-2.1.1 to M-2.1.20. M-2.1.1 The smoke and hot combustion products from a fire, being lighter than the surrounding air, tend to rise, and on reaching the roof or ceiling spread out (mushroom) on all sides and form a layer which floats on top of the cold air beneath. In the absence of vents, this layer becomes progressively deeper until the whole building is filled with hot smoky gases. The time consumed for this to happen may be only a few minutes, depending on variables like, type of materials on fire, process/storage conditions involved, etc. M-2.1.2 The hot gases at the roof level moved by convection currents contribute to rapid lateral spread of fire. M-2.1.3 The provision of properly designed and suitably located vents in adequate number helps the speedy removal of smoke and hot gases, thereby preventing spread of fire, besides reducing risks of explosion of un- burnt gases and reducing damage to the contents and structure of the building by heat and smoke. In addition, they facilitate firefighting operations, and minimise personal hazards to the firemen. M-2.1.4 The time taken for accumulation of smoke and hot gases within a building on fire being very short, the venting devices installed shall be designed to operate in the early stage of the fire and must be automatic so as to ensure speed and efficiency in their operation. M-2.1.5 The smoke and fire venting system shall be designed in such a manner as to keep the temperature of the combustion products from the fire as low as possible, preferably below approximately 150°C. M-2.1.6 Automatic venting systems are complementary to the fire extinguishing systems, and automatic sprinklers, where provided, should operate before the operation of the vents; otherwise, venting may delay sprinkler operation. M-2.1.7 It is easier to vent a building of smoke than clear it of smoke once it has been filled. M-2.1.8 Venting is particularly desirable in large area industrial buildings or warehouses, windowless buildings, underground structures or in areas housing hazardous operations. Automatic fire vents shall be provided for all industrial occupancies (including storage buildings) classified as medium hazard or above having floor areas exceeding 750 m2, irrespective of whether they are compartmentalized or not. M-2.1.9 These provisions do not cover other aspects, of ventilation (or lighting) designed for regulation of temperature within a building for personal comfort or meeting process needs. M-2.1.10 Similarly, fire and smoke venting requirements as given here under are also not applicable to multi - storied buildings, as their requirements are different and more complex. M-2.1.11 It is difficult to determine precise venting requirements on account of the many variables involved. For instance, the rate of combustion varies appreciably according to the nature, shape, size and packaging of the combustible materials as well as the size, height and disposition of the stacks of materials. M-2.1.12 In industrial buildings of floor area less than 750 m2 and used as low fire hazard occupancies, conventional ventilators fitted high up near the eaves of the external walls may serve as vents for smoke and hot gases, provided care is taken to ensure that they are kept open at all times or are designed to open automatically in case of fire. Tripura Fire Safety Rules, 2026 Page 122 of 169 M-2.1.13 Extinction of fires by closing the doors and windows is not likely in the case of industrial buildings because of their large size, where sufficient air to sustain the fire at least in the initial stages can be expected to be present. M-2.1.14 Of the two types of building ventilation, namely, vertical and horizontal, vertical ventilation is the one commonly adopted in the case of single storey industrial buildings. M-2.1.15 Since 70 to 80 percent of heat produced in a fire is convective heat, the ventilation system has to be suitably designed to ensure early outflow of the heat and thereby minimise fire spread. M-2.1.16 Combustible roof linings shall be avoided, as they themselves will contribute to the spread of fire, thereby multiplying the venting problems. M-2.1.17 A wind blowing across a flat roof or a roof with a pitch under 40° produces a negative pressure, that is, it tends to draw gases out of the building and so aids venting of hot gases. Wind blowing across a roof of pitch greater than 40° will draw gases out on the leeward side, but oppose outward flow on the windward side of the roof. M-2.1.18 For vents to work at full efficiency, the area of the inlets for cold air entering the compartment must equal at least the total area of the vents. Ideally, the inlets shall be as close to the ground as possible. M-2.1.19 Where roof vents are installed in a single-storey building any neighbouring buildings, particularly those of more than one storey, will be subject to some degree of exposure hazard either from flying birds or radiation, or both, as a result. M-2.1.20 If vents are to be installed, the size, design, number and disposition of the vents and the associated roof screens/curtain boards have to be assessed after careful analysis of the various factors stated under M- 2.1.11, as well as other related factors like type of building construction, nature and height of roof, process hazards, exposure hazard, etc. M-2.2 Venting Area M-2.2.1 The estimated requirements for ventilation are largely based on the assumed build-up of the fire from the time of initial outbreak to the time of effective fire fighting action by fire brigade. M-2.2.2 The vent area required to be provided shall be approximately proportional to the perimeter of the fire area, because the entrained air forms the bulk of the vented gases. M-2.2.3 The effective area shall be the minimum cross-sectional area through which the hot gases must flow out to the atmosphere. M-2.2.4 No consideration shall be given to the increased air movement obtained by power operated fans, since it must be assumed that in the event of fire, power will be interrupted, or fans damaged by heat. M-2.2.5 The total vent areas to be provided shall be as per the following ratios of effective area of vent openings to floor area for various occupancy classifications indicated: a) Low heat release content — 1 : 150 (Sub-division G-1) b) Moderate heat release content — 1 : 100 (Sub-division G-2) c) High heat release content — 1 : 30 to 1 : 50 (Sub-division G-3) M-2.3 Types of Vents M-2.3.1 Venting shall be accomplished by any of the types such as monitors continuous gravity vents, until type vents or sawtooth roof skylights. M-2.3.2 Where monitor type vents are installed, wire glass or metal panels shall be used only if the sash is arranged to open automatically. M-2.3.3 The use of plain thin glass for venting shall be avoided on account of its unpredictable behavior during fire. However, if glass or other suitable plastic sheet materials with early disintegration characteristics are used, they should be designed for automatic operation. Tripura Fire Safety Rules, 2026 Page 123 of 169 M-2.3.4 Where monitors or unit type vents are used, the panels shall be hinged at the bottom and designed to open automatically. Both sides of the vents shall be designed to vent simultaneously to ensure that their effectiveness at the time of fire is not in any way impeded by wind direction. M-2.3.5 Where movable shutters are provided for continuous gravity vents, these shall open automatically in the event of fire. M-2.3.6 Unit type vents shall be of relatively small area, ranging between 1 m2 and 9 m2, having light weight metal frames and housing with hinged dampers which shall be designed for both manual and automatic operation. M-2.3.7 Sawtooth roof skylight shall be considered as satisfactory for venting purposes only when designed for automatic operation. M-2.3.8 Likewise, exterior wall windows shall not be reckoned as satisfactory means for venting of fire gases and smoke in industrial buildings. However, they may be reckoned as additional means of venting when, they are located close to the caves and are provided with ordinary glass or movable sash arranged for both manual and automatic operation. M-2.3.9 Baffles shall not be installed inside vents, as they greatly reduce the effective area for venting. M-2.4 Vent Operation M-2.4.1 The vents shall be automatic in operation, unless where specified in these provisions that they shall be designed for both manual and automatic operation. M-2.4.2 The release mechanism shall be simple for operation and independent of electrical power, since electrical services may be interrupted by fire. M-2.4.3 The automatic operation of vents shall be achieved by actuation of fusible links or other types of heat and smoke detectors, or by interlocking with operation of sprinkler system or any other automatic fire extinguishing system covering the area. Following their release, the vents shall be designed to open by a system of counterweights and associated equipment utilizing the force of gravity or spring loaded levers. M-2.4.4 Automatic fire alarm system, where installed, shall be coupled to the automatic vents to ensure simultaneous operation. M-2.4.5 Automatic sprinklers, where installed, shall operate before the vents open order to avoid any likely delay in sprinkler operation. However, heat actuated devices used for vent release shall be suitably shielded from sprinkler discharge so that water does not delay their action. Further, provision of operating the vents manually may also be provided. M-2.4.6 Premises where height of roof apex is 10 m or more or where the materials handled or stored have high smoke producing characteristics, in addition to fusible links, the vent release mechanism shall be interlinked to smoke actuated automatic fire detectors to ensure early operation of vents. M-2.4.7 Non-corrosive materials shall be used for hinges, hatches and other related parts to ensure long fail- safe operation of the vents. M-2.4.8 In case of any doubts regarding the types of vents required to be installed for any particular occupancy, authorities having jurisdiction shall be consulted. M-2.5 Size, Spacing and Disposition of Vents M-2.5.1 Vents shall be correctly sited to ensure their functional efficiency. Ideally, they shall be sited at the highest point in each area to be covered. M-2.5.2 They shall, as far as possible, be located immediately above the risk to be protected so as to allow free and speedy removal of smoke and other combustion products in the event of fire. M-2.5.3 The minimum dimension for an effective vent opening shall be not less than 1.25 m in any direction. M-2.5.4 The spacing of the individual vent shall be based on the principle that more number of well distributed smaller vents are more effective than fewer number of badly located larger vents. M-2.5.5 The maximum spacing between vents for the three occupancy classifications shall be as follows: a) Low heat release content : 45 m between centres b) Moderate heat content : 36 to 37 m between release centres c) High heat release : 22.5 to 30 m between centres, depending on the severity of fire potential. M-2.5.6 Vents shall be placed in a sheltered situation where advantage can be taken of the prevailing wind. The design of the vent shall be such as to produce a suction effect. A wind blowing across a flat roof or one with a pitch of 40° produces a negative pressure, that is, it tends to draw gases out of the building and so aids venting Tripura Fire Safety Rules, 2026 Page 124 of 169 of hot gases. Wind blowing across a roof of pitch greater than 40° will draw gases out of the leeward side, but oppose outward flow on the windward side of the roof. M-2.5.7 Low level inlets, with total area not less than the total area of vents, shall be provided to permit outside air to be drawn in to aid automatic venting. These inlets, which may be in the form of doors, windows or such other openings, shall be designed for manual operation when desired. M-2.6 Roof Screens or Curtain Boards M-2.6.1 Industrial buildings with large areas and having no subdivision/separating walls limiting the area of individual compartments to 750 m2 or less, shall be provided with roof screens or curtain boards. These screens which extend from the roof downwards at specific intervals not only prevent lateral spread of heat and smoke in the event of fire below, but substantially assist in early operation of automatic sprinklers and vents. M-2.6.2 They shall be of sheet metal or any other substantially non-combustible material strong enough to withstand damage by heat or impact. M-2.6.3 They shall be reasonably gas-tight, although small openings for passage of pipes, conduits, etc, shall be permitted. M-2.6.4 They shall extend down from the roof/ceiling for a minimum depth of 2.2 m. Around specific hazards, the depth shall be 4 m. Where roof/ceiling height exceeds 15 m they shall extend down to within 3 m of the floor. For pitched sawtoothed roofs, they shall extend down to truss level dividing the roof into compartments. M-2.6.5 In moderate hazard occupancies, the distance between the screens/curtain boards shall not exceed 75 m and the curtained areas shall be limited to a maximum of 4 500 m2. M-2.6.6 In high hazard occupancies, the distance between screens shall not exceed 30 m and the curtained area shall be limited to 750 m2. M-2.6.7 The curtained roof area shall be so arranged that they effectively aid in the venting of smoke and hot gases through the automatic vents provided in each area. M-2.6.8 In sprinklered buildings, the screens shall preferably be so located as to coincide with the individual sprinkler system areas. M-3 EXPLOSION RELIEF VENTS M-3.1 Industrial premises where combustible dusts can accumulate or where flammable gases, vapours or mists in explosive concentrations may be present are constantly exposed to explosion hazards. Pressures developed by such explosions may be of the order of 7 × 105 Pa and ordinary buildings will not be able to withstand the shock of such pressures. Hence, such buildings require explosion relief vents for preventing structural damage. M-3.2 Basic Principle/Considerations M-3.2.1 Most ordinary building walls will not withstand a sustained internal pressure as great as 6.9 × 103 Pa. Hence, explosion relief vents for buildings must be designed to operate at pressures well below those at which the building walls will fail. M-3.2.2 There is a rise in pressure during an explosion within an enclosure even with open, unobstructed vents, and any delay in opening the venting devices increases that pressure. M-3.2.3 Structural damage can be minimised by locating hazardous operations or equipment outside buildings and cut-off from other operations by a pressure resisting wall. Such isolated processes or equipment shall be housed in single-storey buildings properly vented and a device provided at the inlet of the collector which will prevent an explosion from blowing back through the duct work and into the building. M-3.2.4 Where highly hazardous operations cannot be located outside of main buildings they shall be segregated by pressure resisting walls and each such unit shall be ventilated outdoors. External walls may be of heavy construction, if equipped with suitable vents or high weight panels which blow out easily. M-3.2.5 Operations or equipment involving explosion hazards shall not be permitted in basements or areas partially below grade. M-3.2.6 Fire can be expected to follow an explosion in most occupancies, so that any fixed fire extinguishing equipment, like sprinklers, if installed, shall be such that only the minimum damage is caused to it. M-3.2.7 For a given material, the finer the particle size of the dust, the more violent is the explosion. Some materials, such as aluminium powder, hydrogen, and acetylene, are difficult to vent effectively due to the rapid rate of pressure rise. Some slow burning materials, such as coal dust in a confined space, may do much damage because of the longer duration of their presence. Some dusts, such as magnesium, titanium and zirconium and several metal hydrides may react with and ignite in some common inert gases, such as nitrogen and carbon dioxide. Tripura Fire Safety Rules, 2026 Page 125 of 169 M-3.2.8 The maximum explosion pressure in a vented structure decreases as the size of the vent increases, but is independent of the rupturing pressure of a diaphragm. M-3.2.9 The most effective vent for the release of explosion pressures is an unobstructed vent opening. M-3.2.10 Pressure required to rupture diaphragms of the same area and material directly varies with the thickness of the material. M-3.2.11 The slower the rate of pressure rise, the more easily can the explosion be vented. M-3.2.12 The degree of venting required is directly proportional to the degree of explosion hazard. M-3.2.13 Experience has shown that most explosions of dusts, vapours and gases do not involve a large part of the total volume of the enclosure, and frequently occur near the upper or lower limits of the explosive range. Consequently, such explosions are relatively weak compared with the optimum. M-3.2.14 Rectangular unrestricted vents are as effective as square vents of equal area. M-3.3 Types of Explosion Relief Vents M-3.3.1 The explosion relief vents shall be any one or more of the following types, depending on individual requirements as assessed by the Authority. Open or unobstructed vents, louvres, open roof vents, hanger type doors, building doors, windows, roof or wall panels or movable fixed sash. M-3.3.2 The effect or external wind pressure or suction on these devices shall be taken into consideration while designing and selecting the type of vents, since wind pressures may reach over 2 × 105 Pa in severe wind storms. M-3.3.3 The type of vent for explosion relief for any occupancy shall be selected with life safety as the primary aim followed by minimum damage to property. M-3.3.4 Where large hanger type doors of metal curtain doors in side walls are used as vents, care shall be taken to ensure that they are kept wide open during operations. M-3.3.5 Where weather hoods are used to cover roof vents, they shall be as light as possible and lightly attached so as to enable them to be blown off quickly when an explosion occurs. M-3.3.6 Doors and windows when used as explosion vents shall be installed to swing outwards. Doors shall have friction, spring or magnetic latches that will function automatically to permit the door to open under slight internal pressure. M-3.3.7 Movable sash shall be of the top or bottom hinged or protected type. These shall be equipped with a latch or friction device to prevent accidental openingdue to wind action or intrusion. Such latches or locks shall be well maintained. M-3.3.8 Fixed sash shall be set in place with very light wall anchorages, or, if tight, shall be securely fitted and glazed with plastic panes in plastic putty. M-3.3.9 Where the process is such that the whole of a building or a room may be desirable to arrange for a lightly constructed wall or roof to collapse and thus avert the worst effects of an explosion. M-3.4 Design, Size and Disposition of Vents M-3.4.1 The required area of explosion vents shall ordinarily depend on the expected maximum intensity of an explosion in the occupancy, the strength of the structure, the type of vent closure and other factors. M-3.4.2 Venting shall be planned in such a manner as to prevent injury to personnel and damage to exposure. In congested locations, substantial ducts or diverters shall be provided to direct the blast. M-3.4.3 When ductwork is used, the ducts shall be of sufficient strength to withstand the maximum expected explosion pressure. M-3.4.4 Where explosions are likely within duct and piping systems, they shall be vented by the use of suitable diaphragms designed to blow out at a predetermined pressure. There shall be no physical connection between ductwork system for more than one collector. M-3.4.5 In large structures, the position of vents shall be relative to the point of origin of explosion, when it can be determined. M-3.4.6 Where relatively slow explosions involving coal dust, chlorinated solvents, etc, are involved, light, hinged swinging panels may be preferred to diaphragm type of vents. M-3.4.7 Obstructions of any kind blocking the vents from the risk covered shall be avoided, particularly where risks of rapid violent explosions are present. M-3.4.8 Counter weights add to the inertia of the vents and so shall be avoided. M-3.4.9 Various relieving devices, including devices actuated by detonators, shall start to open at as low a pressure as possible. They shall be of light construction, so that full opening can be quickly attained. Tripura Fire Safety Rules, 2026 Page 126 of 169 M-3.4.10 Vents shall be of such size and design as to prevent rupture of the protected device or apparatus. M-3.4.11 Skylights or monitors with movable sash that will open outwards, or fixed sash containing panes of glass or plastic that will blow out readily under pressure from within, can be used to supplement wall vents or windows, provided resistance to their displacement or opening is kept as low as consistent with the requirements for structural strength. M-3.4.12 Flexible plastic sheets when used for vent closures shall be installed in slotted frames in such a way that pressure from within bulges the sheets and releases them from the holding frame. M-3.4.13 Fragile sheets made of plastic, when used for vent closures, shall be thin sheets that will crack or rupture under less pressure than single strength glass. For this reason use of transparent or translucent plast ic sheets is more advantageous than use of glass in window sash. M-3.4.14 If closed vents are used they shall be larger in area than unenclosed vents to provide equivalent explosion pressure relief. M-3.4.15 Small enclosures, such as machines, shall be vented more generously than buildings, because if an explosion occurs in a machine, its entire volume may be involved. M-3.4.16 Vents for the protection of buildings and equipment shall be installed on the following basis: a) Small enclosures of less than 30 m3, machines and ovens of light construction : 1 000 cm2 for each 0.3 m3 to 0.9 m3. b) For small enclosures of more substantial construction having reasonably high bursting strength : 1000 cm2 for each 0.9 m3. c) Fairly large enclosures of 30 to 700 m3, such as bins, silos, rooms, storage tanks, etc : 1000 cm2 for each 0.9 m3 to 1.5 m3. In these cases, attempt shall be made to the extent possible to predict the likely point of origin of the explosion in relation to the vent. d) Large rooms and buildings over 700 m3 containing hazardous equipment comprising a small fraction of the entire volume: 1) For heavy reinforced concrete, walls: 100 cm2 for each 2.25 m3. 2) For light reinforced concrete, brick or wood construction: 1000 cm2 for each 1.65 m3 to 2.25 m3. 3) For lightweight construction such as prefabricated panels: 1000 cm2 for each 1.5 m3 to 1.65 m3. e) Large rooms or building over 700 m3 containing hazardous equipment comprising a large part of the entire volume of a room or building shall be vented as generously as possible: 1000 cm2 for each 0.3 m3 to 1.05 m3. f) In order to obtain these ratios, the size of the building or room must be limited. For some hazardous materials, such as hydrogen, acetylene, carbon disulphide, etc, these limits are extremely low. g) Emphasis shall always be placed on segregating hazardous areas by means of firewalls or separating walls to prevent spread of fire. h) Interior walls of light construction, such as tile, shall be avoided in hazardous locations, since they can cause injuries to personnel in the event of an explosion. Tripura Fire Safety Rules, 2026 Page 127 of 169 CHECK LIST Category of Building based on occupancy as per Schedule- I Name of Industry/Establishment Category Group Sub Category Address of the Industry/Establishment Total area of building/premises in sqm (round off to next whole number) Sl. No. Passive measures of building and Active measures (as per scale of IS) in building Available (Yes/No) Furnish Details in Unit, Measurement, Capacity, etc) 1. Access to Building 1) Approach Road width Mtrs 2) Gate width Mtrs 3) Access ways (open spaces) around the building Front side : Mtrs Left side : Mtrs Right side : Mtrs Rear side : Mtrs Turning Radius : Mtrs 2. Number, Width Type & Arrangement of Exits 1) Number of staircase i) Upper floors ii) Basements 2) Width of staircase i) Upper floors ii) Basements 3) Protection of exits i) Number of Fire Resistant Door ii) Fire resistance rating (in minute) 4) No. of continuous staircase to terrace 5) Width of corridor 6) Door size 7) Emergency Exit 8) Number of Ramp i) Upper floors ii) Basements 9) Width of Ramp i) Upper floors ii) Basements 10) Sloping ratio of Ramp Schedule- II [See rule 4] Tripura Fire Safety Rules, 2026 Page 128 of 169 3. Fire Extinguishers (for First-Aid fire fighting) 1) CO2 2) Dry Chemical Powder (ABC Type) 3) Dry Chemical Powder (BC Type) 4) Dry Chemical Powder (D Type) 5) Wet Chemical 6) Water Mist 7) CAF 8) Others 4. First-Aid Hose Reel 1) Total number in each floor 2) Length of hose reel hose 3) Nozzle diameter 5. Foam and Foam making accessories (For Flammable liquids— Petrol, Gasoline, Kerosene, Grease, Acetone, paints etc. manufacturing or handling large scale units where the blanketing effects is essential for fire fighting) 6. Automatic Fire Detection & Alarming System 1) Type of detectors 2) Location of main panel 3) Location of repeater panel 4) Alternate source of power 5) Hooter 7. Manually Operated Electronic Fire Alarm system 8. Public Address System 9. Automatic Sprinkler System 1) Basement/negative basement if available 2) Upper floors 3) Sprinkler above false ceiling 10. Internal Hydrant system 1) Wet Riser / Down-comer mains Dia: Thickness: 2) Number of Inlet (Ground level) 11. Yard Hydrants Number of hydrant points : 12. Hose box with accessories 1) Hose Box (Double door) 2) Delivery Hose 3) Branch 4) Fireman Axe 13. Pumping Arrangement 1) Ground level Pumps i) Discharge of main pump ii) Head of main pump iii) Number of main pump iv) Jockey pump out put v) Jockey pump head vi) Stand by pump output (Diesel) vii) Stand by pump head (Diesel) viii) Auto pump controller Tripura Fire Safety Rules, 2026 Page 129 of 169 2) Terrace level Pumps i) Discharge of pump ii) Head of pump iii) Power supply iv) Auto pump controller 14. Captive Water Storage for Fire Fighting 1) Underground tank capacity 2) Terrace tank capacity 15. Exit Signage 16. No. of Fireman’s Lifts 17. Standby Power Supply 18. Refuge Area 19. Fire Compartment 1) Number of Fire Compartment 2) Fire resistance rating (in minute) 20. Smoke Exhaust system 21. Fire Fighters / Fire Safety Officer for 24X7 duty 22. Breathing Apparatus Set (for rubber or other toxic gas based industries) 23. Display of DO’s and Don’ts in case of fire at conspicuous places 24. Display of Emergency Telephone numbers at conspicuous places 25. Other fire prevention and life safety measures (specify if available) 26. PPE [Safety Helmet, Eye Protector, Ear Protector, Face Protector, Face Mask (Respiratory Protection), Safety Gloves, Safety Shoes, Hi-visibility Clothing, Safety Harness] I/We solemnly confirm and declare that the information provided above is correct to the best of my/our knowledge and belief and I/We have not concealed any material information. ___________________________________________ Signature with date (empanelled agency) Full Name: __________________________________ License No. _________________________________ Contact No. __________________________________ Official Seal _________________________________ Signature with date (owner or occupier) Full Name: Tripura Fire Safety Rules, 2026 Page 130 of 169 REQUISITE DOCUMENTS FOR FIRE SAFETY CERTIFICATE (FIRE NOC) BASED ON SELF CERTIFICATION, FIRE SAFETY RECOMMENDATION AND FIRE SAFETY CERTIFICATE (FIRE NOC): Sl. No. Fire Safety Certificate (Fire NOC) based on Self Certification 1. Self Certification in Form- D 2. Authorization letter of Power of Attorney (If someone applied for Fire NOC on behalf of the owner) 3. For existing building : i) Building Plan approved by the ULBs/RLBs (comprises Site Plan, Section Plan, Elevation, Floor Plans, Terrace Plan) shall be uploaded. ii) If the building is more than 30 years old, the Building Technical stability certificate for occupancy signed by the approved building planner or any engineer not below the rank of Asstt. Engineer shall be uploaded. iii) Property Tax bill containing commercial or residential area shall be uploaded (for ULBs area). OR For proposed building: Drawings of Building Plan (comprises Site Plan, Section Plan, Elevation, Floor Plans, Terrace Plan) by mentioning the occupancy details signed by the registered planner of ULBs/RLBs. (Emergency evacuation plan and Block Plan of building should be given with the details such as width of the main road on which plot is located, activities of the adjacent plots, width of main entrance, other entrance to the plot, Basement if any. Details of the activity carried out in Basement, approach roads around the building, and other details for industrial activities like utility block, raw material & finish goods storage, tank farm area, storage of hazardous gases, water reactive chemicals/metals, liquids etc, for e.g. LPG, petroleum products, etc.) 4. List of raw material (including Consumable Materials like LPG Cylinders, Storage Qty for Diesel Generators etc) and finished goods with their quantity, their storage place in the plant should be marked on block plan. 5. List of machineries. 6. Details of Centralized Air Conditioning System, Provision of Fire Dampers, Ventilation systems etc., If available. 7. Copy of Registration and License of the company/industry should be submitted. 8. Land ownership documents (Khatian and other relevant documents) 9. Valid Lease agreement with property owner (if applicable) 10. Photographs showing fire prevention & life safety equipment already installed, [Geo-tagging photographs shall be taken in such a manner that the area where the fire fighting equipment is installed is clearly visible] Schedule-III [See rule 6 & 7 ] Tripura Fire Safety Rules, 2026 Page 131 of 169 Sl. No. Fire Safety Recommendation 1. Authorization letter of Power of Attorney (If someone applied for Fire NOC on behalf of the owner) 2. For existing building : i) Building Plan approved by the ULBs/RLBs (comprises Site Plan, Section plan, Elevation, Floor Plans, Terrace Plan) shall be uploaded. ii) If the building is more than 30 years old, the Building Technical stability certificate for occupancy signed by the approved building planner or any engineer not below the rank of Asstt. Engineer shall be uploaded. iii) Property Tax bill containing commercial or residential area shall be uploaded (for ULBs area). OR For proposed building: Drawings of Building Plan (comprises Site Plan, Section plan, Elevation, Floor Plans, Terrace Plan) by mentioning the occupancy details signed by the registered planner of ULBs/RLBs. (Emergency evacuation plan and Block Plan of building should be given with the details such as width of the main road on which plot is located, activities of the adjacent plots, width of main entrance, other entrance to the plot, Basement if any. Details of the activity carried out in Basement, approach roads around the building, and other details for industrial activities like utility block, raw material & finish goods storage, tank farm area, storage of hazardous gases, water reactive chemicals/metals, liquids etc, for e.g. LPG, petroleum products, etc.) 3. List of raw material (including Consumable Materials like LPG Cylinders, Storage quantity for Diesel Generators etc) and finished goods with their quantity, their storage place in the plant should be marked on block plan. 4. List of machineries. 5. Details of Centralized Air Conditioning System, Provision of Fire Dampers, Ventilation systems etc., If available. 6. Copy of Registration and License of the company/industry should be submitted. 7. Land ownership documents (Khatian and other relevant documents) 8. Valid Lease agreement with property owner (if applicable) Sl. No. Fire Safety Certificate (Fire NOC) [after compliance of Fire Safety Recommendation] 1. Self Certification in Form- G 2. Authorization letter of Power of Attorney (If someone applied for Fire NOC on behalf of the owner) 3. Certificate from empanelled agency in Form-A on agency letter head signed by both owner or occupier and empanelled agency regarding compliance of the Fire Prevention and Life Safety Measures according to Fire Safety Recommendation along with Check List in Schedule-II shall be uploaded. 4. Electrification certificate along with electrical diagram showing separate circuit. 5. Copy of Fire Safety Recommendation issued earlier. 6. Photographs showing fire prevention & life safety equipment already installed, [Geo-tagging photographs shall be taken in such a manner that the area where the fire fighting equipment is installed is clearly visible] Tripura Fire Safety Rules, 2026 Page 132 of 169 REQUISITE DOCUMENTS FOR EXTENSION OF VALIDITY OF FIRE SAFETY CERTIFICATE (FIRE NOC) BASED ON SELF CERTIFICATION AND FIRE SAFETY CERTIFICATE (FIRE NOC): Sl. No. Extension of validity of Fire Safety Certificate (Fire NOC) based on Self Certification 1) Self Certification in Form- I 2) Authorization letter of Power of Attorney (If someone applied for Fire NOC on behalf of the owner) 3) Fire Safety Certificate (Fire NOC) based on Self Certification (validity to be extended). 4) Photographs showing fire prevention & life safety equipment already installed, [Geo-tagging photographs shall be taken in such a manner that the area where the fire fighting equipment is installed is clearly visible] Sl. No. Extension of validity of Fire Safety Certificate (Fire NOC) 1) Self Certification in Form- K 2) Authorization letter of Power of Attorney (If someone applied for Fire NOC on behalf of the owner) 3) Certificate from empanelled agency in Form-B on agency letter head signed by both owner or occupier and empanelled agency regarding compliance of the Fire Prevention and Life Safety Measures according to Fire Safety Recommendation along with Check List in Schedule-II shall be uploaded. 4) Fire Safety Certificate (Fire NOC) (validity to be extended). 5) Photographs showing fire prevention & life safety equipment already installed, [Geo-tagging photographs shall be taken in such a manner that the area where the fire fighting equipment is installed is clearly visible] Schedule- IV [See rule 8] Tripura Fire Safety Rules, 2026 Page 133 of 169 LIST OF STANDARDS Sl. No. BIS (Bureau of Indian Standards) specification No. Titles 1. 3808 :1979 Method of test for non-combustibility of building materials (first revision) 2. IS/ISO 834-1 : 1999 Fire resistance tests - Elements of building construction: Part 1 General requirements. IS/ISO 834-4 : 2000 Fire resistance tests - Elements of building construction: Part 4 Specific requirements for load bearing vertical separating elements IS/ISO 834-5 : 2000 Fire resistance tests - Elements of building construction: Part 5 Specific requirements for load bearing horizontal separating elements IS/ISO 834-6 : 2000 Fire resistance tets - Elements of building constructions: Part 6 Specific requirements for beams IS/ISO 834-7 : 2000 Fire resistance tests - Elements of building construction: Part 7 Specific requirements for columns IS/ISO 834-8 : 2003 Fire resistance tests - Elements of building construction: Part 8 Specific requirements for non- load bearing vertical separating elements IS/ISO 834-9 : 2003 Fire resistance tests - Elements of building construction: Part 9 Specific requirements for non- load bearing ceiling elements 3. 8757 : 1999 Glossary of terms associated with fire safety (first revision) 7673 : 2004 Glossary of terms for fire fighting equipment (first revision) 4. 8758 : 2013 Code of practice for fire precautionary measures in construction of temporary structures and pandals (second revision) 5. 9668 : 1990 Code of practice for provision and maintenance of water supplies and fire fighting 3844 : 1989 Code of practice for installation and maintenance of internal fire hydrants and hose reels on premises (first revision) 6. 1646 : 2015 Code of practice for fire safety of buildings (general): Electrical installations (third revision) 7. 9457 : 2005 Code of practice for safety colours and safety signs (first revision) 12349 : 1988 Fire protection-Safety sign 12407 : 1988 Graphic symbols for fire protection plans 8. 11360 : 1985 Specification for smoke detectors for use in automatic electrical fire alarm system 9. 655 : 2006 Specification for air ducts 10. 1649 : 1962 Code of practice for design and construction of flues and chimneys for domestic heating appliances (first revision) 1642 : 2013 Code of practice for safety of buildings (general): Details of construction (second revision) 11. 12777 : 1989 Method for classification of flame spread of products 12. 1642 : 2013 Code of practice for safety of buildings (general): Details of construction (second revision) 13. 16246 : 2015 Elastomer insulated cables with limited circuit Integrity when affected by fire – Specification 14. 6044 (Part 1) : 2013 Liquefied petroleum gas storage installations-Code of Practice: Part 1 Residential commercial and industrial cylinder installations Schedule-V Tripura Fire Safety Rules, 2026 Page 134 of 169 15. 2175 : 1988 Specification for heat sensitive fire detectors for use in automatic fire alarm system (second revision) IS/ISO 7240-5 : 2003 Fire detection and alarm systems: Part 5 Point-type heat detectors IS/ISO 7240-7 : 2011 Fire detection and alarm systems: Part 7 Point-type smoke detectors using scattered light, transmitted light or ionization IS/ISO 7240-11: 2011 Fire detection and alarm systems: Part 11 Manual call points IS/ISO 7240-15: 2004 Fire detection and alarm systems: Part 15 Point-type fire detectors using scattered light, transmitted light or ionization sensor in combination with a heat sensor 11360 : 1985 Specification for smoke detectors for use in automatic electrical fire alarm system 16. 2189 : 2008 Code of practice for selection, installation and maintenance of automatic fire detection and alarm system (second revision) 17. 636 : 1988 Specification for non-percolating flexible fire fighting delivery hose (third revision) 884 :1985 Specification for first-aid hose reel for fire fighting(first revision) 901 : 1988 Specification for couplings, double male and double female instantaneous pattern for fire fighting (third revision) 902 : 1992 Specification for suction hose couplings for fire fighting purposes (third revision) 903 : 1993 Specification for fire hose delivery couplings, branch pipe, nozzles and nozzle spanner (fourth revision) 904 : 1983 Specification for two-way and three-way suction collecting heads for fire fighting purposes (second revision) 905 : 1980 Specification for delivery breechings, dividing and collecting, instantaneous pattern for fire fighting purposes (second revision) 906 : 1988 Specification for revolving branch pipe for fire fighting (third revision) 907 : 1984 Specification for suction strainers, cylindrical type for fire fighting purpose (second revision) 908 : 1975 Specification for fire hydrant, stand post type (second revision) 909 : 1992 Specification for underground fire hydrant: Sluice valve type (third revision) 910 : 1980 Specification for combined key for hydrant, hydrant cover and lower valve (second revision) 926 : 1985 Specification for fireman's axe (second revision) 927 : 1981 Specification for fire hooks (second revision) 928 : 1984 Specification for fire bells (second revision) 937 : 1981 Specification for washers for water fittings for fire fighting purposes 939 : 1977 Specification for snatch block for use with fibre rope for fire brigade use (first revision) 940 : 2003 Specification for Portable Fire Extinguisher, Water Type (Gas Cartridge) 941 : 1985 Specification for blowers and exhauster for fire fighting (second revision) 942 : 1982 Functional requirements for 275 l/min portable pump set for fire fighting (second revision) 943 : 1979 Functional requirement for 680 l/min trailer pump for fire brigade use (second-revision) 944 : 1979 Functional requirement for 1800 l/min trailer pump for fire brigade use (second revision) 947 : 1985 Functional requirement for towing tender for trailer fire pump for fire brigade use (first revision) 948 : 1983 Functional requirement for water tender, Type A, for fire brigade use 949 : 2012 Functional requirement for emergency (rescue) tender (third revision) Tripura Fire Safety Rules, 2026 Page 135 of 169 950 : 2012 Functional requirements for water tender, Type B for fire brigade use (third revision) 951 : 2003 Functional Requirements for Crash Fire Tender for Air Fields 952 : 1986 Specification for fog nozzle for fire brigade use (second revision) 955 : 1980 Functional requirements for dry power tender for fire-brigade use (150 kg capacity) (first revision) 956 : 2004, 2010 Functional Requirements for Rescue Tender for Air Fields 957 : 1967 Specification for control van for fire brigade 1941 (Part I) : 1976 Functional requirements for electric motor sirens: Part 1 AC, 3- Phase, 50 Hz, 415 volts type (second revision) 2097 : 2012 Specification for foam making branch pipe and foam inductor (second revision) 2171 : 2017 Specification for portable fire extinguishers,dry powder (cartridge type) 2175 : 1988 Specification for heat sensitive fire detectors for use in automatic detectors for use in automatic fire alarm system (second revision) 2546 : 1974 Specification for galvanized mild steel fire bucket (first revision) 2696 : 1974 Functional requirements for 1125 1/min light fire engine 2745 : 1983 Specification for non-metal helmet for firemen and civil defence personnel (second revision) 2871 : 2012 Specification for branch pipe, universal for fire fighting purposes 2878 : 2004 Specification for fire extinguisher, carbon-dioxide type (portable and trolley mounted) (third revision) 2930 : 1980 Functional requirements for hose laying tender for fire brigade use (first revision) 3582 : 1984 Specification for basket strainers for fire fighting purposes (cylindrical type) (first revision) 4308 : 2003 Specification for dry chemical powder for fire fighting B and C class fires (second revision) 4571 : 1977 Specification for aluminium extension ladders for fire brigade use 4643 : 1984 Specification for suction wrenches for fire brigade use (first revision) 4861 : 1984 Specification for dry powder for fighting fires in burning metals (first revision) 4927 : 1992 Specification for unlined flax canvas hose for fire fighting (first revision) 4928 : 1986 Specification for delivery valve for centrifugal pump outlets (first revision) 4947 : 2006 Specification for gas cartridges for use in fire extinguishers (third revision) 4989 : 2006 Foam concentrate for producing mechanical foam for fire fighting Specification (third revision) 4989 (Part 4) : 2003 Specification for multipurpose aqueous film forming foam liquid concentrate for extinguishing hydrocarbon and polar solvent fires 5131: 2002. Specification for dividing breeching with control, for fire brigade use (second revision) 5290 : 1993 Specification for landing valve (third revision) 5486 : 1985 Specification for quick release knife (first revision) 5505 : 1985 Specification for multi-edged rescue axe (non-wedging) (first revision) 5612 Specification for hose-clamps and hose-bandages for fire brigade use 5612 (Part 1) : 1977 Hose clamps (first revision) 5612 (Part 2) : 1977 Hose bandages (first revision) 5714 : 1981 Specification for hydrant, standpipe for fire fighting (first revision) Tripura Fire Safety Rules, 2026 Page 136 of 169 6026 : 1985 Specification for hand operated sirens (first revision) 6067 : 1983 Functional requirements for water tender, Type 'X' for fire brigade use (first revision) IS/ISO 7240-5 : 2003 Fire detection and alarm systems-Part 5: Point-type heat detectors IS/ISO 7240-7 : 2011 Fire detection and alarm systems Part 7: Point-type smoke detectors using scattered light, transmitted light or ionization IS/ISO7240-11 : 2011 Fire detection and alarm systems Part 11 Manual call points 8090 : 1992 Specification for couplings, branch pipe, nozzle, used in hose reel tubing for fire fighting (first revision) 8096 : 1992 Specification for fire beaters (first revision) 8149 : 1994 Functional requirements for twin CO2 fire extinguishers (trolley mounted) (first revision) 8423 : 1994 Specification for controlled percolating hose for fire fighting (first revision) 8442 : 2008 Specification for stand post type water and foam monitor for fire fighting (first revision) 9972 : 2002 Specification for automatic sprinkler heads (first revision) 10460 : 1983 Functional requirements for small foam tender for fire brigade use 10658 : 1999 Specification for higher capacity dry powder fire extinguisher (trolley mounted) (first revision) 10993 : 1984 Functional requirements for 2 000 kg dry powder tender for fire brigade use 11101 : 1984 Specification for extended branch pipe for fire brigade use 11108: 1984 Specification for portable fire extinguisher halon-1211 type 11833: 1986 Specification for dry powder fire extinguisher for metal fires 12717 1989 Functional requirements of fire fighting equipment High capacity portable pumpset (1100-1600 l/min) 12796: 1989 Specification for fire rake 13039: 1991 Code of practice for provision and maintenance of external hydrant system 13385 : 1992 Specification for fire extinguisher 50 litre capacity wheel mounted water type (Gas cartridge) 13386 : 1992 Specification for 50 litre capacity fire extinguisher, mechanical foam type 14609 : 1999 Specification for ABC dry powder for fire fighting 14933: 2001 Specification for high pressure fire fighting hose 14951 2001 Specification for fire extinguisher, 135 litre capacity mechanical foam type 15051 2002 Specification for high pressure fire hose delivery couplings IS 15105: 2002 / ISO 6182-1 Design and installation of fixed automatic sprinkler fire extinguishing system IS 15220: 2002/ ISO 7201-1 Specification for halon 1211 and halon 1301-fire extinguishing media for fire protection IS 15683: 2006/ ISO 7165: 2009 Portable fire extinguishers Performance and construction- Specification 11360 1985 Specification for smoke detectors for use in automatic electrical fire alarm system IS 15493: 2004/ ISO 14520-1 Gaseous fire extinguishing systems: General requirements IS 15505: 2004/ ISO 14520-6 Gaseous fire extinguishing systems: HCFC Blend A extinguishing systems IS 15506 2004/’ ISO 14520-14 Gaseous fire extinguishing systems-IG 55 extinguishing systems Tripura Fire Safety Rules, 2026 Page 137 of 169 IS 15525: 2004/ ISO 14520-13 Gaseous fire extinguishing systems-IG 100 extinguishing systems IS 15501: 2004/ ISO 14520-15 Gaseous fire extinguishing systems- IG 541 extinguishing systems IS 15497:2004/ ISO 14520-12 Gaseous fire extinguishing systems-IG 01 extinguishing Systems 15519: 2004 Code of practice for water mist fire protection systems - System design, installation and commissioning IS 15517:2004/ ISO 14520-9 Gaseous fire extinguishing. systems-Carbon dioxide, total flooding and local application including in cabinet subfloors systems IS 15517:2004/ ISO 14520-9 Gaseous fire extinguishing systems — HFC 227ea (Hepta Fluoro Propane) extinguishing system 18. 2190: 2010 Code of practice for selection, installation and maintenance of portable first-aid fire extinguishers (fourth revision) 19. 884: 1985 Specification for first aid hose reel for fire fighting (first revision) 20. 15105 2002 Design and installation of fixed automatic sprinkler fire extinguishing system 21. 15325: 2003 Design and installation of fixed automatic high and medium velocity water spray system —Code of practice 22. 12835 (Part 1) : 1989 Design and installation of fixed foam fire extinguishing system- Code of practice: Part 1 Low expansion foam 23. 15528: 2004 Gaseous fire extinguishing systems-Carbon dioxide, total flooding and local application (sub-floor and in-cabinet), high and low floor pressure (refrigerated) systems 24. 15519: 2004 Water mist fire protection systems - System design, installation and commissioning-Code of Practice 25. 15493: 2004 Gaseous fire extinguishing Systems-General requirements 15497: 2004 Gaseous fire extinguishing systems-IG 01 extinguishing systems 15501: 2004 Gaseous fire extinguishing systems--IG 541 extinguishing systems 15505: 2004 Gaseous fire extinguishing systems HCFC Blend A 15506: 2004 Gaseous fire extinguishing systems -IG 55 extinguishing systems 15517: 2004 Gaseous fire extinguishing Systems HFC 227 ea (Hepta fluoro propane) extinguishing systems 15525:2004 Gaseous fire extinguishing systems-IG 100 extinguishing systems 26. 2189: 2008 Code of practice for selection, installation and maintenance of automatic fire detection and alarm system (fourth revision) 2190: 2010 Code of practice for selection, installation and maintenance of portable first-aid fire extinguishers (fourth revision) 3844: 1989 Code of practice for installation and maintenance of internal fire hydrants and hose reels on premises (first revision) 9668: 1990 Code of practice for provisión and maintenance of water supplies for fire fighting 13039: 1991 Code of practice for provision and maintenance of external hydrant system 13039; 2014 External hydrant systems- Provision and maintenance- Code of practice 27. 4878 1986 Byelaws for construction of cinema buildings (first revision) Tripura Fire Safety Rules, 2026 Page 138 of 169 28. 2726 1988 Code of practice for fire safety of industrial buildings : Cotton ginning and pressing (including cotton seed delintering) factories (first revision) 3034 1993 Code of practice for fire safety of industrial buildings: Electrical generating and distributing stations (second revision) 3594: 1991 Code of practice for fire safety of industrial buildings: General storage and warehousing including cold storage (first revision) 3595: 1984 Code of practice for fire safety of industrial buildings: Coal pulverizers and associated equipment (first revision) 3836: 2000 Code of practice for fire safety of industrial buildings: Jute mills (second revision) 4209: 2013 Code of safety for chemical laboratories (second revision) 4226: 1988 Code of practice for fire safety of industrial buildings: Aluminium/Magnesium powder factories (first revision) 4886: 1991 Code of practice for fire safety of industrial buildings Tea factories (first revision) 6329: 2000 Code of practice for fire safety of industrial buildings: Sawmills and wood works (first revision) 9109: 2000 Code of practice for fire safety of industrial buildings: Paint and Varnish factories 11457 (Part 1): 1985 Code of practice for fire safety of chemical industries: Part 1 Rubber and plastic 29. 13039: 2014 External hydrant systems-Provision and maintenance- Code of practice 30. IS 14665 (Part 1-5): 2000 Electric Traction Lifts 31. 15259: 2022 Installation and Maintenance of Home Lifts - Code of Practice 32. 17900(Part 2):2022 Lifts for the Transport of Persons and Goods - Part 2 Design Rules, Calculations, Examinations and Tests of Lift Components 33. 3861 : 2002 Method of measurement of plinth, carpet and rentable areas of buildings (second revision) 34. 15330 : 2003 Installation and maintenance of lifts for handicapped persons - Code of practice 35. 19328 : 2025 Fire Resistant Glass 36. 2546 : 1974 (Reaffirmed 2005) Specification for galvanized mild steel fire bucket [CED 22: Fire Fighting] Tripura Fire Safety Rules, 2026 Page 139 of 169 FORM – A [See sub-rule (1) of rule 9] Certificate from empanelled agency regarding the compliance of the Fire Prevention and Life Safety Measures in accordance with the proposed Fire Safety Recommendation to be submitted by the owner or occupier for obtaining Fire Safety Certificate (Fire NOC) C E R T I F I C A T E Certified that I/We have carried out inspection of the Fire Prevention and Life Safety Measures installed in the following building or premises, namely:-- ________________________________________________________________________________ _________________________________________________________________________________________ I/We further certify that the Fire Prevention and Life Safety measures as per Fire Safety Recommendation installed in the above mentioned buildings or premises are properly maintained and in working conditions as required under the provisions of the “Tripura Fire Safety Rules, 2026” in accordance with the “Tripura Fire and Emergency Services Act, 2022”. The details of the inspection of installations carried out by me/us are mentioned in the report appended herewith along with Check List in Schedule- II. _______________________________________ Place: Signature of the empanelled agency Date: Full Name: _____________________________ License No. ____________________________ Contact No. ____________________________ Official Seal _________________________________ Signature with date (owner or occupier) Full Name: *Note. For each building a separate certificate in Form 'A' has to be submitted. Tripura Fire Safety Rules, 2026 Page 140 of 169 FORM – B [See sub-rule (2) of rule 9] Certificate from empanelled agency in every year stating all the recommended/installed fire prevention and life safety measures are well maintained and in efficient condition to be submitted by the owner or the occupier for validity extension of Fire Safety Certificate (Fire NOC) C E R T I F I C A T E Certified that I/We have carried out inspection of the Fire Prevention and Life Safety Measures installed in the following building or premises, namely:-- ________________________________________________________________________________ _________________________________________________________________________________________ I/We further certify that the Fire Prevention and Life Safety measures as per Fire Safety Recommendation installed in the above mentioned buildings or premises are properly maintained and in working conditions as required under the provisions of the “Tripura Fire Safety Rules, 2026” in accordance with the “Tripura Fire and Emergency Services Act, 2022”. The details of the inspection of installations carried out by me/us are mentioned in the report appended herewith along with Check List in Schedule- II. _______________________________________ Place: Signature of the empanelled agency Date: Full Name: _____________________________ License No. ____________________________ Contact No. ____________________________ Official Seal _________________________________ Signature with date (owner or occupier) Full Name: *Note. For each building a separate certificate in Form 'B' has to be submitted. Tripura Fire Safety Rules, 2026 Page 141 of 169

Previous and next

All provisions of Tripura Fire Safety Rules 2026

Questions people ask

Is annexure M of Tripura Fire Safety Rules 2026 still in force?

No repeal of Tripura Fire Safety Rules 2026 is recorded.