Regulation 38, The Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023: Provisions for supply and use of electricity in multi-storeyed building more than fifteen metre in height
The Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 - Regulation 38
Text of regulation 38
Provisions for supply and use of electricity in multi-storeyed building more than fifteen metre in height
38. Provisions for supply and use of electricity in multi-storeyed building more than fifteen metre in height. –
(1) The connected load and voltage of supply above which inspection is to be carried out by an Electrical
Inspector for a multi-storeyed building of more than fifteen metre height shall be notified by the Appropriate
Government.
(2) Before making an application for commencement of supply or recommencement of supply after an
installation has been disconnected for a period of six months or more, the owner or occupier of a multi-storeyed
building shall give not less than thirty days notice in writing to the Electrical Inspector specifying therein the
particulars of installation and the supply of electricity shall not be commenced or recommenced within this
period, without the approval in writing of the Electrical Inspector.
(3) The following safety measures shall be provided in the multi-storeyed buildings of more than fifteen metre
height and other premises such as airports, hospitals, hotels, places of entertainment, places of worship, cultural
centers, stadium, academic buildings, test labs, industrial installations, installation with explosive or flammable
material, railway or metro stations and other public buildings, namely: –
(i) the supplier or owner of the installation shall provide at the point of commencement of supply a
suitable isolating device with cut-out or breaker to operate on all phases except neutral in the three-phase,
four-wire circuit and fixed in a conspicuous position at not more than 1.70 metre above the ground so as to
completely isolate the supply to the building in case of emergency;
(ii) the owner or occupier of a multi-storeyed building shall ensure that electrical installations and works
inside the building are carried out and maintained in such a manner as to prevent danger due to shock and fire
hazards, and the installation is carried out as per the relevant standards;
(iii) no other service pipes and cables shall be taken through the ducts provided for laying of power cables
and all ducts provided for power cables and other services shall be provided with fire barrier at each floor
crossing;
(iv) the Fire Retardant Low Smoke and Low Halogen power cables shall be used in building of more than
fifteen metre height as per relevant standards:
Provided that Halogen Free Flame Retardant power cables as per the relevant standards shall be used
in airports, hospitals and hotels irrespective of height;
(v) distribution of electricity to the floors shall be done using bus bar trunking system;
(vi) lightning protection of the building shall be as per the relevant standards;
(vii) verification of electrical wiring of the building shall be carried out as per the relevant standards; and
(viii) electricity meter shall not be installed in the passage of staircase.