Regulation 124, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: General safety requirements for electric vehicle charging station
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 124
Text of regulation 124
General safety requirements for electric vehicle charging station
124. General safety requirements for electric vehicle charging station. – (1) Electric vehicle charging stations shall
be provided with separate protection against the overload of input supply and output supply as per relevant
standards.
(2) Socket-outlet of supply of electric vehicle charging points shall be installed at least 800 millimetre above
the finished ground level.
(3) A cord extension set or second supply lead shall not be used in addition to the supply lead for the
connection of the electric vehicle to the charging point and shall not be used as a cord extension set.
(4) No adaptor shall be used to connect a vehicle connector to a vehicle inlet.
(5) The distance between the charging point and the connection on the electric vehicle shall not be more than
five metre during charging.
(6) The portable socket outlets shall not be permitted for electric vehicle charging.
(7) The lightning protection system shall be provided for the electric vehicle charging stations as per relevant
standards.
(8) The electric vehicle charging station shall be equipped with a protective device against the uncontrolled
reverse power flow from electric vehicle to the charging point.
(9) One second after disconnecting the electric vehicle from the supply mains, the voltage between accessible
conductive parts or any accessible conductive part and earth shall be less than or equal to 42.4 Vpeak (30 Vrms), or
60 V DC, and the stored energy available shall be less than 20 J:
Provided that, if the voltage is greater than 42.4 Vpeak (30 Vrms) or 60 V DC, or the energy is 20 J or
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 145
more, a warning label shall be attached in a conspicuous position on the charging stations.
(10) A vehicle connector used for direct current charging shall be locked on the vehicle inlet if the voltage is
higher than 60 V DC and in case of charging system malfunction, a means for safe disconnection shall be
provided.
(11) The electric vehicle charging point shall disconnect supply of electricity to prevent overvoltage at the
battery, if the output voltage exceeds maximum voltage limit permissible for the vehicle.
(12) The electric vehicle charging points shall not energise the charging cable when the vehicle connector is in
unlock position.
(13) The electric vehicle connector shall not unlock if the voltage between the vehicle connector and the earth is
more than 60 V.
(14) Safety clearance between the oil or gas dispenser and electric vehicle charging point shall be as per the
order issued by the Authority.
(15) Only four core cable shall be used for charging points which require three phase power supply.
(16) Underground cables shall not cross the underground oil tank or oil pipeline.
(17) Underground cables through the charging area or vehicles passage shall be avoided and if provided shall be
at a minimum depth of one metre from the finished ground surface.
Previous and next