Regulation 108, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Cables
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 108
Text of regulation 108
Cables
108. Cables. – All cables, other than flexible cables for portable or transportable apparatus, shall fulfill the following
requirements, namely: –
(i) all such cables, other than the outer conductor of a concentric cable, shall be covered with insulating
material and shall be efficiently protected from mechanical damage and supported at sufficiently frequent
intervals and in such a manner as to prevent damage to such cables;
(ii) (a) except as provided in clause (iii) no cables other than concentric cables or single core or two core or
multi core cables protected by a metallic covering and which contain all the conductors of a circuit shall be
used where the voltage exceeds 125 V or when an Inspector considers that there is risk of igniting gas or coal
dust or other inflammable material, and so directs;
(b) the sheath of metal-sheathed cables and the metallic armouring of armoured cables shall be of a
thickness not less than that recommended from time to time in the relevant standard of the Bureau of
Indian Standards;
(iii) where a voltage exceeding 250 V but not exceeding 650 V direct current system is used, two single core
cables may be used for any circuit provided that their metallic coverings are bonded together by earth
conductors so placed that the distance between any two consecutive bonds is not greater than thirty metre
measured along either cable;
(iv) The metallic covering of every cable shall be. –
(a) electrically and mechanically continuous throughout;
(b) earthed, if it is required, to be earthed by a connection to the earthing system of conductivity;
(c) efficiently protected against corrosion where necessary;
(d) of a conductivity at all parts and at all joints at least equal to fifty per cent of the conductivity of the
largest conductor enclosed by the said metallic covering; and
(e) where there may be risk of igniting gas, coal-dust, or other inflammable material, so constructed as
138 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
to prevent, as far as practicable, the occurrence of open sparking as the result of any fault or leakage from
live conductors;
(v) cables and conductors where connected to motors, transformers, switchgear and other apparatus, shall be
installed so that, -
(a) they are mechanically protected by securely attaching the metallic covering to the apparatus; and
(b) the insulating material at each cable end is efficiently sealed so as to prevent the diminution of its
insulating properties;
(vi) where necessary to prevent abrasion or to secure gas-tightness, properly constructed glands or bushes
shall be provided;
(vii) unarmoured cables or conductors shall be conveyed either in metallic pipes or metal casings or suspended
from efficient insulators by means of non-conducting materials which will not cut the covering and which shall
prevent contact with any timbering or metal work and if separate insulated conductors are used, they shall be
installed at least 3.75 cm apart and shall not be brought together except at lamps, switches and fittings.